Loading...
HomeMy WebLinkAboutSDP200100079 Review Comments 2001-08-15 `Vri 'err►' Albemarle County Development Departments SDP-2001-079 SPIN Submission and Comments Peter Jefferson Plase I Maintenance Build Service Authority Minor Amendment revision 1 reviewer received reviewed decision Pete Gorham 8/15/01 8/15/01 requested changes Stephen, We have reviewed the minor amendment concerning the proposed Property Maintenance Building in Phase 1 of Peter Jefferson Place, and it is not approved. The following items must be satisfactorily addressed prior to us granting final approval: (1). The proposed maintenance building will have to have a separate metered connection to the existing public water main in Peter Jefferson Place. It cannot be connected to the existing water line serving the sewer pump station. (2). Gravity sewer mains are readily available to the maintenance building, however, a private grinder pump would have to be installed. Let us know if you have any questions. Thanks. -Pete 8/24/01 01:50 PM Page 1 of 1 Albemarle County Development Departments SDP-2001-079 SPIN Submission and Comments Peter Jefferson Plase I Maintenance Build Zoning [description and date] revision 1 reviewer received reviewed decision susan snead 8/13/01 8/13/01 requested changes FROM: Susan Carol Snead, Zoning Plans Reviewer DATE: August 13, 2001 RE: SDP 01-079 PJP-1 Property Maintenance Bldg Minor Amendment The Albemarle County Department of Building Code and Zoning Services will approve this site plan amendment for zoning compliance when the following items have been satisfactorily addressed. The Building Official may provide separate comments. [Each comment is preceded by the applicable reference,which is to the Zoning Ordinance unless otherwise specified.] 1. [32.5.6(a)] Please note on the plan the specific use for the proposed building (offices, storage of equipment, etc.). 2. [32.5.6(b)] Please note on plan the maximum number of employees. 3. [32.5.6(b)] Please note on the plan the maximum height of the proposed building. 4. [4.12.6.6] Please note on the plan the required number of parking spaces and the standard used for this calculation. 5. [4.17.4] Please note on the plan, "Each outdoor luminaire equipped with a lamp which emits 3,000 or more initial lumens shall be a full cutoff luminaire or a decorative luminaire with full cutoff optics." 6. [4.17.4.3] Please note on the plan,"The spillover of lighting from parking area luminaires onto public roads and property in residential or rural areas zoning districts shall not exceed one-half(1/2)foot candle." 7. [32.5.6(n)] Show the location of all outdoor lighting on the plan. 8. [32.6.6(j)] Provide a description and photograph or diagram and show the location of each type of outdoor luminaire that emits 3,000 or more initial lumens. Please be aware that installation of such luminaires in the future that are not shown on this plan shall require an amendment to this plan. 9. [32.6.6(j)] [4.17.4(b)] Include a photometric plan on the site plan demonstrating that parking area luminaires are in compliance with 4.17.4 b. 10. [32.5.6(1)] [32.5.6(n)] Show the location of all proposed utility structures, including above ground fuel tanks, HVAC equipment and the like on the plan. 11. [30.6] The final plan approval is subject to the issuance of a Certificate of Appropriateness from the Architectural Review Board. 8/24/01 01:51 PM Page 1 of 1 Albemarle County Development Departments SDP-2001-079 SPIN Submission and Comments Peter Jefferson Plase I Maintenance Build Fire/Rescue Minor Amendment 07/31/01 revision 1 reviewer received reviewed decision BRUCE CROW 8/8/01 8/8/01 approved with conditions Verify that adequate fire flow is available. Required fire flow is 1,125 gpm @ 20 psi. Based on a 1,152 sq. ft. building of Type 5 construction. (Albemarle County Zoning Ordinance 18-32.7.6) Provide a fire hydrant within 400 feet of the building. (Albemarle County Zoning Ordinance, Section 18- 32.7.6) 8/24/01 01:50 PM Page 1 of 1 Albemarle County Development Departments SDP-2001-079 SPIN Submission and Comments Peter Jefferson Plase I Maintenance Build Engineering [description and date] revision 1 reviewer received reviewed decision Glenn Brooks 8/7/01 8/7/01 requested changes TO: Stephen Waller, Planner (to be in SPIN) FROM: Glenn E. Brooks, Engineer DATE: 14 December 2000 RE: Peter Jefferson Place phase 1, maintenance building The site plan amendment for a travelway and maintenance building at Peter Jefferson Place received on 31 July 2001 has been reviewed. The Engineering Department will recommend approval when the following items have been addressed: 1. Please indicate on the plan that the access drive will be restricted from the general public. If not, circulation,turnaround and safety features will be a priority. [32.7.2] 2. Please provide stormwater management computations and plans. With a disturbed area of less than an acre, detention requirements are waived, but water quality provisions are not. Perhaps conceptually some minor grading changes and a rain-garden type facility for the building and parking would work. [17- 312, 314, 315] 3. An erosion and sediment control plan, narrative and computations are required. The details provided on the site plan amendment were not reviewed. An application and fee must be provided with plans, narrative and computations to the Engineering Department. [14-311, 17-203, 18-32.7.4.3] Please contact me if you have questions. Copy: file 1802 File: Peter Jefferson PI phase 1 maint bldg mia (1).doc 8/24/01 01:50 PM Page 1 of 1 Albemarle County Development Departments SDP-2001-079 SPIN Submission and Comments Peter Jefferson Plase I Maintenance Build Building minor site plan amendment revision 1 reviewer received reviewed decision Jay Schlothauer 7/31/01 7/31/01 approved Based on plans dated July 9, 2001. No comments or conditions. -- -- --- - 8/24/01 01:49 PM Page 1 of 1 ''err OF AL ,c.1.04' I i 111, ��RG1N�P COUNTY OF ALBEMARLE Department of Planning&Community Development 401 McIntire Road,Room 218 Charlottesville,Virginia 22902-4596 (804)296-5823 Ext.3385 Fax(804)972-4035 MEMORANDUM (FAX) TO: Andrew Dracopoli (977-6578) FROM: Stephen B. Waller, Planner DATE: August 24, 2001 RE: SDP 01-079 Peter Jefferson Place I Maintenance Building Site Plan Amendment The Department of Planning and Community Development will approve of the above-mentioned site plan amendment when the following conditions have been satisfied 1. [32.5.6aJ Provide notation of the source of the topography. 2. [32.5.6a] Provide notation of the source of the topography and survey. 3. [32.5.6fJ Indicate whether, or not, this site is located within a reservoir watershed. 4. [32.5.6n] Show the locations of any fencing or gates for security. Copy: SDP 01-079 T I ;,►n9 se frinGfros COUNTY OF ALBEMARLE Department of Building Code and Zoning Services 401 McIntire Road,Room 227 Charlottesville,Virginia 22902-4596 FAX(804)972-4126 TELEPHONE(804)296-5832 TTD(804)972-4012 MEMORANDUM TO: Stephen Waller, Planner \7_6/r. FROM: Susan Carol Snead, Zoning Plans Reviewer '" DATE: September 7, 2001 RE: SDP 01-079 PJP-1 Property Maintenance Bldg Minor Amendment Revised August 29, 2001 The Albemarle County Department of Building Code and Zoning Services will approve this site plan amendment for zoning compliance when the following items have been satisfactorily addressed. The Building Official may provide separate comments. [Each comment is preceded by the applicable reference, which is to the Zoning Ordinance unless otherwise specified.] 1. [30.6] The final plan approval is subject to the issuance of a Certificate of Appropriateness from the Architectural Review Board. Please contact me if you have questions or require additional information. Stephen Waller From: Pete Gorham Sent: Tuesday, September 11, 2001 2:40 PM To: Stephen Waller Subject: Peter Jefferson Place Property Maintenance Bldg. SDP-01-079 Stephen, We have reviewed the minor amendment concerning the proposed Property Maintenance Building in Phase 1 of Peter Jefferson Place, and it is not approved. The following item must be satisfactorily addressed prior to us granting final approval: (1). Approval of final water construction drawings which shall be submitted directly to the Service Authority. Let us know if you have any questions. Thanks. -Pete 1 9/11/61 £Brun' 1114r ':: Sr `ffiGIInP COUNTY OF ALBEMARLE Department of Planning&Community Development 401 McIntire Road,Room 218 Charlottesville,Virginia 22902-4596 (804)296-5823 Ext.3385 Fax(804)972-4035 MEMORANDUM (FAX) TO: Andrew Dracopoli (977-6578) FROM: Stephen B. Waller, Planner DATE: August 24, 2001 RE: SDP 01-079 Peter Jefferson Place I Maintenance Building Site Plan Amendment The Department of Planning and Community Development will approve of the above-mentioned site plan amendment when the following conditions have been satisfied [32.5.6a] Provide notation of the source of the topography. 1. [32.5.6a] Provide notation of the source of the topography and survey. [32.5.6] Indicate whether, or not, this site is located within a reservoir watershed. I1 [32.5.6n] Show the locations of any fencing or gates for security. 10lefte,j ilk 4 ,w,ayc Copy: SDP 01-079 *owe r.rO �� 7v J$��7�'p111111� O.<40"ilikt INer I'�RGINIP COUNTY OF ALBEMARLE Department of Engineering&Public Works MEMORANDUM TO: Stephen Waller, Planner (to be in SPIN) FROM: Glenn E. Brooks, Engineer DATE: 12 Sep 2001 RE: Peter Jefferson Place phase 1, maintenance building The revised site plan amendment for a travelway and maintenance building at Peter Jefferson Place received on 4 Sep 2001 has been reviewed. The Engineering Department recommends approval with the following conditions: 1. The stormwater management bond is $1800. 2. An erosion and sediment control plan will be required if disturbance exceeds 10,000 sf. Please ensure the bond is posted before signing the final site plan. The Engineering Department will notify you when this occurs. Copy: file 1802 Pam Shifflett File:Peter Jefferson P1 phase 1 maint bldg mia(2).doc Ns," Impel Albemarle County Development Departments SDP-2001-079 SPIN Submission and Comment Peter Jefferson Plase I Maintenance Build Architectural Review Board revision 1 reviewer received reviewe decision Margaret Maliszewski 9/13/01 approved The proposed maintenance building is not expected to be visible from the Entrance Corridors. Consequently, ARB review is not required. 9/26/01 09:38 AM Page 1 of 1