September 30, 2014
Mike Myers
Dominion Engineering
172 S. Pantops Drive
Charlottesville, Virginia 22911
RE:SDP-2014-057 and SUB2014-136 Cascadia BI 1-3 Preliminary Plat and Initial Site Plan
Mr. Myers:
The Agent for the Board of Supervisors hereby grants administrative approval to the above referenced
site plan and subdivision plat.
This approval shall be valid for a period of five (5)years from the date of this letter, provided that the
developer submits a final site plan for all or a portion of the site within one (1)year after the date of this
letter as provided in section 32.4.3.1 of Chapter 18 of the Code of the County of Albemarle and 14-226
of the Subdivision Ordinance of the County Code, and thereafter diligently pursues approval of the final
site plan and subdivision plat.
An Erosion and Sediment Control Permit may be issued after the following approvals are received:
1. Approval an Erosion and Sediment Control Plan meeting the requirements of Chapter 17 of the
Code of the County of Albemarle.
2. Approval of a Stormwater Management Plan meeting the requirements of Chapter 17 of the
Code.
3. Approval of all easements for facilities for stormwater management and drainage control.
4. Approval of a mitigation plan for the disturbance of Water Protection Ordinance buffers.
5. Submittal of a tree conservation checklist.
The final site plan will not be considered to have been officially submitted until the following items are
received:
1. A final site plan that satisfies all of the requirements of section 32.6 of Chapter 18 of the Code.
2. A fee of$1,500.
The final subdivision plat will not be considered to have been officially submitted until the following
items are received:
1. A final subdivision plat that satisfies all of the requirements of 14-226 of the Subdivision
Ordinance.
2. A fee of$1,230.
1
NOP, NNW
Please submit 10 copies of the final plans to the Community Development Department.The assigned
Lead Reviewer will then distribute the plans to all reviewing agencies (except for ACSA, please submit
copies directly to them as stated in their comments). Once you receive the first set of comments on the
final site plan, please work with each reviewer individually to satisfy their requirements.
The final site plan and subdivision plat will not be approved until the following conditions are met:
The Department of Community Development shall not accept submittal of the final site plan and
subdivision plat for signature until tentative approvals for the following conditions have been obtained:
Planning Division Approval of(2 copies):
1. A site plan meeting all the requirements of section 32.6 of Chapter 18 of the Code.
2. A landscape plan meeting the requirements of section 32.7.9 of Chapter 18 of the Code,
including a tree conservation checklist.
3. A plat meeting all the requirements for final subdivision plats per the subdivision ordinance.
4. [14-302 (B)(5)]Zoning classification. Provide the ZMA number on the notes sheet (ZMA2002-
004).
5. [14-401] Double Frontage Lots. An exception is needed for Lots 30-37 for double frontage.
Additional planting will also be required. "Double frontage lots for single family detached and
attached residential uses are prohibited. The prohibition of double frontage lots may be varied
or excepted by the agent as provided in section 14-203.1. Double frontage lots shall be
screened as provided in section 14-419."
6. [32.5.2 (c)] Will this section be phased? If so, show the phasing lines.
7. [Variation#5] The variation request for the garages did not include the elevation or details as
stated. Provide those details for review.Also, as part of this variation,the front porches may
need to be extended the full length of the house.
8. Approval of the variation requests by the Board of Supervisors. Once the variation requests have
been revised per these comments, resubmit so that they can be scheduled for the Board
meeting.
9.
Please contact Megan Yaniglos at 296-5832 if you have questions or require additional information.
Engineering Division Approval of(1 copy of site plan;WPO plan number stated in application):
A. Initial Site Plan (SDP201400057)
1. Show matchlines on sheets.
2. There are items from blocks 4-7 shown as existing on this plan, which means that this
application will be approvable once the subdivision, site plan and wpo plan from blocks 4-7 are
approved. Please clarify if this is how you would like to proceed. Also,there is a new grading
plan for lots along the proposed Delphi Lane extension and commercial bldg area. This area has
changed since the approved WPO2013-32. Please address how you would like to proceed with
coordination of that plan. For example, a sediment trap should be placed south of the proposed
Cascadia Drive. What are revisions to the erosion control measures as the temporary
conveyance channel is removed and Dephi Lane is constructed?
3. In conjunction with comment 2,the SWM Pond#2 is shown as existing. Under the new VSMP
regulations, as-builts shall be provided for existing SWM facilities. Since the facility is not yet
built, please clarify coordination of these plans.
4. There should be no disturbance within the SWM Pond#2 easement. It appears the layout of the
commercial site shows disturbance within this easement. Please address.
5. The road plan shall be approved by VDOT.
6. Parking should be separated from entrances and street. Remove the parallel parking near the
commercial bldg. One recommendation is to rotate the entire parking layout by 90 degrees and
2
remove the choked entrance or flip the bldg and parking lot to change entrance location.
7. I do not recommend the street ending as shown near lot 22. I recommend a radius of 200'to
avoid this stub out.
8. Show and label the managed slopes.
9. All retaining walls on managed slopes should adhere to section 30.7.5[a] of Albemarle County
Code.
10. Show design of retaining wall.
11. Revise the road layout for lots 106-111 and remove turnarounds and stubouts. Show a 200'
radius and connect the Knoll Lane to Delphi Lane.
12. Provide drainage computations.
B) Preliminary Plat(SUB201400136)
1. An approved and bonded road plan for blocks 1-3 will be required prior to the approval of this
plat.
2. VSMP/WPO may need to be updated per comment 2 under the initial site plan comment.
Please contact Michelle Roberge at 296-5832 if you have questions or require additional information.
ACSA approval to include(3 copies):
The ACSA has determined certain items that will be evaluated during the construction review that the
applicant should be aware of:
1. Submit 3 copies of the final site plan directly to the ACSA(ATTN:Jeremy Lynn, P.E.) with water
and sewer data sheets attached for construction review and approval.
2. Lots 112-120 appear to share a private force main.The ACSA does not allow shared private force
mains or laterals. Update the utilities to reflect one force main per lot.
3. Include utility profile views (including the existing 8" sanitary sewer).
Please contact Alex Morrison at 977-4511 ext 116 if you have questions or require additional
information.
E911 approval to include(1 copy):
1. The road names, 'Village Drive' and 'Meadow Lane' are not acceptable road names currently.
The road name of'Village Drive' should remain the same as 'Delphi Drive' because it is the
logical extension of the existing 'Delphi Drive'. The name 'Meadow' has been used five or more
times to begin a road name and is unacceptable. The other road names found on the plan
('Knoll Lane', 'Cascadia Drive', 'Delphi Lane', and 'Delphi Drive') are all acceptable road names.
The applicant should contact this office with a list of three (3) proposed replacement names for
'Meadow Lane'.
Please contact Andrew Slack at 296-5832 if you have questions or require additional information.
Fire& Rescue approval to include (1 copy):
1. Streets shall provide a 20 ft unobstuctred travelway for fire access. Please mark streets "No
Parking Fire Lane"to ensure the 20 ft travelway.
Please contact Robbie Gilmer at 296-5833 if you have questions or require additional information.
ARB approval to include(1 copy):
3
Num. Now
1. Regarding requirements to satisfy the design guidelines as per§ 18-30.6.4(2), (3) and (5):
o Provide large shade trees parallel to all interior roads,40' on center, and 2'/2" caliper at
planting. Shift pipes and utilities to accommodate the required trees.
o Provide 2%2" caliper perimeter parking lot trees for the commercial building in Block 1. Provide
a quantity of trees equivalent to 40' on center, coordinated with the entry park trees and the
retaining wall.
2. Regarding recommendations on the plan as it relates to the guidelines:
o None.
3. Regarding recommended conditions of initial plan approval:
A Certificate of Appropriateness is required prior to final site plan approval. Your next ARB submittal
should include architectural designs and all final review checklist items, and should address the
following comments:
1. Note that a "back of building" appearance will not be appropriate for any buildings visible
from the EC.
2. Provide a site section taken through the EC,the commercial building, and the residential units
above.
3. Include a dumpster screen detail in the plan. Identify the material of the screen on the plan.
Coordinate the screen material with the building material.
4. Add the mechanical equipment note to the plan. "Visibility of all mechanical equipment from
the Entrance Corridor shall be eliminated."
5. If lighting is proposed, provide a complete lighting plan for review.
6. Revise the site plan to show the approved frontage planting for Blocks 4-7.
7. Revise the regular row of shrubs west of stormwater pond#1 to a mix of shrubs in an
irregular layout consistent with the approved planting to the north.
8.Add landscaping at the southwest corner and east end of stormwater pond#1, consistent
with the approved planting to the north,to blend this end of the frontage with the area to the
north.
9. Provide large shade trees parallel to all interior roads,40' on center, 2%z" caliper at planting.
Shift pipes and utilities to accommodate these trees.
10. Provide 2%z"caliper perimeter parking lot trees for the commercial building in Block 1.
Provide a quantity of trees equivalent to 40' on center, coordinated with the entry park trees
and the retaining wall.
11. Revise the plan to show the trees in the back yards of lots 22-29 on the entry park side of the
property line.
12. Add the standard plant health note to the plan. "All site plantings of trees and shrubs shall
be allowed to reach, and be maintained at, mature height;the topping of trees is prohibited.
Shrubs and trees shall be pruned minimally and only to support the overall health of the plant."
13. At the east end of stormwater management pond#1, round contours with a ten foot
minimum radius where they meet the adjacent condition.
14. Indicate on the plan the material and color proposed for the retaining wall. Terrace walls
over 6' tall. Use landscaping to soften the visual impacts of the wall.
15. Include a conservation checklist in the plan. Show tree protection fencing.
4. Regarding conditions to be satisfied prior to issuance of a grading permit:
o Include a conservation checklist in the plan. Show tree protection fencing.
Please contact Margaret Malisewski at 296-5832 if you have questions or require additional
information.
4
Noe
VDOT approval to include (2 copies):
1. The typical section for Meadow Lane is labeled as Meadow Drive.
2. The typical sections for the streets should be identified as either providing on-street parking or
not.
3. The pavement designs will need to be verified by pavement design calculations.
4. The proposed entrance to the commercial lot 120 does not appear to comply with the
commercial entrance design standards as identified in Appendix F of the Road Design Manual.
5. Can storm manhole 5 be replaced with a drop inlet and structure 6 eliminated?
6. Some of the drop inlets appear to be graphically drawn as DI-2 structures. These structures
should be DI-3 structures.
7. It appears that a section of storm sewer between structures 32 and 37 has been omitted from
the plan.
8. A minimum of 90°should be maintained between the upstream and downstream storm sewer
pipes at each structure. It appears that structure 17 should be shifted slightly to provide 90° at
structure 16.
9. As the road plans are developed and reviewed,there may be additional comments.
Please contact Troy Austin at 434-589-5871 if you have questions or require additional information.
Inspection approval to include (1 copy):
1. Provide one van-accessible, barrier-free parking space,with associated curb cut, at the
Commercial Office.
Please contact Jay Schlothauer at 296-5832 if you have questions or require additional information.
If you have any questions about these conditions or the submittal requirements please feel free to
contact me at Extension 3004, myaniglos @albemarle.org.
Sincerely,
Megan Yaniglos
Senior Planner