HomeMy WebLinkAboutSDP201500009 Correspondence 2015-07-16 i 1M Cfli BOH tII4 Warrenton,VA 20186 E N G I N E E R I N G PHONE 540.349.4500 July 16, 2015 Via Hand Delivery County of Albemarle Department of Community Development 401 McIntire Road Charlottesville,VA 22902 Attn: Megan Yaniglos Re: SDP-2015-009 5th Street Station Phase 11 1St Review Comments 5th Street SW& Avon Street Ext. Charlottesville,VA 22902 Albemarle County BE#V122001 Dear Ms. Yaniglos: Bohler Engineering is pleased to submit on behalf of S.J. Collins Enterprises, the revised Final Site Plan for the 5th Street Station in Charlottesville, VA. The following is our comment response letter addressing comments received from you and the agencies dated March 26, 2015. Each comment is addressed and responded to as follows: Department of Transportation—Troy Austin,P.E.: Comment 1: The road plans for Bent Creek Parkway will be reviewed and approved separately from this site plan. This site plan should not be approved until the road plans for Bent Creek Parkway are approved. Response 1: Comment Acknowledged. Bent Creek Parkway plans are now approved. Comment 2: The centerline striping in the entrance shown on sheet 6C should be perpendicular to Bent Creek Parkway. Response 2: The proposed striping has been revised. Please see Sheet 6C. Comment 3: The stop bar shown for the entrance shown on sheet 6C should be parallel to Bent Creek Parkway. Response 3: The proposed stop bar has been revised. Please see Sheet 6C. CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOH LERENGINEERING.COM B O H L E R `'' w► Megan Yaniglos 5th Street Station E N G I N E E R I N G Phase II 1St Review Comments July 16,2015 Page 2 of 11 Comment 4: I do not believe that the one-way lane at the entrance shown on sheet 6C will allow vehicles coming from the lane to turn right onto Bent Creek Parkway without driving over the curb and gutter. The one-way lane appears to be located too close to the connection with Bent Creek Parkway to allow a vehicle to adequately enter the queue perpendicular to Bent Creek Parkway. This condition will be even worse if delivery trucks are the vehicles proposed to be using the lane. Response 4: Comment Acknowledged. Layout has been revised to remove the one-way lane at the entrance shown on 6C. Please see Sheet 6C. Comment 5: The end of proposed right-of-way shown on sheet 7G does not match that shown in the most current road plans that have been provided to this office with a revision date of 3/25/15. Response 5: Right-of-way has been revised to match approved Bent Creek Parkway dated 5/13/15. Please see Sheet 7G. Rivanna Water and Sewer Authority—Victoria Fort,EIT: Comment 1: Since the proposed development will produce over 40,000 gallons per day of wastewater, Phase II of the 5th Street Station Development will require a flow capacity certification from RWSA prior to final site plan approval. Response 1: Comment Acknowledged. Comment 2: Additionally, I wanted to see whether a plan was ever submitted to the County for the Bent Creek Road Bridge over Moores Creek, since this may impact the existing RWSA Moores Creek Interceptor. Response 2: Since the first submission, the Bent Creek Road Bridge over Moore's Creek has been coordinated with RWSA. County of Albemarle Department of Community Development Information Services (E911)—Andy Slack: Comment 1: The applicant should contact this office with a list of proposed road names before final approval is given. This development will need two(2)road names. Response 1: Comment Acknowledged. Road names (Wegmans Boulevard and Merchant Walk Avenue) have been provided. County of Albemarle Fire Rescue—Robbie Gilmer: Comment 1: Please add a note showing that Knox Box's are required on each structure. Response 1: Note has been added to all Site Plan Sheets. Please see Sheets 6C-6G. CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOHLERENGINEERING.COM (�u T '�„r .� Megan Yaniglos V 1 1 L 5`h Street Station E N G I N E E R I N G Phase II 1St Review Comments July 16,2015 Page 3 of 11 County of Albemarle Department of Community Development Engineering—Justin Deel: Comment 1: Please remove all reference sheets(site plans, grading plans, etc.)that contain no changes being proposed with this site plan as well as all E&SC and retaining wall plans. Response 1: Per direction from Megan Yaniglos, plan is required to show the site as a whole (all phases). Comment 2: Please correct your Existing Conditions sheet. Previously approved plans that have not been constructed (Wegmans) or plans that are currently being reviewed (connector road) should not appear as existing conditions. Response 2: Construction of the Overall Phase II portion of the development will begin after construction on the approved Wegmans and Bent Creek Parkway has commenced; therefore,for clarity purposes they are shown as existing. Please see Sheet 3A. Comment 3: Please clarify your phasing plan by clearly illustrating what is part of"56 Street Station Overall Phase II". The phasing needs to coordinate with the E&SC and SWM phasing. This looks like more of a construction phasing plan rather than a design phasing plan and should be titled as such, if so. Response 3: Comment noted. The sheet title has been revised. Please see Sheet 4. Comment 4: Please clearly differentiate areas proposed with this plan from other parts or phases of the site on all plans using line weights and/or shading. Response 4: Overall Phase II Site Plan area has been revised to be clearly defined. Please see Sheet 4. Comment 5: There is a conflicting left turn at the 3-way intersection coming into the western Wegmans parking area. Stop signs are needed for the roads coming from the west and east giving the entering traffic the right-of-way, avoiding back-up to Bent Creek Road. Please correct. Response 5: Comment Noted. The intersection was approved with the Wegmans Final Site Plan; therefore, the Wegmans pavement striping has been turned on for clarity. Please see Sheet 6D. Comment 6: Provide pavement markings, appropriate signing, and splitter islands at the crosswalks for the roundabout. Please define roundabout type and ensure that it meets VDOT design standards. See VDOT Road Design Manual,Appendix F, Section 2. Response 6: Appropriate pavement markings, signage, mountable curb, and striped splitter islands have been added for proposed roundabout. Roundabout is designed and intended to be private, since it is not included in a VDOT road network. Please see Sheet 6D. CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOHLERENGINEERING.COM B O H L E RM Megan Yaniglos 5th Street Station E N G I N E L I Z I N G Phase II 1st Review Comments July 16,2015 Page 4 of 11 Comment 7: Several parking spaces would require backing into or very near to the roundabout upon exiting. Please eliminate these spaces. Ensure that parking spaces leading up to and exiting the roundabout have adequate sight distance and do not interfere with the above requested splitter islands and signs. AASHTO recommends 20 feet from cross-walk. Response 7: Comment Noted. Parking spaces have been eliminated. Please see Sheets 6D and 6E. Comment 8: All rear travelways need to be more clearly defined with pavement markings, bollards, and curbing at building corners, dumpster pads, etc., while maintaining safe sight distances. Note that the rear travelway at the Wegmans is shown as "Site Circulation" on ZMA200900001. Please correct. Response 8: Comment Noted. All proposed travel ways have been revised to show more detail. Please see Sheets 6C-6G. Comment 9: A redesign is needed at the northern most entrance into the shopping center (Sheet 6C). There is inadequate throat length and an unenforceable one-way created by the rear travelway. This could be avoided by eliminating the entrance or routing the rear travelway west toward the parking area. Note that this entrance does not appear on ZMA200900001. Response 9: Comment Acknowledged. Layout has been revised to remove one-way travel way into shopping center. Please see Sheet 6C. Comment 10: Your plan shows at least one, possibly two, drive-throughs. Drive-throughs require special use permits and need to be adequate in length for 5 cars in queue and have a bypass. Please shade these areas out and label them to be approved with future design. Response 10: Comment Noted. A note has been added to the Site Plan sheets stating that the drive-thrus will be approved following a Special Use Permit. Please see note 10, Sheet 6E. Comment 11: Provide stop bars exiting the Wegmans parking lot. Response 11: Stop bars have been added. Please see Sheet 6E. Comment 12: Curb radii on islands should be 3' minimum. Please adjust islands in center parking lot. Response 12: Curb Radii have been revised to be 3' minimum. Please see Sheet 6D-6E. Comment 13: Please check your 10 year storm inlet computations. You're showing a 40'+ spread at A40. This needs to be reduced, if it is not a typo. Response 13: Comment noted. Storm computations have been revised. Please see Sheet 12C. Comment 14: Please explain unmarked area south of building 700. Response 14: A hatch and label has been added to the plans stating that portions of the site, including the unmarked area south of building 700, will be revised with a future submission once the actual tenants are acquired. Please see Note 8, Sheet 6C-6D. CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOHLERENGINEERING.COM HMegan Yaniglos 1 1 I , F, 5th Street Station L R I N G Phase II 1st Review Comments July 16,2015 Page 5 of 11 Comment 15: Please label all retaining walls. Response 15: All retaining walls have been labeled. Please see Sheets 6C-6G. Comment 16: There are duplicate building numbers, please correct. Response 16: Building numbers have been revised. Please see Sheet 4. Comment 17: Note that the road plans and retaining wall plans are not being approved with this application. Response 17: Comment noted. County of Albemarle ARB—Margaret maliszewski: Comment 1: ARB review and approval are required prior to final site plan approval. Schedules, application form and checklists are available at www.alemarke.org/arb. Response 1: Comment Acknowledged. County of Albemarle Department of Community Development—Megan Yaniglos: Comment 1: [32.5.2 (p)] The conservation checklist shown will need to be updated and signed with a new/revised date. Response 1: Conservation checklist has been updated and revised. Please see Sheet 14A. Comment 2: [Proffer 10(D)] Provide engineering documentation that states the Wegman's and the site meet the Best Management Practices to be reviewed and approved by the County's Program Authority. Also provide written documentation that the Thomas Jefferson Foundation has approved the proposed roof material color for the buildings as it is not clear from the prior approval if the roof color was for just the Wegman's or all proposed buildings. Response 2: Best Management Practices for the entire site, including Wegmans, were approved with the WPO and SWM Phase II Plan dated 10/23/14. Also, client intends to use the roof color that was approved for Wegmans by the TJ Foundation on the rest of the buildings on site. Comment 3: [4.17] Proposed lighting must have a half a foot candle or less at the property lines and rights of way. Revise the lighting plan or request a special exception under 4.17.5 Response 3: Comment Acknowledged. Lighting plan has been revised to show 0.5fc or less at the property and ROW lines. Please see Sheets 15A-15J. Comment 4: [32.7.9.7 (a)(2)] It appears that some of the houses within Willoughby will be at the same elevation as the site. Please provide screening of the parking in accordance with this section. Response 4: Comment Acknowledged. Proposed plantings have been added along Bent Creek Parkway in order to provide screening from the Willoughby subdivision. Please see Landscaping Sheets 13C, 13E,and 13G. CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOHLERENGINEERING.COM B o H L E R Megan Yaniglos 5th Street Station E N G I N L E R I N G Phase II 1 S`Review Comments July 16,2015 Page 6 of 11 Comment 5: [ZMA Application Plan] Shown on Sheet 2 of the application plan is a pedestrian connection that would connect Zone `A' and Zone `B'. Provide this connection within the proposed parking areas. Response 5: Comment Noted. Pedestrian connection provided along sidewalk path connecting the Wegmans Site Plan to the Phase II Site Plan. Please see Sheets 6D and 6F. Comment 6: [32.7.2.2] Extend the sidewalk along Bent Creek Parkway all the way to Avon St. Extended. Also, provide sidewalk along the frontage of Avon St. Extended to the property lines. Response 6: Comment Acknowledged. Sidewalk has been extended along Bent Creek Parkway all the way to Avon Street Extended. Sidewalk is also proposed going north on Avon St. Ext. and stops at the property line in anticipation of future continuation. Sidewalk was not run along Avon Street Ext. heading south due to insufficient Right of Way at bridge structure south of the site. It is the opinion of the engineer that leading pedestrians towards the bridge would create a false sense of security and an unsafe condition,therefore the sidewalk was not proposed. Please see Sheet 6J. Comment 7: The LLF needs to be set at 1.0 for the photometric plan. Response 7: Comment Acknowledged. Albemarle County Service Authority—Michael Vieira: General Comment 1: Place original stamp and signature on first sheet. Response 1: Comment Acknowledged. Comment 2: Provide water and sewer data sheets Response 2: Comment Acknowledged. Water and Sewer data sheets will be provided with submission. Comment 3: Remove sheets from ACSA review set, as indicated on plans Response 3: Comment Acknowledged. Only selected sheets have been provided. Comment 4: Wastewater capacity certification will be required from Rivanna Water & Sewer Authority. ACSA will submit request to RWSA. Response 4: Comment Acknowledged. Comment 5: Relocate water meter vaults as indicated on plans Response 5: Water meter vaults have been relocated as indicated on the plans. Please see Sheets 8C-8G. Comment 6: Sanitary sewer manholes shall have minimum 0.2 foot drop across manhole. Response 6: Comment Noted. Sanitary system has been revised. Please see Sheet 10A. CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOHLERENGINEERING.COM B O H L E R _ Megan Yaniglos 5th Street Station E N G I N E E R I N G Phase II 1St Review Comments July 16,2015 Page 7 of 11 Comment 7: Provide fixture counts for each building for water meter size confirmation. Response 7: Fixture counts for each building will be provided with submission. Sheet 8C Comment 1: Dumpster pad cannot be located within ACSA easement. Relocated as indicated on plans (shift sanitary lateral as needed). Response 1: Dumpster pad has been shifted. Please see Sheet 8C. Comment 2: Relocate water meter vault as indicated on plans. Include water line easement up to, and around meter vault. Response 2: Water meter has been relocated. Please see Sheet 8C. Comment 3: Expand island to accommodate water meter vault as indicated on plans. Response 3: Island has been expanded to accommodate vault. Please see Sheet 8C. Comment 4: Shift light out of hydrant easement as indicated on plans. Response 4: Light has been shifted. Please see Sheet 8C. Comment 5: Install 8" x 4" tee with 4" gate valve, then reduce to 2" rather than 2" corp stop (typical for water services located in travel ways). Response 5 Comment noted. All water service connections have been revised. Please see Sheet 8C. Sheet 8D Comment 1: Relocate water meter vault as indicated on plans. Include water line easement up to, and around meter vault. Response 1: Water meter has been relocated. Please see Sheet 8D. Comment 2: Expand island to accommodate water meter vault, as indicated on plans Response 2: Island has been expanded to accommodate vault. Please see Sheet 8D. Comment 3: Install 8" x 4" tee with 4" gate valve, then reduce to 2" rather than 2" corp stop (typical for water services located in travel ways) Response 3: Comment noted. All water service connections have been revised. Please see Sheet 8D. Sheet 8E Comment 1: Relocate water meter vault as indicated on plans. Include water line easement up to, and around meter vault. Response 1: Water meter has been relocated. Please see Sheet 8E. CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOHLERENGINEERING.COM B 0 H L E R `- Megan Yaniglos 5th Street Station E N G I N E E R I N G Phase II 1st Review Comments July 16,2015 Page 8 of 11 Comment 2: Expand island to accommodate water meter vault as indicated on plans. Response 2: Island has been expanded to accommodate vault. Please see Sheet 8E. Comment 3: Install 8" x 4" tee with 4" gate valve, then reduce to 2" rather than 2" corp stop (typical for water services located in travel ways). Response 3: Comment noted. All water service connections have been revised. Please see Sheet 8E. Sheet 8F Comment 1: Relocate water meter vault as indicated on plans. Include water line easement up to, and around meter vault. Response 1: Water meter has been relocated. Please see Sheet 8F. Sheet 8G Comment 1: Relocate water meter vault as indicated on plans. Include water line easement up to, and around meter vault. Response 1: Water meter has been relocated. Please see Sheet 8G. Comment 2: Provide bollards for water meter vault located in pavement as indicated on plans. Response 2: Comment Noted. Bollards have been provided. Please see Sheet 8G. Sheet 9A Comment 1: Lower storm pipes crossing water line E to allow water main to cross over storm pipes. Burial depth >5' requires a trench box for excavation. Water line is too close to building to safely use trench box. Response 1: Lowering the Storm pipes in this area was evaluated, and it was found that they need to stay at current elevation in order to provide adequate height above the HGL of the sand filter. However, building layout is subject to change in this area, and storm pipe/water layout will be revised and optimized with submission revising the building footprints.See Sheet 9A. Sheet 10B Comment 1: Change manhole MH-10 to internal drop connection with 60"diameter manhole. Response 1: MH1- has been revised with an internal drop connection. Please see Sheet 10A. Comment 2: Change pipe segment from manhole MH-10 to manhole MH-20 to ductile iron. Burial depth is>15'. Response 2: Comment noted. Pipe segments with burial depth greater than 15' have been revised. Please see Sheet 10B. CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOHLERENGINEERING.COM B 0 H LE RM`° Megan Yaniglos 5th Street Station E N G I N E E R I N G Phase II 1St Review Comments July 16,2015 Page 9 of 11 Sheet 13C Comment 1: Remove tree as indicated on plans. Tree is in conflict with hydrant. Response 1: Comment Noted. Tree has been moved. Please see Sheet 13C. Comment 2: Shift tree as indicated to accommodate water meter vault. Response 2: Tree has been shifted. Please see Sheet 13C. Sheet 13D Comment 1: Shift or call-out smaller tree as indicated on plans. Response 1: Tree Plantings have been revised. Please see Sheet 13D. Sheet 13E Comment 1: Shift or call-out smaller tree as indicated on plans. Response 1: Tree Plantings have been revised. Please see Sheet 13E. Sheet 25A Comment 1: Include typical detail for 1 1/2"water meter vault(TD-12). Response 1: Comment Noted. Detail has been provided. Please see Sheet 25A. Albemarle County ARB—Margaret Maliszewski: Comment 1: Revise the building design to significantly reduce the proportion of white and other light- colored materials on the I64 elevation of the Dick's/Field & Stream/Harvey's/Fitness building. Response 1: Building design has been revised. Please see provided building elevation sheets. Comment 2: Provide side elevations and/or other details to clarify the design of the metal roof, wood siding and stone piers in the Field & Stream elevation. Response 2: Comment Noted. Elevations have been revised to show requested information,as shown in the ARB meeting on 6/15/15. Comment 3: Further modify the design of the building between the easternmost brick pier of Dick's and the westernmost stone pier of Field& Stream to reduce blankness. Response 3: Comment Noted. Elevations have been revised to show requested information,as shown in the ARB meeting on 6/15/15. Comment 4: Coordinate the plans and elevations regarding the division of tenant spaces. Response 4: Comment Acknowledged. CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOHLERENGINEERING.COM Megan Yaniglos B CJ H L E R 5th Street Station E N G I N E E R I N G Phase 11 1st Review Comments July 16,2015 Page 10 of 11 Comment 5: Provide material samples for review. Response 5: Materials board will be provided with this submission. Comment 6: Provide details showing how much change in depth is provided by the various pilasters and piers used in the building. Response 6: Comment Noted. Elevations have been revised to show requested information,as shown in the ARB meeting on 6/15/15. Comment 7: Include rooftop equipment on the elevation drawings(dashed outlines are sufficient)to show that the equipment won't be visible from the ECs. Response 7: Comment Noted. Elevations have been revised to show requested information,as shown in the ARB meeting on 6/15/15. Comment 8: Clarify the location of the screening walls on the elevation drawings. Response 8: Comment Noted. Elevations have been revised to show requested information,as shown in the ARB meeting on 6/15/15. Comment 9: Add the standard mechanical equipment note to both the site and architectural drawings: "Visibility of all mechanical equipment from the Entrance Corridor shall be eliminated." Response 9: Comment Acknowledged. The requested note has been added. Comment 10: Revise the photometric plan using an LLF of 1.0. Response 10: Comment Acknowledged. Photometric plan has been revised. Comment 11: Continue the mixed tree planting approved for Wegman's along the Dick's/Field & Stream/Harvey's/Fitness property line(up to the wooded area to remain). Response 11: Mixed tree planting has been continued along the property line. Please see Sheet 13G. Comment 12: Revise the regular row of American holly and Norway spruce at the top of the living retaining wall to a more irregular, informal row of evergreens including a greater number of species, and extend this planting beyond the west end of the living retaining wall. Response 12: Plantings on top of the living retaining wall have been revised to be more irregular and informal. Please see Sheet 13G. Comment 13: Provide photos and addresses of local examples of living retaining walls constructed from the same manufacturer's product. Update the retaining wall details and landscape plan to address the plants proposed to be used on the wall. A mix of plants is recommended. Indicate on the plan that the wall will be irrigated. Response 13: Examples of living retaining walls were provided at the ARB hearing on 6/15/15. Plan has been revised to show that the wall will be irrigated. Please see Sheet 13G. Comment 14: Eliminate the background panel from the Dick's wall sign. Note that sign applications and additional review will be required for all wall and freestanding signs. Response 14: Comment Acknowledged. Background panel has been revised. CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOHLERENGINEERING.COM B 0 H L E RM "- Megan Yaniglos 5th Street Station E N G I N E E R I N G Phase II 1St Review Comments July 16,2015 Page 11 of 11 Comment 15: Rear elevations of the front facade parapets should reflect the design shown on El — El Winter view presented on June 15, 2015. Response 15: Comment Acknowledged. Rear elevations have been revised. Should you have any questions regarding this project or require additional information, please do not hesitate to contact me at(540)349-4500. Sincerely, Bohler Engineering Daniel R. Hines, P.E. DRH/mw H:\12\V122001\Permitting\Jurisdictional Letters\Overall Phase II Site Plan 1st Review Comments\150716 Phase II Site Plan Ist Review Comments.doc CIVIL AND CONSULTING ENGINEERS • PROJECT MANAGERS • SURVEYORS • ENVIRONMENTAL CONSULTANTS • LANDSCAPE ARCHITECTS WWW.BOHLERENGINEERING.COM