Re: SDP -2013 -00063 Cole's Import Specialists
Dear Ms. Ray:
We have reviewed the final site plan for Cole's Import Specialists dated 12-2.13 with revisions dated 10.30.14 and
1!9.15 as submitted by Meridian Planning Group, LLC and offer the following comments.
1. The proposed entrance reflects the requests by VDOT for a right- in/right -out entrance.
2. The left -turn arrow currently shown in the center lane of Rio Road should be eradicated.
3. Sheet 4 of 10 shows a TC spot elevation of 29.6 at the potential inter - parcel connection with TMP 45-
1 OOA. However, the elevation at the property line approximately 4' from this Iocation is approximately
527.47. 1 question the ability of parcel 45 -100A making this connection upon development within the
casement shown on the site plan. Additional casement should be provided to allow for this connection or
the pavement and curbing should be constructed all the way to the property Iine as part of this site
development.
Maintenance of Traffic Plan
I. TTC -16 references various notes on the detail. The page from the VA Work Area Protection Manual that
has these notes should be included on the plan.
2. The location of the Shadow Vehicle in relation to the work area should be shown on the plan.
3. The buffer space begins at the shadow vehicle as shown on the TTC.
4. Per Table 61-1-3, the length of the buffer space is 250' to 260' for a posted speed limit of 35 mph.
5. The length of the channelizing taper and shoulder taper needs to be dimensioned in accordance with the
table on page 61-1-38 of the VA Work Area Protection Manual.
6. Per note 2 on page 61-1-38 of the VA Work Area Protection Manual, the spacing between the signs should
be between 350' and 500'. While we have some flexibility on the spacing of these signs, 100' is too close.
7. The Maintenance of Traffic Plan will need to be approved by NWRO staff prior to site plan approval.
If you need additional information concerning this project, please do not hesitate to contact me at (434) 422 -9782.