HomeMy WebLinkAboutARB201500120 Staff Report 2015-11-09ARCHITECTURAL REVIEW BOARD STAFF REPORT
Project #/Name
ARB -2013-26: Avinity Phase 2 Townhomes Amendment
Review Type
Amendment to an approved Certificate of Appropriateness
Parcel Identification
09100000001400
Location
2085 Avinity Loop, on the east side of Avon Street, north of Avinity Drive and south of Cale Elementary School
Zoned
Planned Residential Development (PRD)/Entrance Corridor (EC)
Owner/Applicant
Avon Properties LLC/Williams Mullen (Ashley Davies)
Magisterial District
Scottsville
Proposal
To revise the architectural design of the townhouses on lots 1 through 9.
Context
The Avon Street corridor is characterized by a mix of single family, multi -family, commercial and light industrial
development. The Cale Elementary School is located immediately to the north. The clubhouse and townhouses east of
units 18 and 26 have been built.
Visibility
The EC elevations and the side elevations of units 1 through 9 will be readily visible from the Avon Street Entrance
Corridor. The Avinity Drive elevations of units 19 through 26 and the west elevation of unit 19 will be visible from
the EC. The north elevations of units 10 and 14 through 18 will have some visibility from the EC. The existing
wooded area on the Cale site is very thin and can be seen through. Trees to be added on the Avinity site will
somewhat reduce the visibility of those elevations. The westernmost blocks of townhouses, north and south of the
clubhouse, are currently visible at a distance from the EC.
ARB Meeting Date
November 16, 2015
Staff Contact
Margaret Maliszewski
PROJECT HISTORY
DATE
APPLICATION/REVIEW
RESULT
7/29/2015
ARB -2015-97: Sip
Application for subdivision si s received and under review.
3/20/2015
SDP -2014-62
Minor site plan amendment approved.
1/20/2011
ARB -2010-121
Overall residential development approved.
10/3/2010
ARB -2010-87
I Preliminary review of the overall residential development completed.
3/19/2007
ARB -2007-11
ARB advisory comments provided on the rezoning, comments provided on the prelimina site plan.
ANALYSIS
REF
GUIDELINE
ISSUE RECOMMENDATION
Structure design
1
The goal of the regulation of the design of development
The proposed architectural design reflects Revise the architectural
within the designated Entrance Corridors is to insure that new
elements of traditional architecture of the design (materials, forms,
development within the corridors reflects the traditional
area in the traditional townhouse form with a details, etc.) to establish a
architecture of the area. Therefore, it is the purpose of ARB
narrow width and 3 -story height, bracketed front for the Avon Street
review and of these Guidelines, that proposed development
hoods over some entrances, and emphasized elevations.
within the designated Entrance Corridors reflect elements of
window heads. The design also uses non -
design characteristic of the significant historical landmarks,
traditional elements, including a rooftop Revise the terrace level
buildings, and structures of the Charlottesville and Albemarle
structure, and a wooden rooftop terrace level parapet to achieve a more
area, and to promote orderly and attractive development
parapet that does not extend down to the traditional and
within these corridors. Applicants should note that replication
third -story cornice. These features appear coordinated appearance.
of historic structures is neither required nor desired.
"added on" and aren't completely
coordinated with the character of the main Revise the design of the
2
Visitors to the significant historical sites in the Charlottesville
and Albemarle area experience these sites as ensembles of
buildings. terrace level structures to
buildings, land, and vegetation. In order to accomplish the
significantly increase
integration of buildings, land, and vegetation characteristic of
The overall appearance of the EC elevations coordination with the
these sites, the Guidelines require attention to four primary
is of the back of a building that doesn't main buildings and to
factors: compatibility with significant historic sites in the
sufficiently address the street. The EC appear as a fully
area; the character of the Entrance Corridor; site development
elevations have a reduced level of materials integrated element of the
and layout; and landscaping.
compared to the front elevation. The EC residential design.
elevations are all faced with siding; there is
3
New structures and substantial additions to existing structures
should respect the traditions of the architecture of historically
no brick. The structure and detailing of the
significant buildings in the Charlottesville and Albemarle
balconies and the concrete patios (with
area. Photographs of historic buildings in the area, as well as
optional screened porches) are typical of rear
drawings of architectural features, which provide important
townhouse elevations. The simple support
examples of this tradition are contained in Appendix A.
posts (sometimes placed without respect to
lower level fenestration) and the character of
4
The examples contained in Appendix A should be used as a
guide for building design: the standard of compatibility with
the ground level doors emphasize the "back
the area's historic structures is not intended to impose a rigid
of building" appearance. Choosing the
design solution for new development. Replication of the
optional fireplace at the main (balcony) level
design of the important historic sites in the area is neither
adds an exterior element on the EC elevation
intended nor desired. The Guideline's standard of
that is not fully coordinated with the building
compatibility can be met through building scale, materials,
design. A dryer vent is located above the
and forms which may be embodied in architecture which is
main level on the EC elevation, reinforcing
contemporary as well as traditional. The Guidelines allow
the "back of building" appearance. The
individuality in design to accommodate varying tastes as well
fireplace and window options can result in
as special functional requirements.
un -aligned windows on the EC elevations.
This situation does not occur on the front
9
Building forms and features, including roofs, windows,
doors, materials, colors and textures should be compatible
elevations. The proximity and orientation of
with the forms and features of the significant historic
the townhouses to Avon Street requires a
buildings in the area, exemplified by (but not limited to) the
design with a positive presentation to the
buildings described in Appendix A [of the design guidelines].
street. That presentation does not exist in the
The standard of compatibility can be met through scale,
proposed design.
materials, and forms which may be embodied in architecture
which is contemporary as well as traditional. The replication
of important historic sites in Albemarle County is not the
objective of these guidelines.
5
It is also an important objective of the Guidelines to establish
The applicant has indicated that the proposed
The recommendations on
a pattern of compatible architectural characteristics
design is for units 1 through 9 (the units that
the design of units 1
throughout the Entrance Corridor in order to achieve unity
front the EC) and the owner is still
through 9 also apply to
and coherence. Building designs should demonstrate
considering the re -design of units 10 through
the design of units 19
sensitivity to other nearby structures within the Entrance
26.
through 26 and the north
Corridor. Where a designated corridor is substantially
elevations of units 10 and
developed, these Guidelines require striking a careful balance
14 through 18.
between harmonizing new development with the existing
character of the corridor and achieving compatibility with the
significant historic sites in the area.
10
Buildings should relate to their site and the surrounding
context of buildings.
11
The overall design of buildings should have human scale.
The projections forward and back, the
None.
Scale should be integral to the building and site design.
windows and doors, the siding and brick, and
the balconies help establish human scale in
the townhouses.
12
Architecture proposed within the Entrance Corridor should
There are currently no townhouses fronting
None.
use forms, shapes, scale, and materials to create a cohesive
the Avon Street corridor. Single family
whole.
residences do front the corridor in a few
places. Those residences use brick and siding
and traditional residential forms and scale.
The proposed townhouse design is a different
form but is not incompatible with those
existingbuildings.
13
Any appearance of "blankness" resulting from building
The side elevations of the townhouses show
Revise the architectural
design should be relieved using design detail or vegetation, or
only three windows and are mostly blank.
design of the end units to
both.
This degree of blankness is not appropriate
eliminate blankness by
for the EC.
adding windows and/or
architectural detailing.
14
Arcades, colonnades, or other architectural connecting
There are no physical connecting devices to
None.
devices should be used to unify groups of buildings within a
unify townhouse blocks. (None were
development.
previously proposed.) The buildings are
unified by the use of compatible forms and
materials.
15
Trademark buildings and related features should be modified
The applicant has indicated that this model
None.
to meet the requirements of the Guidelines.
has not yet been constructed.
16
Window glass in the Entrance Corridors should not be highly
Information on VLT and VLR has not been
Ensure that the window
tinted or highly reflective. Window glass in the Entrance
provided on the drawings.
glass in the townhouses
Corridors should meet the following criteria: Visible light
meets the following
transmittance (VLT) shall not drop below 40%. Visible light
requirements and add a
reflectance (VLR) shall not exceed 3001o. Specifications on the
note to the architectural
proposed window glass should be submitted with the
drawings indicating such:
application for final review.
Visible light
transmittance (VLT) shall
not drop below 40%.
Visible light reflectance
(VLR) shall not exceed
30%.
Accessory structures and equipment
17
Accessory structures and equipment should be integrated into
The elevation drawings suggest that an
Revise the elevation
the overall plan of development and shall, to the extent
HVAC unit is located on the EC side of the
drawings to show that the
possible, be compatible with the building designs used on the
building. The plan shows the units on the
HVAC units are on the
site.
other side of the building. The EC side of the
Avinity Lane and Avinity
18
The following should be located to eliminate visibility from the
townhouses is too visible a location for
Place sides of the
Entrance Corridor street. If, after appropriate siting, these
HVAC units.
townhouses.
features will still have a negative visual impact on the Entrance
Corridor street, screening should be provided to eliminate
Choosing the fireplace option at the main
See recommendations
visibility. a. Loading areas, b. Service areas, c. Refuse areas,
(balcony) level results in an exterior element
under #1 and #32.
d. Storage areas, e. Mechanical equipment,
on the EC elevation that is not fully
f. Above -ground utilities, and g. Chain link fence, barbed
coordinated with the building design. A
wire, razor wire, and similar security fencing devices.
dryer vent is located above the main level on
the EC elevation, reinforcing the "service"
19
Screening devices should be compatible with the design of
the buildings and surrounding natural vegetation and may
appearance of this side of the building.
consist of: a. Walls, b. Plantings, and c. Fencing.
The rooftop structure has an "added on"
appearance that is not fully coordinated with
the main building.
Utility connections are made at the lower
level of the side elevations. The landscape
plan does not include plants for screening
these elements.
20
Surface runoff structures and detention ponds should be
No changes proposed.
None.
designed to fit into the natural topography to avoid the need for
screening. When visible from the Entrance Corridor street,
these features must be fully integrated into the landscape. They
should not have the appearance of engineered features.
21
The following note should be added to the site plan and the
The note does not appear on the architectural
Add the standard
architectural plan: "Visibility of all mechanical equipment
drawings.
mechanical equipment
from the Entrance Corridor shall be eliminated."
note to the architectural
drawings.
22-
Lighting
No street lights were proposed in this
None.
31
development. Residential scale building -
mounted wall lights are proposed. Cut sheets
indicate fixtures with incandescent lamps
emittin less than 3000 lumens.
32-
Landscaping
No landscape changes are proposed. Plants
Revise the landscape plan
38
could be added to screen lower level utility
to include plants to screen
connections.
the utility connections.
Development pattern
6
Site development should be sensitive to the existing natural
The approved site layout for this
I Revise the architectural
landscape and should contribute to the creation of an
development places the townhouses 30-40'
design (materials, forms,
organized development plan. This may be accomplished, to
from the property line and 50-65' from the
details, etc.) to establish a
the extent practical, by preserving the trees and rolling terrain
paved street. The townhouse units are
front for the Avon Street
typical of the area; planting new trees along streets and
situated nearly parallel to the EC street. A
elevations.
pedestrian ways and choosing species that reflect native
sidewalk is to be built along the frontage,
forest elements; insuring that any grading will blend into the
and steps are provided from the sidewalk up
surrounding topography thereby creating a continuous
to each unit. In the original approved design,
landscape; preserving, to the extent practical, existing
steps led to the front porch of each
significant river and stream valleys which may be located on
townhouse. In the current proposal, the steps
the site and integrating these features into the design of
lead to the rear patio of each townhouse, with
surrounding development; and limiting the building mass and
the patio located below a main level balcony.
height to a scale that does not overpower the natural settings
The proximity and orientation of the
of the site, or the Entrance Corridor.
townhouses to Avon Street requires a design
with a positive presentation to the street.
39
The relationship of buildings and other structures to the
Entrance Corridor street and to other development within the
That presentation does not exist in the
corridor should be as follows:
proposed design.
a. An organized pattern of roads, service lanes, bike paths,
and pedestrian walks should guide the layout of the site.
b. In general, buildings fronting the Entrance Corridor street
should be parallel to the street. Building groupings should be
arranged to parallel the Entrance Corridor street.
c. Provisions should be made for connections to adjacent
pedestrian and vehicular circulation systems.
d. Open spaces should be tied into surrounding areas to
provide continuity within the Entrance Corridor.
e. If significant natural features exist on the site (including
creek valleys, steep slopes, significant trees or rock
outcroppings), to the extent practical, then such natural
features should be reflected in the site layout. If the
provisions of Section 32.5.6.n of the Albemarle County
Zoning Ordinance apply, then improvements required by that
section should be located so as to maximize the use of
existing features in screening such improvements from
Entrance Corridor streets.
f. The placement of structures on the site should respect
existing views and vistas on and around the site.
40-
Site Grading
No grading changes are proposed.
None.
44
SUMMARY OF RECOMMENDATIONS
Staff recommends the following as the primary points of discussion:
1. The appearance of the EC elevations; the lack of a "front" facing the EC.
2. The appearance of the terrace level elements: the parapet and the rooftop structure.
3. The blankness of the side elevations.
4. The visibility and level of review required for units 10 through 26.
Staff recommends the following changes to the proposal:
1. Revise the architectural design (materials, forms, details, etc.) to establish a front for the Avon Street elevations.
2. Revise the terrace level parapet to achieve a more traditional and coordinated appearance.
3. Revise the design of the terrace level structures to significantly increase coordination with the main buildings and to appear as a fully integrated
element of the residential design.
4. Revise the architectural design of the end units to eliminate blankness by adding windows and/or architectural detailing.
5. Ensure that the window glass in the townhouses meets the following requirements and add a note to the architectural drawings indicating such:
Visible light transmittance (VLT) shall not drop below 4001o. Visible light reflectance (VLR) shall not exceed 3001o.
6. Revise the elevation drawings to show that the HVAC units are on the Avinity Lane and Avinity Place sides of the townhouses, with no visibility
from the EC.
7. Add the standard mechanical equipment note to the architectural drawings. "Visibility of all mechanical equipment from the Entrance Corridor shall
be eliminated."
8. Revise the landscape plan to include plants to screen the utility connections. This will require an amendment to the site plan.
9. Note that these recommendations apply to any future re -design of units 19 through 26 and the north elevation of units 10 and 14 through 18.
This report is based on the following submittal items:
Sheet #
Drawing Name
Drawin Date/Revision Date
Minor amendment plan
6/18/2015
Color rendering of front elevations
-
1
Front Elevation
9-9-15
2
Side Elevations
9-9-15
3A
Rear Elevations
9-11-15
4A
Foundation Plan on Grade
9-11-15
5A
Lower Level
9-11-15
6A
Main Level
9-11-15
7
Upper Level
9-10-15
8
Rooftop Terrace Level
9-10-15
9
Electrical Plan
9-10-15
10
Details
8-18-15