The following items are comments from the Albemarle County Architectural Review Board's preliminary review for the project
referenced above and responses indicating how each comment is being addressed by the project team.
ARB Review Comments Response to Address Reviewer Comments
1. Note the height of the mechanical equipment located at each Planting plan has been adjusted to show taller evergreen shrubs
building.Revise the landscape plan and schedule to identify adjacent to A/C units in order to block views from Entrance
the screening plants proposed for the equipment.Ensure that Corridor.
the plants will fully screen the equipment from view.
2. Add the standard mechanical equipment note to both the Requested note has been added to both the architectural and site
architectural and site plans. plans.
3. If exterior building-mounted lights are proposed,include them Wall sconce lights have been added to the photometric plan.The
in the lighting drawings. corresponding cut sheet has been added to sheet L3.04.
4. Provide the 20 scale landscape plans to cover the entire The requested plans have been provided.
development.Be sure all utilities and easements are shown on
the landscape plan.
5. Check and correct the quantity of CK and PL in the plant The quantity of CK and PL in the plant schedule and plan have
schedule and on the plan. been corrected as directed.
6. Clarify the reason for the off-site CK located at the west end The additional CK was an error.The tree has been removed.
of the 5th Street frontage.Off-site grading and planting
required easements.
7. Shift utilities to eliminate conflicts between landscaping and The noted conflicts between landscaping and utilities/easements
utilities/easements without reducing the quantity of proposed have been reconciled.
plants.
8. Add a large shade tree to fill the gap in street trees between The gap between buildings 3&4 is the location of the tot lot.
buildings 3 and 4,or clarify why the gap is required. Shade trees will be provided along southern edge to help shade
the area during summer months.
9. Indicate how the landscape on the slop down to buildings 3,4 The slope between the 5th Street EC&Buildings 3 through 5 will
and 5 from the EC will be handled. be a native warm season grass seed mix.This is predicated by an
Albemarle County Design Standards Manual requirement on
slopes steeper than 3:1.The slopes themselves will not be visible
from the EC as there are existing trees to remain along Buildings
3&4 within the ROW.It should be noted all steep slopes are at a
lower elevation,and the face of the slopes are facing away from
the EC.
10. Limit the number of proposed plants for any one species to The requested limit for any one species to 25%of the total
25%of the total proposed for that plant type(tree,shrub). proposed per plant type has been accommodated.
MEETING MINUTES MEMORANDUM
Gateway Apartments
Charlotte,NC
ARB Review Comments Response to Address Reviewer Comments
11. Provide retaining wall details on the plans. Retaining wall details have been provided on plans.
12. Identify on the plan top-of-wall and bottom-of-wall elevations Requested elevations for retaining walls have been noted on
for the retaining walls. drawings.
13. Coordinate the tree save and grading shown south of the The tree save and grading shown south of the clubhouse has been
clubhouse coordinated.
14. Provide site sections showing the building profiles and Requested site sections have been provided showing building
topography at each condition around the perimeter of the site profiles and topography at each requested condition. In lieu of the
that fronts on an Entrance Corridor.Perspective views should requested perspective views,color rendered site sections and
be provided in order to more accurately describe the building elevations have been provided to more precisely describe
relationship of the buildings and landscape to the EC. the relationship of the buildings and landscape to the EC.
15. Reconsider elevations of Building 5 to be more in keeping Building 5 elevations(identified as building type 4 on drawings)
with the earlier color rendering presented at the previous have been revised to more closely relate to the earlier color
meeting.All building elevations fronting on the EC require the rendering.The requested revisions have been clouded on sheets
same appropriate level of detail. A5-04A and A5-04B.
16. Applicant has indicated that the satellite dishes will not be Confirmed.
allowed on the building.
17. Revised drawings addressing#s 14 and 15 may return for a Revised site sections and elevations addressing items 14 and 15
work session. were presented at ARB work session held on November 16,2015.
No additional changes to the drawings were requested at the
referenced work session;as such,the drawings have been
resubmitted as previously presented and dated 12/7/15.
END OF MEMO
CMN+U N ENS
D�vEL0P
2 of 2
'titu,r
Margaret Maliszewski
From: Blake Simmons <bsimmons @rjtrdesign.com> j' ZOI. I 91
Sent: Tuesday, December 29, 2015 1:32 PM
To: Margaret Maliszewski
Cc: Michael Campbell; Pete Price; 14-063 Charlottesville Apt. Master Planning; Joe Murray
Subject: 5th Street Apartments ARB submission
Attachments: 2015-12-29_5th Street apartments changes list.pdf
Margaret,
Please see the attached document for a list of revisions made to 5th Street Apartments elevations between the
July and November ARB submissions as requested. Please let me know if any additional clarification is needed.
Thanks,
1
RULE JOYTRAMMELL RUBIO
Architecture Interior Design
A limit/Id Liability Company
December 29, 2015
Ms. Margaret Maliszewski
County of Albemarle
Department of Community Development
401 McIntire Rd. North Wing
Charlottesville, VA 22902
Re: 5th Street Apartments
Charlottesville, VA
Dear Margaret,
The following list of changes corresponds to the comments provided during the July 22, 2015
hearing, and submitted for approval on December 7, 2015. The modifications presented below
correspond to item 15 on the list of comments, which reads-
"15. Reconsider elevations of Building 5 to be more in keeping with the earlier color
rendering presented at the previous meeting. All building elevations fronting on the EC
require the same appropriate level of detail"
In response to this comment, the following changes were implemented:
1. 3'-0" roof pop-ups were added above balconies to add architectural interest to the building
elevation and roof line.
2. The balcony tower adjacent to the entry breezeways was extended, and the roof element
was popped-up 3'-0"to create a change in planes thus creating a more dynamic façade.
3. Arched trim was added and board and batten panels were extended on the top level of the
building to keep with the overall aesthetic and level of detail presented on buildings
elsewhere in the property.
Please feel free to contact me if you have further questions.
Sincerely,
Blake Simmons
Associate
Rule Joy Trammell+Rubio,LLC
Architecture+Interior Design
(+ 1 t' 71i7
r,f,I i 492
rylf ...%{7'*ji.'"C: ,'J"1.i:f13T
RULE JOYTRAMMELL4RUBKO
Architecture Interior Design
A Untied ■ebIIty company
ARB Review Response Memo
PREPARED BY: Blake Simmons
PROJECT: 5th Street Place
Charlottesville,VA
ARB-2015-66
The following items are comments from the Albemarle County Architectural Review Board's preliminary review for the project
referenced above and responses indicating how each comment is being addressed by the project team.
ARB Review Comments Response to Address Reviewer Comments
1. Note the height of the mechanical equipment located at each Planting plan has been adjusted to show taller evergreen shrubs
building.Revise the landscape plan and schedule to identify adjacent to A/C units in order to block views from Entrance
the screening plants proposed for the equipment.Ensure that Corridor.
the plants will fully screen the equipment from view.
2. Add the standard mechanical equipment note to both the Requested note has been added to both the architectural and site
architectural and site plans. plans.
3. If exterior building-mounted lights are proposed,include them Wall sconce lights have been added to the photometric plan.The
in the lighting drawings. corresponding cut sheet has been added to sheet L3.04.
4. Provide the 20 scale landscape plans to cover the entire The requested plans have been provided.
development.Be sure all utilities and easements are shown on
the landscape plan.
5. Check and correct the quantity of CK and PL in the plant The quantity of CK and PL in the plant schedule and plan have
schedule and on the plan. been corrected as directed.
6. Clarify the reason for the off-site CK located at the west end The additional CK was an error.The tree has been removed.
of the 5th Street frontage.Off-site grading and planting
required easements.
7. Shift utilities to eliminate conflicts between landscaping and The noted conflicts between landscaping and utilities/easements
utilities/easements without reducing the quantity of proposed have been reconciled.
plants.
8. Add a large shade tree to fill the gap in street trees between The gap between buildings 3&4 is the location of the tot lot.
buildings 3 and 4,or clarify why the gap is required. Shade trees will be provided along southern edge to help shade
the area during summer months.
9. Indicate how the landscape on the slop down to buildings 3,4 The slope between the 5th Street EC&Buildings 3 through 5 will
and 5 from the EC will be handled. be a native warm season grass seed mix.This is predicated by an
Albemarle County Design Standards Manual requirement on
slopes steeper than 3:1.The slopes themselves will not be visible
from the EC as there are existing trees to remain along Buildings
3&4 within the ROW.It should be noted all steep slopes are at a
lower elevation,and the face of the slopes are facing away from
the EC.
10. Limit the number of proposed plants for any one species to The requested limit for any one species to 25%of the total
25%of the total proposed for that plant type(tree,shrub). proposed per plant type has been accommodated.
NI le 4#411
MEETING MINUTES MEMORANDUM
Gateway Apartments
Charlotte,NC
ARB Review Comments Response to Address Reviewer Comments
11. Provide retaining wall details on the plans. Retaining wall details have been provided on plans.
12. Identify on the plan top-of-wall and bottom-of-wall elevations Requested elevations for retaining walls have been noted on
for the retaining walls. drawings.
13. Coordinate the tree save and grading shown south of the The tree save and grading shown south of the clubhouse has been
clubhouse coordinated.
14. Provide site sections showing the building profiles and Requested site sections have been provided showing building
topography at each condition around the perimeter of the site profiles and topography at each requested condition. In lieu of the
that fronts on an Entrance Corridor.Perspective views should requested perspective views,color rendered site sections and
be provided in order to more accurately describe the building elevations have been provided to more precisely describe
relationship of the buildings and landscape to the EC. the relationship of the buildings and landscape to the EC.
15. Reconsider elevations of Building 5 to be more in keeping Building 5 elevations(identified as building type 4 on drawings)
with the earlier color rendering presented at the previous have been revised to more closely relate to the earlier color
meeting.All building elevations fronting on the EC require the rendering.The requested revisions have been clouded on sheets
same appropriate level of detail. A5-04A and A5-04B.
16. Applicant has indicated that the satellite dishes will not be Confirmed.
allowed on the building.
17. Revised drawings addressing#s 14 and 15 may return for a Revised site sections and elevations addressing items 14 and 15
work session. were presented at ARB work session held on November 16,2015.
No additional changes to the drawings were requested at the
referenced work session;as such,the drawings have been
resubmitted as previously presented and dated 12/7/15.
END OF MEMO
RECEIVED
{ C7 2015
COMMUNITY
DEVELOPMENT
2 of 2
waterst et .
COMMENT R E S P O N S E
DATE February 15, 2016
PROJECT Fifth Street Place
TO Mdrgarei +v a,�s<ewski
FROM Pete Price
SUBJECT ARB Comment Reponses
COMMENT RESPONSES:
1. All evergreen shrubs(Schip Laurel, and Dwarf Burford Holly) used to screen AC
units along Entrance Corridor have been set to 4' height at install.
2. The chain link fence has been removed from visible areas.A 6' black ornamental
fence is now called out around the pool and clubhouse.A 42" black ornamental
fence is now called out along the top of all retaining walls and the tot lot. Please
see sheets C-07A thru C-07E for revised fence locations and call outs.A detail of
the proposed ornamental fence is shown on sheet C-02A.
3. One (1) UP has been moved to avoid water line.
4. Two (2) BN have been moved approximately 3'away from storm lines.
5. One (1)JV has been moved to avoid storm line.
6. Additional shrub types have been added to increase diversity throughout the all
foundational plantings.The shrub types and counts have been clouded on the
planting plans, and plant schedule sheets.
7. Retaining wall information is now included with this submission. Please see the
supplemental documents from the manufacturer.
8. Retaining wall information is now included with this submission. Please see the
attached documents from the manufacturer.
ADDITIONAL PLAN CHANGES:
1. Grades along the entrance and parking areas adjacent to the mail kiosk have been
revised.These revisions were per VDOT and Engineering comments.
2. Main access drive widths were increased 2' around the site to comply with fire
code.This revision is per comment from the Fire Marshall.
3. Some fire hydrant locations were revised.These revisions were at the request of
the Albemarle County Service Authority.
4. Retaining wall location and grades were revised behind buildings 1 &2.This
revision is per and Engineering comment regarding maximum retaining wall height
in steep slope areas.
The above record constitutes our understanding of the matters discussed and the decisions made.Please send
any additions or corrections to the recorder within five(5)days of receipt. d•
418 East Main Street Charlottesville, Virginia 22902 434 295.8177 www waterstreetstudio.net
waterst- et .
!VI 1V3 L . u i g L ," f" ;.J i v" L
�,
COMMENT RESPONSES:
1. The shrubs used to screen the mechanical units along the western facade of
Building 5 have been switched from Inkberry Holly to a Cherry Laurel (4' height at
time of installation).The plant schedule has been updated to quantify this
planting change.
2. Notations have been added to sheet C-02A regarding retaining wall color to be
Shannon Tan.
ADDITIONAL NOTES:
1. Sheet C-02A shows typical planting layout per retaining wall manufacturer's
instructions. Notes have been added above this specification sheet to ensure
plantings shown on planting plan will be installed per the drawings, and that the
structural engineer of the retaining wall needs to take proper steps to
accommodate plantings to alleviate any concerns with the root balls of the
trees/shrubs and the required retaining wall geo-grid.