NARRATIVE REPORT
INTRODUCTION
The Rivanna Water and Sewer Authority(RWSA) is proposing to repair a segment of their North
Rivanna water transmission main in northern Albemarle County, VA. An existing 12 inch
diameter cast iron water main currently crosses the North Fork Rivanna River just west of Rte.
29. The water main is an existing high pressure line which services residential, commercial,
industrial and government properties in the north Albemarle service area. The TMP parcel Nos.
for this project will include 32-6A and 32G-C.
The project site resides within the jurisdiction of Albemarle County, and all necessary permits
will be coordinated with the County. A USCOE permit and VDOT Land-use permit will also be
obtained. The river banks have seen recent, accelerated erosion problems and the line is in
danger of being exposed. The RWSA proposes to relocate approximately 300 LF of water main
to move the line back away from the banks, and to bury it deeper to gain adequate cover over
the pipe. This project is simply a pipe relocation, and no impervious area exists, or will be
increased, as a result of the work. Disturbed area will be limited to that normally occurring
during a small diameter pipe trenching job. Access to the north river bank will be along an
existing gravel road, and a temporary gravel access road will be constructed on the south side.
The gravel access road will be fully removed at the conclusion of the project, and all disturbed
areas restored with seeding and mulch.
The disturbed area for these improvements is approximately 0.76 acres. The project will be
done by open cut trenching methods, and the excavated soil will be re-used as backfill in the
trench. It is anticipated that excess soil will be minimal, but if encountered it will be removed
from the site by the contractor, and disposed of in an approved location with all required permits
to be acquired by the contractor.
Erosion and sediment control measures will be used to limit erosion and contain sediment from
the construction and cleared areas prior to the establishment of vegetation. Due to the confined
work area space available near the river, the options for erosion and sediment control features
were limited.
CONTACT INFORMATION
The Owner Point of Contact for this project will be:
Doug March, P.E.
Rivanna Water and Sewer Authority
695 Moores Creek Lane
Charlottesville, VA 22902
434-977-2970 ext. 201 —office
434-996-7793—work cell
dmarchrivanna.orq
t
1
SOILS
Three soil types exist on the project site. These soils have been identified and classed by the
Natural Resources Conservation Service (NRCS), and are detailed below.
10— Buncombe Loamy Sand
The Buncombe series soils, an excessively well-drained series, exist predominantly in
floodplains and typically have a depth to the water table or restrictive features of over 80 inches.
Buncombe series soils originate from sandy alluvium derived from igneous rock.
14D—Chester Loam
The Chester series soils, a well-drained series, exist predominantly in hillslopes and typically
have a depth to the water table or restrictive features of over 80 inches. Chester series soils
originate from residuum weathered granite and gneiss. Slopes range from 15 to 25 percent.
88— Udorthents, Loamy
Udorthents exist predominantly in interfluves and flood plains. They typically have a depth to the
water table or restrictive features of over 80 inches. Udorthents soils originate from residuum
weathered granite and gneiss. Slopes can range from 2 to 25 percent.
ADJACENT AREAS
Land use immediately surrounding the property consists primarily of rural woodland with some
light residential development to the north. The property is bounded to the east by VDOT public
R/W on Rte. 29 (major divided highway corridor).
EROSION AND SEDIMENT CONTROL MEASURES
A majority of the erosion and sediment control devices and measures have been designed and
placed in accordance with the Virginia Erosion and Sediment Control Handbook (VESCH), Third
Edition, 1992.
If necessary, temporary measures will be used to limit erosion and contain sediment from
cleared areas prior to the establishment of permanent vegetation. Once construction, including
all structural measures, is complete and permanent vegetative cover has been established,
these measures may be removed with approval from the engineer. Vegetative cover for
disturbed areas will consist of grasses as recommended by the Virginia Erosion and Sediment
Control Handbook. See the Plans and Specification Section 02911 — Seeding, Topsoiling,
Fertilizing and Mulching.
The temporary measures proposed for this improvement include silt fence, construction
entrances, temporary seeding and mulching, construction road stabilization, check dams, utility
stream crossing (cofferdam) and dewatering structures (filter box) measures as required. The
above devices will filter sediment from runoff to prevent sediment from being deposited off-site,
while the temporary seeding will limit erosion during construction activities. Permanent
measures proposed include permanent seeding and mulching. See Specification Section
02370— Erosion and Sediment Control and Section 02911 —Seeding, Topsoiling, Fertilizing and
Mulching for further details on these temporary and permanent measures.
An additional temporary measure to be utilized is a modified mudtrap. A variance request has
been included in the E&SC plan submittal, and will need approval from Albemarle County for it's
use. The construction work area is extremely confining near the river bank, and beneficial
results will be evident if the smaller footprint mudtrap device is allowed.
Temporary Stabilization
A majority of the temporary sediment and erosion control measures were designed and chosen
based on criteria from the Virginia Erosion and Sediment Control Handbook (VESCH).
Stabilization construction entrances/exits and silt fence are designed in accordance with the
guidelines established in VESCH Sections 3.02 and 3.05.
Temporary seeding measures were chosen as per the recommendations of VESCH Section
3.31.
Permanent Stabilization
Upon completion of the project, permanent vegetative plantings will be used to achieve
stabilization of the site. All temporary erosion and sediment control measures will be removed
once the site has been stabilized. All permanent vegetative plantings conform to those
specified in the VESCH Section 3.32. See Specification Section 02911 — Seeding, Topsoiling,
Fertilizing, and Mulching for the proposed seeding schedule.
Erosion Control Sequence
1) No demolition, construction or land disturbance activities may begin until a pre-construction
meeting has been held with the County, and all perimeter erosion control measures have
been installed as per Contract Drawings. If clearing is required for installation of a particular
measure, all other measures shown shall be installed first; clearing of the land necessary
may then proceed.
2) Once all measures have been installed, the site shall be mobilized onto as necessary within
the limits of disturbance as per the Contract Drawings. Efforts shall be made to minimize
the amount of cleared area exposed at any given time.
3) Once mobilization is complete, any necessary topsoil stripping may begin. Topsoil shall be
stockpiled on site in the stockpiling areas per the Contract Drawings. The stockpile shall
receive such temporary seeding measures as may be required. Any soil taken offsite shall
be stockpiled at locations with all required permits. If offsite location does not have all
required permits, the contractor is responsible for obtaining any required permits.
4) Demolition, earthwork and construction operations may begin once topsoil has been
removed and stockpiled.
5) Once perimeter erosion control measures are in place, construction activities for the water
main relocation may begin.
6) All pipes shall be installed in accordance with standard construction techniques. Only the
length of trench in which pipe can be installed per the Contract Documents shall be open at
any time, with spoil material placed on the uphill side of the trench. Piping shall be capped
at the end of each day's work to prevent sediment from entering. The trench shall be
backfilled at the end of each day's work and the disturbed area seeded and mulched within
seven (7) days of backfill.
7) Temporary soil stabilization shall be applied within seven (7) days to denuded areas that
may not be at final grade but will remain dormant for longer than fourteen (14) days, except
for that portion of the site on which work will be continuous beyond fourteen (14) days.
8) Once water main construction is complete, final seeding and mulching may begin.
9) Upon completion of final grading, permanent seeding, mulching and fertilizing measures
shall be employed on all disturbed areas as per Section 02911 — Seeding, Topsoiling,
Fertilizing, and Mulching. Permanent soil stabilization shall be applied within seven (7)
days after final grade is reached on any portion of the site. All erosion control measures
shall remain in place until the entire site has been stabilized.
10)Once permanent stabilization has occurred, temporary sediment control measures shall be
removed. Any areas disturbed by the removal of these measures shall be returned as
closely as possible to original condition and seeded, mulched and fertilized as per
Specification Section 02911.
Maintenance and Sediment Disposal
All sediment and erosion control measures shall be inspected upon installation, at least once
every fourteen (14) days and within 48 hours following any runoff-producing rainfall event.
Repairs to, or replacement of, measures shall occur immediately if necessary and accumulated
sediment removed as needed.
Sediment shall be removed from all erosion control measures when the sediment storage
volume of the measure has become 50% full. All removed sediment shall be disposed of in an
approved manner at the stockpile location or a location to be designated by the Engineer or
Owner. Steps shall be taken at the disposal site to insure that further sediment transport does
not occur.
All disturbed areas shall be permanently seeded as soon as possible, but in no case later than
seven (7) calendar days after construction activities are complete. Areas shall be seeded,
fertilized and mulched in accordance with the Seeding schedule in Section 02911 — Seeding,
Topsoiling, Fertilizing and Mulching of the Specifications.
STORMWATER ANALYSIS
The proposed site, which disturbs less than one (1) acre of land, currently has no impervious
area on it. The proposed project consists solely of relocation of buried waterline utility piping and
appurtenances. There will be no additional impervious area created as a result of this project,
therefore, new SWM features are not required.
CRITICAL SLOPES
Critical slopes, as defined by the County of Albemarle, are areas of topographic inclines that
exceed a 25% slope. By definition, if these slopes exist naturally, no disturbance or impact are
to be made to these slopes without approval by the County. Critical slopes may exist near the
river banks on this site, however, the waterline relocation work will not permanently impact
these slopes. The river banks will receive rip-rap armoring in the location of the relocated
waterline.
Appendices
Appendix I — Maps (FIRM, Vicinity, Soils)
Appendix II — Contract Drawings (Under Separate Cover)
Appendix III —Specifications
Section 02101 — Dewatering and Drainage
Section 02230—Clearing and Grubbing
Section 02315— Excavation and Backfill
Section 02316— Fill and Granular Fill Materials
Section 02370 — Erosion and Sediment Control
Section 02511 — Ductile Iron Pipe and Fittings for Water
Section 02512—Copper Pipe and Tubing
Section 02513—Valves, Hydrants, and Appurtenances
Section 02514—Water Piping Specialties
Section 02515—Water Piping Installation
Section 02516 - Water Pipe Testing
Section 02910—Seeding, Topsoiling, Fertilizing and Mulching
Appendix A—Approved Products List
Appendix B—Standard Details and Modified Mud Trap Calcs
Appendix I
Maps
(FIRM, Vicinity, Soils)
.
v6
o
u a52.-5
a EFAEE
MH O ge II m•r cO u l
C7
Q - i 5
Q t a
WomN' •upa LoY b. 111111
1« H t. LaJII 0 q5c.,ON1'T W UO . O LL4.4 W z = W O tW if O u js
co
.c ZQir, i < L °; q a°1.D 4F 8 E w .41' x W S2?ffim g r°'o W 2 3 o `4 1 &LLo2
n xou o.-wgd o W w �; Eg c-z Ii u. CCO s N
oEaLLo
F
2$E
0_
mea
E3W
IA0
N m 0
_.„„iiiiiamp. ,,j '''*7111.,-,_,.<>.,,74.1.,.... or.,..1111:44144,:.\\:,
3'6.f.-.0.
Z W /44 , 7
in
0 o c‘, ..-14, 0)
cal
p my 't \ �-'�� ii
0x �
W o .cc J x m Ca. t.
o O N1 i 3
N' Mo s ' act� `� ca
.... -.."1111111111111111mbli.---..wittitt - --,,'-'t..---.
K W ZZ O �0 W cd Z .4
,
W 0.'i Z ti Z F. 0 /1. 3 ,t4k4 .
Z 0 n U J •
N N Q OJl, 13SaOQ fly j''s, c` rt. /.
zL ‹z-i , . fir, q;7V i"Fty,'" 4�4'',r.,{ �� {ry ,
60 -4
..(s Q�j r'q xr a ,,.r�, �,.,,).,v ' Z
@ggco
y
h 5 � ''
W4 3r� ZT+trtsO } , ) KZ2;W ��'" r .,-,.. -,:,,,-,;,::),;..:,-,:,,i),,,,,... I'. r ,2,,,,'"
1 0
03
�'. ° ,ryS ei'
bby K ' O ' X z o o
Otibtiy a W Z o W
N i W Z 0Z
0 co Q
O -` .p ' /f ,' Z------.,
" e
,� ;" M �► N W 111P®1111‘111
Hz
''x M !7 1 N m W sb��`�/p
111 '
} - _ – - 32E-08-131r32E70*k_, 3 S
32-5
N ' 2E--08-26 , � 41
i _ ;.32E'0 -14i 32E-4)&5
- - 32 - 1B-1 j •- I' ;
_ w I 32E;-0:-4 ,32E--08-26tr
32G-B
O,NRW9t9
32E-(6416 - f=Q032E--0B_3 '
is 32E--op-215 f .- Q NRW-018 32 5F'
t: - 32E--(1 17 f
32E-A4 .�, { _ J
ti 32E-0642 132E• Ealy , . i �
rf
32G-1 32E--013-23.--; '---7,-------7-'-';`' 32E4-11-1 .
4 7. " . -. '''',326..--013-1.4'. r - .
32E--08:2?a`` ` • _ f 4
�jj
;`- 32E'08-2f�'?\4;26 0B-26."—
'`"-!-, Q•N_RW-0* fr'
0 NRW 023 m'_ - rk - .---/-1' �I E., :t.:
r
,'r f.. ''*-;:4' '.: / .^-1 --'''''''.:-'41 ,7-,Z:::,.. .',,::7;--,-i _ ..,) ,., „'
32G..0 f 132 5D
/ d y t
;"
PROJECT LOCATION .2. y:-1' ,,'
NW/4)24 a NRWO2I
,
am
NRW-024A -----
r x . "r „t,-;'.1;Y:liV
G `
/
32-6A g --, ,
`If , /4
Note: Access to the repair site will be along existing
g ,c Waterline easements off of Rte. 29-Seminole Trail
7V7 4 - -'W-ARV-03 /
7/1
,'' - – s"r 32,--„5411-d
f //,72,,7
-1-C 'e v��g1�dG r "
.,I --,-•./ , „,.”,"•-, „:
//
-••• •.•.:,-,i7.''''-,' ,:r.-- - ,:,,,,,,,,,,,
, �f ' / Sk 32-22K1
r. 1
//2'
/12
22K 33-15
yA RWSA
,% NORTH FORK RIVANNA
WATERLINE REPAIR
1
N
4.1c."i" i
o lz I 8•z mm `�'��,
I a
r, -----A2---)'',7;- ,-1, --:1\3• '),C7(.-N--1--,•\c,- ):7--'` .\ . mow• s 4,
��-J ./•'• ',-1, +,. \1t`,Jq ` , !, /, 4�I"▪ rl ,'4\�\. .� j; ,.�1,` . r .? -w
��_�� J ', '6 n ,- ,,,,T,.._,,..._.„,�-'i'_',fJ' i I�'��_ ye <`>'} 8 Z a eDW W
�..,_ I'ti` `_ \'`�jj ��\c\�1'.-. J-c'i,3,-, \-1-1-1il'el t� it( �.'�'f.'' E �. rW8 iiiz
"-�' ISI I L;, _✓' (� { A h m ""I o p' O Pt'S
`"L,;lf,��,-�- �,\1 =`.1;'•.. `f ^121 ..\ '.\-V %--) ` i R co
``\, { �, \`_ , '"- .,�, , 1 _-. ice ST ( / .��, ,
S.\\-.4:---:1,\s-\,,-. ,\,�. , :-ml, 0 I ' ' - . J n .1,��i LL i• -`
�� ,sj}J`"�' f=ti'-1 ltrf:. (��` > ` �J S '.r� )5 r r/( '��,�, j J i' tJ/lZ \t(`�"•2
If�A�/�` --L-P.
i --.),,,,,\7-
0�� � ;1';- 'r >' "� ��) j�(ms S
11
-\;-,..v\ '. .i--.,.-)__5‘.-,.:,,\---=:,,,,, , i:_c: ,/
''''IL'
' l,�'^/ �bi�'A�'` !\ l ®�\''.. \-;.„)Y-.‘.--,6. -.1r-__.,'''''' ,.-.-'s- ,� ` � J�1�c r� €�-.., !.--(6'5"� o
. ,..,.t
- Li' ,-,i7.‘ - --- ,r-,52-- ,-•,-,,,' ,,-7-1, ):--.`-_-•) '1 it ,, ;,,.-, __t ,,,,t (•\.(,_.. :)0('' Li2 :",, a .2'
l_o__
-17-<'''' ._14:-•:'---)
/--- '' • i\ l' �� i,j /1 ` /'---=--77----,,
';\ \\ - ''' -'rt\3 � �_ �
,„Z,;:f,\:',7g-iirrs-,-_-z`;:`-_,\\(i,),,,'-'''',,:S:r;:;.),,,,,,,...$...._:s:)..::::,,r - a
,:--- 1 --\\.1.---A 7)...4. 7,i:— i —/ ,.. -,, ---6_,--c__);\\—130 l• - " * --' •..g. 9 0 g
i ) H
li;fl• Ng• • a$>�
wap
� J1sA ✓-c ,:-.,-7.;:-2g-4 -] {., (rl Ll :; X, o"rn I�g t �B um/
C- t3�-�/ ,_'tel , [."r _1 1 < L, e•�W �- ♦� > / ,1 P T O� rn 0�¢W
:"1-'7,7,-);.),,,A,,,,,& -&_.-Ty' ' -,:',..-z-;E'i'.; s II; Fili #, ".')\kA('`; -"."--`-\ ((i_ ;„ ',r,",
F--f.
�, -mss / c,-`I � ; p.r `) - J >> _ ( m cd
°
-,,s-\
°a1 (n.2-r-- :rz, }` °� c."-- l=am ft"l(> 0 sly--` n-ti --".-)ArI o •Z
---%), '-1 �.�� },%F 1`J 1,02(1c.,_,,,,,3,1 ;\' i/\ r` 1^�; F;2_ i� 14�! 1. -1 j $i p
i', t,, -.( ,----,----:,!4,i,41::--!'\\� i _4(\r! 1 n•. - r),.../2f)",---1`/17 -. '�N�i"41
5,,)/((:=2:1---2-,:„_;___ _,' ,;-..: —4'7-',\ ,,--::;,,,,r ilo.'`-`7_,z"!2, !,4 -
tali%
� ll` \1� �r �l M
a .L �,�,� .c.1,,\'\
,),,,,,,,/,:::,,,,fir 1 - , l;' •v, ) ' - ,, \i II , Vii'' f E�
fi' oA lG1 y',.� \t" }� ;,._. / `(IC`-�)/.I r 1� :/- '.
i, °`--�-�- -m
-J ( -alp �-... ▪,i -M1.\ �` / -.,...k I... - N .:,.x \,-\ . I A-- a- ix i
\ t , -:),`7 .",. 'v :IN� \ ire- •l i /�1 i �`•l ,\�� _ / 1` c"--,/
(� �z�- :,..1:,
},5 -:,_>r. ,))1,-2,_
I 1 l, '\; / N a' I '_ I�/r / in \ S'�/ F ..4.
_
-r„5,\`- 11.. 1,..,0,...-.„ �� 1/ 'ii �' _ '° .'l.. �' }/,- V
..}� `�
�1 Ii \
,_-,S' ;: {o. - ° .- - . 1 , <;2:'.�C� i /i l\o------____,757)*?
«h
,�iJ\„...,...,,,,,,,L,-,-v.y �' i- 1/-� •�`� �,�'.,r �;-'-\ �t ice._" ,-; _ ��.2�: - i`•. l�_...1�p)? '"
1,«�ti '�A•- 1'.,,t"p/, 1, _,, `' , , l `iir �', _ i-�-,`' �..„e ---'1171.Jt( .-- �' <i'
Custom Soil Resource Report
Soil Map
` in,',1
N
725620 725700 725780 725860 725940 726020 726100
38°9'22"N
` 38°9'22"N
i
i f � " 0. ,
- � �P
! q} 1,'''', (1
`•• ' 4" o
7. �'R .•Y r '} Rl
-b-'; '„
v
N
a
0
R
f♦ �jj '
{
r Lit
a
N
v 4 t
FI 4
'ts EdgC 5t
cU
0
a o
38°659"N °
38°859'N
725620 725700 725780 725860 725940 726020 726100
3
Map Stale:1:3,400 f printed on A Poba (8.5"x 11")sheetMetes
a
N 0 50 100 200 Feet 300 IN
N 0 150 300 600 900
Map pn lemon:Web Nk�or Comer coo dinates.WCS84 Edge tics:UTM Zone 17N WGS84
6
N.
o Wo C C y N N O C
•
Z7C
T ' O C• f 7 co I7
C
•
co f0 le- CN V a) -c 37of0 O _
O O a : Cu0 2O V v yy Ny cOOc U U 0 y 7 0 V C Ea 3 7 Q=y E co � a 0 co E . cE0Oyyy 0. y 0 Z0 0Nu- N b T a y0N N G l0
• a CW 01 c 03 aO y
;,;('1 Os y NN 01 cowN. • Ef0 w N h d aL m ,D C E O
2'N UE E o o c vy d z a acm� m ▪tyQ Y E U w 0 oacoO is'8. y = 0 U ° aa f0 c,,, 0..,c
y d c . y
Aa
cL y c >0m m o Qo c
72 y E 5 ' 8� � 11) o v, ' a > " p y
• !O 0
T > w•` o5°ly Vf0tr0O7 ` .- R _. o y \ m mac m 30a o u CO 2)asm CaocO 0 a2 'Oa0d EO 'cc y .c a EZ C C Q' L7 y U p W �a EvO N O 3,.
,a O cm m � o0 ' 0a E c TV
y ON
m va 0 ao • -0v
0 8 — . aofi aaa yLc.aE m
ici
� c �•� o om o > > oo CO E ° E o a> CO co • ° v `' 0orn�d c � rLe F2 a co 2 as -o aN g v vLo T _ 6ova a OC cma CC_ Z. c coaE '=a 07 CO N U 2` ,. n, 7C Oc ov d °
'Sc o O 8 a7vo Cvm� _ N a a.
y E C el ...
l0 y N l0 > na d N OC7U y > V71 a) Em
OlN.2 C •- f0'Q N a) o ao co O ..y a _/ NH 3 w E ay n. E co c.) 2 5.5 g it co O o OcN FE
al
H 8 E o
r
O
0.
a)
CC
a)
o0
Cl)
a)
cN.
0
co a
a
aE C ;0
Lao p pLL WU .0 ey c vO C W v 0 a
g.•Z co 2 c y N 15 `W W E m K o
u)) Cl) > 3 0 CO a re E 7 f J '01 7g<
C
Z :: ttaz... ] y 1
W •
w . i 1 It iliw am
W 3 1- m
J
a s
Q 0 Q a C 8 1
3 c .4 W m
'" a. 17 a E w m
m
'c 'c 'c o P o W W 0. a
P. > > > Y o r fn ; a o i 3 Q - - w a
p a a n •W Q. o 'a • o a c `') in
W W W W 5 ; `o W 3 = y co a o
2 2 2 a o y -2 z 2 LL .c `o c O W e 3 $ y
Z d o Ti 'o e o 0 m o @ e = W m c m �' a co o' C o
y u) co c m m 0 0 0 0 . . M a M a K u) u) co in N u)
e a
< E � �— 90 0 . 0 •Al 4( 0 ► > 4- ; . 0 . 4« 'It
1 T
Custom Soil Resource Report
Map Unit Legend
Albemarle Count.Virginia(VA003)
Map Unit Symbol Map Unit Name Acres in AOI Percent of AOI
10 Buncombe loamy sand 5.9 23.6%
14D Chester loam, 15 to 25 percent 5.3 21.2%
slopes
19C Cullen loam,7 to 15 percent 1.4 5.5%
slopes
27C Elioak loam,7 to 15 percent 0.8 3.3%
slopes
34D Glenelg loam, 15 to 25 percent 4.0 15.8%
slopes
34E Glenelg loam,25 to 45 percent 0.0 0.1%
slopes
66E Parker very stony loam,25 to 45 1.4 5.7%
percent slopes
76 Riverview loam 0.2 0.9%
88 Udorthents,loamy 4.7 18.6%
W Water 1.3 5.1%
Totals for Area of Interest 25.1 100.0%
Map Unit Descriptions
The map units delineated on the detailed soil maps in a soil survey represent the sods
or miscellaneous areas in the survey area.The map unit descriptions, along with the
maps, can be used to determine the composition and properties of a unit.
A map unit delineation on a soil map represents an area dominated by one or more
major kinds of soil or miscellaneous areas.A map unit is identified and named
according to the taxonomic classification of the dominant soils. Within a taxonomic
class there are precisely defined limits for the properties of the soils.On the landscape,
however,the soils are natural phenomena,and they have the characteristic variability
of all natural phenomena.Thus, the range of some observed properties may extend
beyond the limits defined for a taxonomic class.Areas of soils of a single taxonomic
class rarely, if ever, can be mapped without including areas of other taxonomic
classes.Consequently,every map unit is made up of the soils or miscellaneous areas
for which it is named and some minor components that belong to taxonomic classes
other than those of the major soils.
Most minor soils have properties similar to those of the dominant soil or soils in the
map unit, and thus they do not affect use and management. These are called
noncontrasting, or similar, components. They may or may not be mentioned in a
particular map unit description. Other minor components, however, have properties
and behavioral characteristics divergent enough to affect use or to require different
management.These are called contrasting,or dissimilar,components.They generally
are in small areas and could not be mapped separately because of the scale used.
8
Appendix II
Contract Drawings
(Under Separate Cover)
i
Appendix III
Specifications
RivANNA
North Fork
Rivanna •
• River WATER & SEWER AUTHORITY
ALBEMARLE COUNTY,VIRGINIA
\Xa t e r MIain
Repair
TECHNICAL
SPECIFICATIONS
RFB No.
if*
cbai
GARY WAYNE FERN5:*
A Lie, No. 048914
3/z,yeas
4'4+,l ONLL 1.**
100% SUBMITTAL
MARCH 2015
1 J 15 100 YEARS 2015
t r UU Kraft Drive, Suite 1200
F I l';hurg. Virginia 24060
North Fork Rivanna River Water Main Replacement Project Table of Contents
RIVANNA WATER& SEWER AUTHORITY
ALBEMARLE COUNTY, VIRGINIA
NORTH FORK RIVANNA RIVER
WATER MAIN REPAIR
March 24, 2015
TABLE OF CONTENTS
DIVISION 02 EXISTING CONDITIONS
02101 Dewatering and Drainage
02230 Clearing and Grubbing
02315 Excavation and Backfill
02316 Fill and Granular Fill Materials
02370 Erosion and Sediment Control
02511 Ductile Iron Pipe and Fittings for Water
02512 Copper Pipe and Tubing
02513 Valves, Hydrants, and Appurtenances
02514 Water Piping Specialties
02515 Water Piping Installation
02516 Water Pipe Testing
02911 Seeding, Topsoiling, Fertilizing, and Mulching
DIVISION 03 CONCRETE
03300 Cast-in-Place Concrete
APPENDIX A APPROVED PRODUCTS LIST
APPENDIX B STANDARD DETAILS
CONTRACT DRAWINGS (Bound Separately)
1. Title Sheet
2. Erosion& Sediment Control and Details
3. Plan and Profile Sta. 10+00 to Sta. 13+25
4. Construction Access& Easements
N:\46601-014\Engineering\Design\Contract_Documents\Specifications\Table of Contents.doc 03/24/15
TC-1
North Fork Rivanna River Water Main Repair Dewatering and Drainage
SECTION 02101
DEWATERING AND DRAINAGE
PART 1 - GENERAL
1.00 STATUTORY REQUIREMENTS
A. Obtain and pay for all permits required for temporary dewatering and drainage
systems.
B. Original permits shall be prominently displayed on the site prior to constructing
dewatering and drainage systems.
1.01 SCOPE OF WORK
A. Furnish, install, operate, monitor, maintain, and remove temporary dewatering and
drainage systems as required to lower and maintain groundwater levels below sub-
grades of excavations and trenches. Prevent surface water runoff from entering or
accumulating in excavations and trenches.
B. Collect and properly dispose of all discharge water from dewatering and drainage
systems in accordance with state and local requirements and permits.
C. Repair damage caused by dewatering and drainage system operations.
D. Remove temporary dewatering and drainage systems when no longer needed.
Restore all disturbed areas.
1.02 RELATED WORK
A. Section 02315, Excavation and Backfill.
B. Section 02370, Erosion and Sediment Control.
PART 2 -PRODUCTS (Not Used)
N:\46601-014\Engineering\Design\Contract_Documents\.Specifications\02101_Dewatering_and_Drainage.doc 03/24/15
02101-1
North Fork Rivanna River Water Main Repair Dewatering and Drainage
PART 3 - EXECUTION
3.01 GENERAL
A. Control surface water and groundwater such that excavation to final grade is made
in-the-dry, and bearing soils are maintained undisturbed. Prevent softening, or
instability of, or disturbance to, the sub-grade due to water seepage.
B. Provide adequate protection against flotation for all work.
C. The anticipated subsurface soil/water conditions shall be considered when selecting
methods of excavation and temporary dewatering and drainage systems. Where
groundwater levels are above the proposed bottoms of excavations, a pumped
dewatering system shall be evaluated for pre-drainage of the soils prior to
excavation to final grade and for maintenance of the lowered groundwater level
until construction has been completed to such an extent that the foundation,
structure, pipe, or fill will not be floated or otherwise damaged. Type of
dewatering system, spacing of dewatering units, and other details of the work are
expected to vary with soil/water conditions at a particular location. Excavation
support system designs shall be prepared by a licensed Professional Engineer
registered in the Commonwealth of Virginia.
3.02 SURFACE WATER CONTROL
A. Control surface water runoff to prevent flow into excavations. Provide temporary
measures such as dikes, ditches, and sumps.
3.03 EXCAVATION DEWATERING
A. Provide and maintain adequate equipment and facilities to promptly remove and
properly dispose of all water entering excavations. Excavations shall be kept in-
the-dry, so as to maintain an undisturbed sub-grade condition throughout
construction below grade, including backfill and fill placement.
B. Pipe shall not be installed in water or be allowed to be submerged prior to
backfilling. Pipe that becomes submerged shall be removed and the excavation
dewatered and restored to proper conditions prior to reinstalling the pipe.
C. Dewatering and drainage operations shall at all times be conducted in such a
manner as to preserve the natural, undisturbed bearing capacity of the sub-grade at
the bottom of the excavation. If the sub-grade becomes disturbed for any reason,
the unsuitable sub-grade material shall be removed and replaced with compacted
granular fill to restore the bearing capacity of the sub-grade to its original
undisturbed condition. Costs of such removal and restoration shall be the
responsibility of the Contractor.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications\02101_Dewatering_and_Drainage.doc 03/24/15
02101-2
•
•
North Fork Rivanna River Water Main Repair Dewatering and Drainage
D. Dewatering and drainage operations shall be conducted in a manner that does not
cause loss of ground or disturbance to the pipe bedding or soil that supports
overlying or adjacent structures.
E. Provide diesel or gasoline powered standby pumping units ready for immediate use
to serve the system in case of failure of normal pumping units.
F. The Contractor shall prevent flotation by maintaining a positive and continuous
operation of the dewatering system. The Contractor shall be fully responsible and
liable for all damages that may result in failure of this system.
G. The Contractor shall take all necessary precautions to preclude the accidental
discharge of fuel, oil, etc., in order to prevent adverse effects on groundwater or
surface water quality.
H. If for any reason the dewatering system is found to be inadequate to meet the
requirements set forth herein, the Contractor shall at his own expense make such
additions, changes and/or replacements as necessary to provide a satisfactory
dewatering system.
I. Removal of dewatering equipment shall be accomplished after the system is no
longer required. The Contractor shall remove the material and equipment
constituting the system.
3.04 DISPOSAL OF DRAINAGE
A. All water discharged from temporary dewatering and drainage systems shall be
disposed of in accordance with the sediment and erosion control plan and as
specified in Section 02370 Erosion and Sediment Control.
END OF SECTION
N:46601-014\Engineering\Design\Contract_Documents\Specifications\02101_Dewatering_and_Drainage.doc 03/24/15
02101-3
North Fork Rivanna River Water Main Repair Clearing and Grubbing
SECTION 02230
CLEARING AND GRUBBING
PART 1 - GENERAL
1.01 SCOPE OF WORK
A. Contractor shall provide all labor, equipment, materials, and incidentals necessary
to perform all clearing and grubbing within the limits of work as shown on the
Drawings and specified herein.
1.02 RELATED WORK
A. Section 02315, Excavation and Backfill.
B. Section 02370, Erosion and Sediment Control.
C. Section 02911, Seeding, Topsoiling, Fertilizing, and Mulching.
PART 2 - PRODUCTS (Not Used)
PART 3 -EXECUTION
3.01 CLEARING
A. The area to be cleared and grubbed shall be completely cleared of all timber, brush,
stumps, roots, grass, weeds, rubbish, and all other objectionable obstructions
resting on or protruding through the surface of the ground. Clearing operations
shall be conducted so as to 1) prevent damage to existing structures and
installations, and to those under construction, and 2) provide for the safety of
employees and others.
B. Minimize damage to trees outside construction limits and preserve as specified
hereinafter.
3.02 GRUBBING
A. Grubbing shall consist of the complete removal of all stumps, roots larger than 1-
1/2 inches in diameter, matted roots, brush, timber, logs, concrete rubble, and all
other debris encountered. All depressions excavated below the original ground
surface for or by the removal of such objects shall be refilled with suitable
materials and compacted to a density conforming to the surrounding ground
surface.
N:\46601-014\EngincerineDesign\Contract_Documents\Specifications`02230_Clearing_and_Grubbing.doc 03/24/15
02230-1
North Fork Rivanna River Water Main Repair Clearing and Grubbing
3.03 DISPOSAL OF CLEARED AND GRUBBED MATERIAL
A. The Contractor shall dispose of all material and debris from the clearing and
grubbing operation by hauling such material and debris away to an approved dump.
Disposal by burning or burial will not be permitted.
3.04 PRESERVATION OF TREES
A. Trees beyond construction limits shall be carefully protected from damage. The
Contractor shall erect such barricades, guards, and enclosures he may consider
necessary for the protection of the trees during all construction operations.
Materials and equipment shall be maintained beyond the drip lines of such trees to
the extent practicable. Where required, cut back limbs and branches to preserve
trees and paint with an approved tree wound paint.
3.05 PRESERVATION OF DEVELOPED PRIVATE PROPERTY
A. The Contractor shall exercise extreme care to avoid unnecessary disturbance of
adjacent private property. Trees, shrubbery, gardens, lawn, and other landscaping
damaged by the Contractor beyond the construction limits shall be restored to pre-
construction conditions.
B. All soil preparation procedures and replanting operations shall be performed under
the supervision of a licensed nurseryman approved by the Owner.
END OF SECTION
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02230_Clearing_and_Grubbing.doc 03/24/15
02230-2
North Fork Rivanna River Water Main Repair Excavation and Backfill
SECTION 02315
EXCAVATION AND BACKFILL
PART 1 - GENERAL
1.00 STATUTORY REQUIREMENTS
A. All excavation, trenching, sheeting, bracing, etc., shall comply with the requirements of
OSHA excavation safety standards (29 CFR Part 1926 Subpart P Excavations) and any
State and local requirements. Where conflict between OSHA, State, and local regulations
exists, the most stringent requirements shall apply.
1.01 SCOPE OF WORK
A. Furnish all labor, materials, equipment, and incidentals required and perform all excavation
work and grading; place and compact backfill and fill; and dispose of unsuitable waste and
surplus materials as specified herein.
B. Provide the services of a licensed Professional Engineer, registered in the Commonwealth
of Virginia, to prepare temporary excavation support system designs and to inspect the
installed temporary support systems.
C. Furnish and install temporary excavation support systems, including sheeting, shoring, and
bracing, to insure the safety of personnel and protect adjacent structures, piping, etc., in
accordance with federal, state and local laws, regulations, and requirements.
1.02 RELATED WORK
A. Section 02101, Dewatering and Drainage.
B. Section 02230, Clearing and Grubbing.
C. Section 02316, Fill and Granular Fill Materials.
D. Section 02370, Erosion and Sediment Control.
E. Section 02911, Seeding, Topsoiling, Fertilizing, and Mulching.
1.03 SUBMITTALS
A. Test reports of compaction testing on embankment, fill, and backfill materials shall be
submitted directly to the Owner with copies to Contractor.
N:\46601-014\Engineering\Design'Contract_Documents\Specifications'A2315_Excavation_and_Backfill.doc 03/24/15
02315-1
North Fork Rivanna River Water Main Repair Excavation and Backfill
1.04 REFERENCE STANDARDS
A. American Society for Testing and Materials(ASTM).
1. ASTM D698 - Test Method for Laboratory Compaction Characteristics of Soils Using
Standard Efforts.
2. ASTM D1557 - Test Methods for Laboratory Compaction Characteristics of Soil
Using Modified Effort.
B. Virginia Department of Transportation(VDOT).
1. Road and Bridge Specifications.
C. Where reference is made to one of the above standards, the revision in effect at the time of
bid opening shall apply.
1.05 QUALITY ASSURANCE
A. Excavation support system designs shall be prepared by a licensed Professional Engineer
registered in the Commonwealth of Virginia.
B. Materials will be tested and observed as described in the following paragraphs. Free access
to the work for selection of test materials, testing, and observations shall be granted to the
independent testing laboratory.
1. Materials used in the work shall be tested by a certified independent testing
laboratory engaged by the Contractor to verify conformance with the requirements
of these Specifications.
2. Testing methods shall comply with the latest applicable ASTM or VDOT
Standards specified.
3. During the placement of bedding and backfill, the soils testing laboratory shall
perform in-place soil density testing to confirm that bedding and backfill material
has been compacted in accordance with the requirements of this Section. The
Owner may designate areas where soil density testing will not be required.
a. It shall be required that a minimum of one (1) compaction test for each of
three depth locations will be conducted on trench backfill and in three
locations of the project; one on the north-side river bank, one on the south-
side river bank, and one under the Route 29 southbound bridge, for a total
of nine compaction tests. The Contractor shall bear the expense of all
compaction tests. The precise location of tests may be selected in the field
by the Owner's RPR and will not necessarily be limited to regular intervals.
W6601-014\EngineerineDesign�Contract_Documents\Specifications`+02315_Excavation_and_Backfill.doc 03/24/15
02315-2
North Fork Rivanna River Water Main Repair Excavation and Backfill
b. The results of all compaction tests shall be submitted to the Owner for
review and approval prior to acceptance of construction. If the tests
indicate the required density has not been obtained, the Contractor shall
remove, replace and recompact the material to the specified density. Fail-
ure of any compaction tests may result in additional compaction tests being
required.
c. For trenches within paved areas of VDOT roadways, Contractor shall
submit compaction testing results to VDOT personnel and comply with
Land Use Permit requirements as applicable.
4. Materials that have been previously tested may be subjected to further testing from
time to time and may be rejected if it is determined that they do not conform to the
requirements of these Specifications. Rejected materials shall be removed from the
Work immediately when so directed by the Owner, notwithstanding the results of
previous testing.
1.06 PROJECT/SITE CONDITIONS
A. Existing structures. The Drawings may show certain surface and underground structures
adjacent to the Work. This information has been obtained from existing records. It is not
guaranteed to be correct or complete and is shown for the convenience of the Contractor.
Contractor shall explore ahead of the required excavation to determine the exact location
of all structures. They shall be supported and protected from damage by Contractor. If
they are broken or damaged by Contractor, Contractor shall restore them immediately at
their expense.
B. Existing utilities.
1. It shall be the responsibility of the Contractor to conduct the Work in such a
manner as to avoid damage to, or interference with, any utility services. The
Contractor is responsible for providing temporary supports for any utility that may
be affected by its work. If any damage, interference, or interruption of service
occurs as a result of its work, it shall be the Contractor's responsibility to promptly
notify the Owner and utility owner of the occurrence and to repair, or cause to be
repaired, the damage immediately, at Contractor's expense, and to the satisfaction
of the Owner and the owner of the utility.
2. It shall be the Contractor's responsibility to uncover and expose the location of all
service connections to avoid damage or interruption of service. If damage occurs,
the Contractor shall make the necessary repairs in accordance with the above
requirements.
N:k16601-014\Engineering\Design\Contract_Documents\Specifications`02315_Excavation_and_Backfill.doc 03/24/15
02315-3
North Fork Rivanna River Water Main Repair Excavation and Backfill 1
3. It is the responsibility of the Contractor to determine in advance of beginning the
construction effort the exact location of all utilities, and the affect they will have on
the Work. Contractor shall contact "Miss Utility" prior to starting work, allowing
for the 2-working day marking period in accordance with the Underground Utility
Damage Prevention Act. All costs related to identification of utility location shall
be the responsibility of the Contractor.
1. Do not interrupt existing utilities serving facilities occupied and used by the
Owner or others, except when permitted in writing by the Owner and then only
after acceptable temporary utility services have been provided.
2. Demolish and completely remove from site the existing underground utilities
indicated to be removed. Coordinate with utility companies for shut-off of
services if lines are active.
C. If conditions vary with those described in the Contract Documents or Supplemental
Project Information, are encountered during construction, immediately notify the Owner in
accordance with the requirements of the General Conditions.
1.07 DEFINITIONS
A. Where the phrase "in-the-dry" is used in this Section, it shall be defined to mean a soil sub-
grade that is stable with no ponded water, mud, or muck, and is able to support
construction equipment without rutting or disturbance.
B. Where used in this Section, "structures" refers to all buildings, bridges, wet wells,
manholes, and below- grade vaults.
PART 2-PRODUCTS
2.01 GENERAL
A. Fill materials designated for use in this Section are specified in Section 02316 Fill and
Granular Fill Materials.
B. Filter fabric shall conform to the requirements of Standard and Specification 3.05 Silt
Fence, of the Virginia Erosion and Sediment Control Handbook, latest edition.
C. High strength geotextile fabric.
1. Geotextile fabric shall conform to the following requirements.
a. Minimum tensile strength of 360 lbs. per ASTM D4632.
b. Minimum puncture strength of 150 lbs. per ASTM D4833.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications\02315_Excavation_and_BackfilLdoc 03/24/15
02315-4
North Fork Rivanna River Water Main Repair Excavation and Backfill
c. Apparent opening size to be equal to or greater than the U.S. Standard
Sieve No. 40 per ASTM D4751.
d. Fabric material shall be woven polypropylene or polyester.
e. High strength geotextile fabric shall be LINQ Industrial Fabrics, Inc., GTF
375N, or approved equal.
PART 3 - EXECUTION
3.01 PREPARATION
A. Contact "Miss Utility" before beginning excavations and allow required time for marking.
Before excavating within 20 feet of utility poles and gas lines, and after pipeline stake out,
coordinate construction with the appropriate utility company. Immediately notify the
Owner of any conflict of new Work with existing utilities that may require relocation of
new Work or of existing utilities. All necessary support of utility poles shall be the sole
responsibility of the Contractor at no additional expense to the Owner.
B. Prior to excavation, other utilities and underground facilities shall be located to confirm
location, proper depth, and clearances. Care shall be taken in excavating to prevent
damage to underground structures, utilities, and adjacent structures and properties. When
approaching and crossing such installations, a combination of installation methods may be
used. Trenching equipment shall not be used within 2 feet of existing utilities and within
the distances from existing structures indicated on the plans.
C. Test holes.
1. Perform exploratory excavation work (test holes) for the purpose of verifying the
location of underground utilities and structures and to check for unknown utilities
and structures, prior to commencing excavation work. Contractor shall immediately
notify the Owner if such exploratory work yields information that may alter the
design or installation of the pipeline.
2. Test holes shall be backfilled as soon as the desired information has been obtained.
Backfilled surfaces shall be stabilized in accordance with approved erosion and
sediment control plans. Test holes in asphalt pavement shall be patched with a
thickness equal to existing adjacent pavement.
D. Dewatering and drainage systems.
1. Temporary dewatering and drainage systems shall be in place and operational prior
to beginning excavation work.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications902315_Excavation_and_Backfill.doc 03/24/15
02315-5
'
North Fork Rivanna River Water Main Repair Excavation and Backfill
3.02 EXCAVATION SUPPORT
A. Furnish, install, monitor, and maintain excavation support (e.g., shoring, sheeting, bracing,
trench boxes, etc.) as required by Federal, State, or local laws, ordinances, regulations,
and safety requirements. Support the sides of excavation to prevent any movement which
could in any way reduce the width of the excavation below that necessary for proper
construction and protect adjacent structures from undermining, settlement, or other
damage. Take care to prevent the formation of voids outside of sheeting. If voids occur
behind sheeting, immediately backfill and compact the voids with common fill material.
Voids in locations that cannot be properly compacted upon backfilling shall be filled with
2000 psi concrete or flowable fill.
B. Install excavation supports outside the neat lines of foundations. Supports shall be plumb
and securely braced and tied in position. Excavation support shall be adequate to
withstand all pressures to which the supports will be subjected. Any movement or bulging
of supports shall be corrected to provide the necessary clearances, dimensions, and
structural integrity.
C. Excavation supports left in place.
1. Excavation supports are required to remain in place if installed below the
foundation and within a zone extending from the edge of the foundation and then
outward and downward at 1 H:1 V below the pipe spring line, or as specified on the
Drawings.
2. The Owner may direct that certain excavation supports remain in place, or be cut
off at any specific elevation. If the Contractor believes that such a directive
increases Contractor's cost and would thereby entitle Contractor to a change in
contract cost, Contractor shall notify the Owner in accordance with the applicable
article(s) in the Contract General Conditions pertaining to changes in the Work.
3. The right of the Owner to direct that certain excavation supports remain in place
shall not be construed as creating any obligation to give such direction, nor shall
failure to give such direction relieve the Contractor from liability for damages to
persons or property occurring from or upon the work occasioned by negligence, or
otherwise growing out of a failure on the part of the Contractor to leave in place
sufficient excavation supports to prevent any movement of the ground or damage
to adjacent structures.
D. Excavation supports shall be carefully removed in such manner so as not to endanger the
Work or other adjacent structures, utilities, or property. All voids left or caused by
withdrawal of supports shall be filled with flowable fill.
E. Excavation support systems shall be inspected during and after installation and monthly
thereafter by the support system design engineer. The support system design engineer
N:W6601-014\Engineering\Design\ContTact_Documents\Specifications'A2315_Excavation_and_Backfill.doc 03/24/15
02315-6
•
North Fork Rivanna River Water Main Repair Excavation and Backfill
shall submit a written report to the Contractor for each inspection describing
recommendations, if any.
3.03 EXCAVATION BELOW GRADE
A. If the bottom of any excavation is taken out below the limits shown on the Drawings, it
shall be refilled with 4-inch layers of compacted granular fill or other material approved by
the Owner.
B. If the sub-grade is damaged by water, remove the unsuitable material and replace it with
compacted granular fill or other approved material at Contractor's own expense so that the
condition of the sub-grade meets with the approval of the Owner before any work is
placed thereon.
C. If, in the opinion of the Owner, the material, in its undisturbed natural condition at or
below the normal grade of the excavation as indicated on the Drawings, is unsuitable for
the work being performed, it shall be removed to such depth and width as directed and be
replaced with suitable material for which compensation will be made at the unit prices
established in the Contract.
3.04 STRUCTURE EXCAVATION
A. Excavation shall be made to the grades shown on the Drawings and to such widths as will
give suitable room for construction of the structures for bracing, shoring, and dewatering.
The bottom of the excavations shall be rendered firm and dry and in all respects acceptable
to the Owner.
B. Excavation and dewatering shall be accomplished by methods that preserve the
undisturbed state of sub-grade soils. Exposed soil and rock sub-grades shall be proof
rolled with at least two coverages of the compaction equipment. Sub-grade soils that
become soft, loose, "quick," or otherwise unsatisfactory for support of structures as a
result of inadequate excavation dewatering, proof rolling, or other construction methods
shall be removed and replaced by granular fill at the Contractor's expense.
C. Dewatering shall be such as to prevent boiling or detrimental under-seepage at the base of
the excavation as specified herein.
D. Excavation equipment shall be satisfactory for carrying out the Work in accordance with
the requirements specified. In no case shall the earth be plowed, scraped, or dug with
machinery so near to the finished sub-grade as to result in excavation of or disturbance of
material below grade. Equipment used for excavation to final sub-grade shall furnish an
undisturbed sub-grade surface.
E. During final excavation to sub-grade level, take whatever precautions are required to
prevent disturbance and remolding. Material that has become softened and mixed with
N:k16601-014\Engineering\Design\Contract_Documents\Specifications\02315_Excavation_and_Backfill.doc 03/24/15
02315-7
4 4
North Fork Rivanna River Water Main Repair Excavation and Backfill
water shall be removed. Hand excavation of the final 3 to 6 inches may be required to
obtain a satisfactory undisturbed bottom. The Owner will be the sole judge as to whether
the work has been accomplished satisfactorily.
3.05 EXCAVATION AND BACKFILLING FOR UNDERSLAB TRENCHES
A. Excavation for all pipelines beneath structures shall be carried out with the excavating
equipment operating from above the sub-grade for the structure. The excavation shall be
carried out in-the-dry and in a manner that will preserve the undisturbed state of the sub-
grade soils. The excavations may be completed with shoring and bracing at the
Contractor's option with no additional cost to the Owner.
3.06 TRENCH EXCAVATION AND BACKFILLING
A. Excavation for all trenches required for the installation of pipes shall be made to the
depths indicated on the Drawings and in such a manner and to such widths as will give
suitable room for laying the pipe within the trench, for bracing and shoring, and
dewatering. Render the bottom of the excavations firm and dry and in all respects
acceptable to the Owner.
Pavement, when encountered, shall be cut along straight lines before excavating. All
excavations in concrete shall be precut in neat straight lines with a pavement breaker or
saw. In sidewalks the excavation shall be a minimum of one "block" in size. If the
sidewalk is combined with the curb, the curbing shall also be removed.
B. Rock shall be removed to a minimum 6-inch clearance around the bottom and 12-inch
minimum clearance on the sides of all pipe being laid.
C. Excavation of earth material below the bottom of a trench shield shall not exceed the
limits established by ordinances, codes, laws, and regulations.
1. When using a trench shield for installing rigid pipe, any portion of the shield
extending below mid-diameter shall be raised above this point prior to moving the
shield ahead to install the next pipe.
2. When using a trench shield for installing flexible pipe (PVC, PE, etc.), the bottom
of the shield shall not extend below mid-diameter at any time.
3. When a shield is removed or moved ahead, extreme care shall be taken to prevent
the movement of pipe or the disturbance of the pipe bedding. Pipe that has been
disturbed shall be removed and reinstalled at Contractor's own expense.
D. Where pipelines are to be constructed in fill areas, all fill material to a level 2 feet above
the "top of pipe" elevation shall be placed and compacted to 95 percent dry density as
determined by ASTM D698 prior to excavating pipe trench.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02315_Excavation_and_Backfill.doc 03/24/15
02315-8
North Fork Rivanna River Water Main Repair Excavation and Backfill
E. Backfill excavations as promptly as work permits, removing bracing and shoring as
backfilling progresses.
F. Where the pipes are laid in unpaved areas, initial backfill as noted on the Detail Drawings
shall be placed and compacted in 6-inch lifts to a minimum depth of 24 inches above top
of pipe. Compaction shall be to 95 percent of maximum dry density as determined by
ASTM D698. Pipe bedding shall be as shown on the Detail Drawings.
G. In unpaved areas, the remainder of the trench shall be filled with common fill in lifts not to
exceed 1 foot and thoroughly compacted by rolling or tamping to prevent subsequent
settling. The top 1-foot lift shall be common fill. The backfill shall be mounded 3 inches
above the existing grade or as directed. Wherever a loam or gravel surface exists prior to
excavation, it shall be removed, conserved, and replaced to the full original depth as part
of the Work. In some areas it may be necessary to remove excess material during the
clean-up process so that the ground may be restored to its original level and condition. If
storage of loam, gravel, or topsoil is not preferred, replace it with material of equal quality
and in equal quantity at Contractor's own expense. Compaction shall be to 95 percent of
maximum dry density as determined by ASTM D698.
H. Where the pipes are laid in streets or other paved areas within the VDOT right-of-way, the
trench shall be backfilled, from the spring line of the pipe, with VDOT #21 B crushed
stone in 6 inch lifts thoroughly compacted by rolling or tamping. Compaction shall be to
95 percent of maximum dry density as determined by ASTM D698.
I. Where the pipes are laid in streets or other paved areas within the VDOT right-of-way, a
temporary gravel surface may be placed for a maximum of 5 days, but not extending over
a weekend or holiday. At the end of each work week, Contractor shall replace the
temporary gravel with a temporary pavement patch, or the final pavement surface.
J. Where shown on the plans, along the length of the pipeline, construct impervious dams or
bulkheads of clay or concrete in the trench bottom at 300-foot intervals or at manholes
and structures, whichever is less, to obstruct the free flow of groundwater after
construction is completed. Install impervious dams at all points where a pipe trench enters
an excavated area where a permanent under-drain system is installed.
3.07 MISCELLANEOUS EXCAVATION
A. Perform all miscellaneous excavations as required to complete the Work. Make all
excavations necessary to permit the placing of loam and plants, for constructing roadways,
and any other miscellaneous earth excavation required under the Contract.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02315_Excavation_and_Backfill.doc 03/24/15
02315-9
North Fork Rivanna River Water Main Repair Excavation and Backfill
3.08 ROCK AND BOULDER EXCAVATION AND DISPOSAL
A. Blasting will not be permitted.
B. If rock excavation is classified for purposes of payment, the Owner must approve all rock
excavation and processes prior to any rock excavation.
C. Rock excavation may be performed by jack hammering, expansive chemical splitting, or
other similar processes.
D. Fragmented rock with dimensions not exceeding 4 inches in any direction may be mixed
with common fill and used as common fill in accordance with Section 02316 Fill and
Granular Fill Materials. Unused rock and boulders shall be removed and disposed of off-
site.
E. If rock excavation is classified for purposes of payment, rock shall be defined as material
in beds, ledges, unstratified masses, and conglomerate deposits and boulders of rock
material exceeding 1 cu. yd. that cannot be removed by rock excavating equipment
equivalent to the following in size and performance ratings, without systematic drilling,
ripping, or blasting:
1. Late-model, loader/backhoe; equipped with a 12-18 inch wide, short-tip-radius
rock bucket; rated at not less than 90-hp flywheel power with bucket-curling force
of not less than 12,500 lbf and dipper dig force of not less than 8,000 lbf;measured
according to SAE J-1179.
3.09 DISPOSAL OF SURPLUS MATERIAL
A. Excess excavated materials shall be removed from the site and disposed of in accordance
with local, state, and federal regulations. Materials shall be neatly piled so as to
inconvenience as little as possible the public and adjoining property owners until used or
otherwise disposed of as specified below.
Erosion and sediment control measures shall be installed in accordance with Section
02370 Erosion and Sediment Control as appropriate.
B. Suitable excavated material meeting the requirements of Section 02316 Fill and Granular
Fill Materials may be used for fill embankments or backfill on the Work as required.
C. Surplus materials shall become the property of the Contractor and shall be removed and
disposed off site.
N:k16601-014\Engineering\Design\Contract_Documents\Specifications`02315_Excavation_and_Backfill.doc 03/24/15
02315-10
North Fork Rivanna River Water Main Repair Excavation and Backfill
3.10 GRADING
A. Grading in preparation for placing of loam, planting areas, paved walks and drives, and
appurtenances shall be performed in all places that are indicated on the Drawings, to the
lines, grades, and elevations shown, and shall be performed in such a manner that the
requirements for formation of embankments can be followed. All material encountered, of
whatever nature within the limits indicated, shall be removed and disposed of in
accordance with these specifications. During the process of grading, the sub-grade shall
be maintained in such condition that it will be well drained at all times.
B. If at the time of grading it is not possible to place any material in its final location, it shall
be stockpiled in approved areas for later use. No extra payment will be made for the
stockpiling or double handling of excavated material.
C. The Owner reserves the right to make minor adjustments or revisions in lines or grades if
found necessary as the Work progresses.
D. Stones or rock fragments larger than 4 inches in their greatest dimension will not be
permitted and shall be removed from the site.
E. In cuts, all loose or protruding rocks on the bank slopes shall be barred loose or otherwise
removed to line or finished grade of slope. All cut and fill slopes shall be uniformly
dressed to the slope, cross section, and alignment shown on the Drawings.
3.11 RIPRAP FOR SLOPE STABILIZATION
A. Prepare sub-grade for riprap. Remove vegetation, brush, tree stumps, or other
objectionable material. Cut or fill to the required lines and grades. Any fills required shall
be of the same type as and compacted to a density approximating that of the surrounding
undisturbed material.
B. Before installing riprap, install geotextile filter fabric as shown on the Drawings and in
accordance with the geotextile manufacturer's instructions.
C. Place riprap as soon as practicable after embankment construction. Limit lag between
placement of embankment and riprap protection to the least time possible, and prevent
mixture of soil with riprap material.
D. Place riprap and geotextile bedding as shown on the Drawings and in conformance to the
requirements of VDOT Road and Bridge Specifications Section 414 - Riprap. Geotextile
bedding shall be in conformance with high strength geotextile fabric specified in this
section. Place stones so that the weight of the stones is carried by the underlying material
and not by the adjacent stones. Place large stones at the bottom of the slope. Fill spaces
between stones with spalls of suitable size to construct a solid, stable slope, free from
large voids and defects.
END OF SECTION
N:\46601-014\Engineering\Design\Contract_DocumentsSpecifications\02315_Excavation_and_Backfill.doc 03/24/15
02315-11
North Fork Rivanna River Water Main Repair Fill and Granular Fill Materials
SECTION 02316
FILL AND GRANULAR FILL MATERIALS
PART 1 - GENERAL
1.01 DESCRIPTION
A. Granular fill materials are specified in this Section, but their use for bedding pipe,
replacement of unsuitable materials, cushion in ledge excavation, pavement base,
foundation support, fill and backfill, and similar uses are specified in detail elsewhere.
1.02 RELATED WORK
A. Section 02315, Excavation and Backfill.
1.03 SUBMITTALS
A. At least five(5)working days prior to the date of anticipated use of any backfill or fill
material, Contractor shall supply material for testing.
1.04 REFERENCE STANDARDS
A. American Association of State Highway&Transportation Officials(AASHTO).
1. Standard Specifications for Transportation Materials and Methods of Sampling and
Testing.
B. American Society for Testing and Materials(ASTM).
1. Standard Specifications as referenced.
C. Virginia Department of Transportation(VDOT).
1. Road and Bridge Specifications.
2. Materials Division, Virginia Test Methods(VTM).
PART 2 PRODUCTS
2.01 MATERIALS
A. Riprap shall conform to VDOT Road and Bridge Specifications Section 414.
/4:W6601-014\Engineering\Design\Contract_Documents\Specifications\02316_Fili_and_Granular_Fill_Materials.doc 03/24/15
02316-1
Ali
•
,
North Fork Rivanna River Water Main Repair
Fill and Granular Fill Materials
B. Gravel or crushed stone shall be open-graded coarse aggregate with clean, hard, tough,
and durable pieces free from adherent coatings and deleterious amounts of friable, thin,
elongated, or laminated pieces, soluble salts, or organic materials. Coarse aggregate
shall conform to VDOT Road and Bridge Specifications Section 203 and the following
requirements.
1. VDOT No. 57: Grade B or better stone conforming to the following gradation when
tested in accordance with AASHTO T27.
Sieve % Passing by
Weight
1-1/2" Min. 100
1" 95 ±5
1/2" 43 ± 17
No.4 Max. 7
No. 8 Max. 3
2. VDOT No. 68: Grade B or better stone conforming to the following gradation when
tested in accordance with AASHTO T27.
Sieve % Passing by
Weight
1" Min. 100
3/4" 95 ±5
3/8" 48± 17
No.4 Max. 20
No. 8 Max. 8
No. 16 Max. 5
3. VDOT No. 1: Grade B or better stone conforming to the following gradation when
tested in accordance with AASHTO T27.
Sieve % Passing by
Weight
4" Min. 100
3-1/2" 95±5
2-1/2" 43 ± 17
1-1/2" Max. 15
3/4" Max. 5
N:kt6601-014\Engineering\DesignContract Documents\Specifications02316_Fill_and_Granular_Fill_Materials.doc 03/24/15
02316-2
North Fork Rivanna River Water Main Repair Fill and Granular Fill Materials
C. VDOT No. 25: Crusher run aggregate shall be crushed from stone, slag or gravel, and
shall contain all of the sizes produced when the original aggregate is reduced through a
series of crushers to the maximum size specified. The material shall conform to the
following gradation when tested in accordance with AASHTO T27.
Sieve % Passing by
Weight
1-1/2" Min. 100
3/4" 95±5
No.4 32± 18
D. Fine aggregate shall be crushed from Grade A stone or gravel and shall conform to the
requirements of VDOT Road and Bridge Specifications Section 202, Grading F or G.
The material shall conform to the following gradations when tested in accordance with
AASHTO T27.
Sieve Grading F Grading G
% Passing by Weight % Passing by Weight
3/8" 100 100
No.4 92±8
No. 8 80±20 _
No. 16 62±22 70±30
No. 30 39± 19 50±35 _
No. 50 Max. 26 Max. 26
No. 100 Max. 10 Max. 10
No. 200 Max. 7 Max. 5
E. VDOT 21B: Structural fill shall consist of gravel stone or slag screenings; fine
aggregate and crushed coarse aggregate; sand-clay-gravel mixtures; or combinations of
these materials. It shall be free of organic material, loam, wood, trash, snow, ice, frozen
soil, and other objectionable material and shall conform to the following requirements:
Sieve % Passing by
Weight
2" 100
1" 85 to 95
3/8" 50 to 69
No. 10 20 to 36
No.40 9 to 19
No. 200 4 to 7
N:\46601-014\Engineering\Design\Contract_Documents4Specifications\02316_Fill_and_Granular_Fill_Materials.doc 03/24/15
02316-3
North Fork Rivanna River Water Main Repair Fill and Granular Fill Materials
F. Screened gravel shall be hard, durable, rounded, or sub-angular particles of proper size
and gradation and shall be free from sand, loam, clay, excess fines, and other deleterious
materials. Screened gravel shall be graded within the following limits:
Sieve % Finer by
Size Weight
5/8" 100
1/2" 40 to 100
3/8" 15 to 45
No. 10 Oto 5
G. Common fill shall consist of uniformly graded mineral soil, substantially free of clay,
organic material, loam, wood, trash, snow, ice, frozen soil, and other objectionable
material which may be compressible, or which cannot be compacted properly. Common
fill shall not contain rocks larger than 4 inches in any dimension, broken concrete,
masonry, rubble, asphalt pavement, or other similar materials.
1. Common fill shall have a maximum 75 percent passing the No. 40 sieve and a
maximum of 20 percent passing the 200 sieve.
2. Soft, wet, plastic soils that may be expansive, and clay soils having natural in-place
water content in excess of 30 percent, shall not be used.
3. Soils containing more than 5 percent(by weight) fibrous organic materials or having
a plasticity index(PI) greater than 30 shall not be used.
4. Rocks larger than 2 inches in any dimension shall not be permitted within 12 inches
of finished grade.
H. Select or initial backfill shall be as specified for common fill, except that the material shall
contain no stones and shall have a plasticity index less than 20. Select or initial backfill
used above/around the pipe may contain no stones greater than 1 inch.
I. Sand shall conform to VDOT Road and Bridge Specifications Section 202, Grade A for
fine aggregate.
J. Impervious fill shall consist of on-site clayey sandy silt or imported material with a
permeability coefficient(K-value) less than 1 x 10-'that can be readily spread and
compacted. Low permeability fill shall not be placed under sidewalks or paved areas.
2.03 FLOWABLE FILL
A. Flowable fill shall be in accordance with VDOT S302A0B, Special Provision for
Flowable Backfill.
PART 3—EXECUTION (Not Used)
END OF SECTION
N:\46601-014\Engineering\DesignContract_Documents\Specifications 02316_Fill_and_Granular_FiII_Materials.doc 03/24/15
02316-4
North Fork Rivanna River Water Main Repair Erosion and Sediment Control
SECTION 02370
EROSION AND SEDIMENT CONTROL
PART 1 - GENERAL
1.01 SCOPE OF WORK
A. Furnish all labor, materials, equipment, permits, and incidentals necessary to perform all
installation, maintenance, removal, and area cleanup related to erosion and sedimentation
control work as specified, shown, and required by the Owner, local sediment control
inspectors, and any other regulatory agency that has control or jurisdiction in the area in
which the project is located. The Work shall include, but not necessarily be limited to,
installation of temporary access ways and staging areas, silt fences, block and gravel
filters, sediment traps, diversion dikes, splash aprons, sediment removal and disposal,
device maintenance, removal of temporary devices, temporary mulching, erosion control
matting installation, permanent stabilization, and final cleanup.
1.02 RELATED WORK
A. Section 02101, Dewatering and Drainage.
B. Section 02230, Clearing and Grubbing.
C. Section 02315, Excavation and Backfill.
D. Section 02911, Seeding,Topsoiling, Fertilizing, and Mulching.
1.03 SUBMITTALS
A. Contractor shall submit to the Owner technical product literature for all commercial
products to be used for sedimentation and erosion control.
1.04 REFERENCE SPECIFICATIONS
A. The materials and method of construction shall be in accordance with the latest edition
of the Virginia Erosion and Sediment Control Handbook.
1.05 PERFORMANCE REQUIREMENTS
A. Contractor shall have at least one (1) employee that has successfully completed the
VDOT Erosion & Sediment Control Contractor Certification training and be a DEQ
Responsible Land Disturber (RLD). This person shall be on site during all land
disturbance activities and will be responsible for insuring compliance with all applicable
local, State and Federal erosion and sediment control regulations during land disturbance
N:\46601-014\Engineering\DesignContract_Documents\Specifications`02370_Erosion_and Sediment Control.doc 03/24/15
02370-1
rr�►
North Fork Rivanna River Water Main Repair Erosion and Sediment Control
activities. This person must have their certification card with them while on the project
site. The land use permit or erosion and sediment control permit will be suspended if
proof of certification cannot be provided. Improper installation, maintenance and
removal of erosion and sediment control devices may result in revocation of VDOT
Erosion& Sediment Control Contractor Certification.
B. Contractor shall be responsible for the timely installation and maintenance of all
sedimentation control devices necessary to prevent the movement of sediment from the
construction site to off-site areas or into the stream system via surface runoff or
underground drainage systems. Measures in addition to those shown on the Erosion and
Sediment Plan necessary to prevent the movement of sediment off-site shall be installed,
maintained, removed, and cleaned up at no additional cost to the Owner. Should the
Contractor fail to control the movement of sediment from the construction area into the
storm sewer system, the Owner may at its discretion require the Contractor to clean the
sediment from the affected reaches of the storm sewer system at the Contractor's
expense.
D. Erosion and Sediment Control measures shall conform to the requirements of the
Virginia Erosion and Sediment Control Law and Regulations and the Virginia Erosion
and Sediment Control Handbook(VESCH).
E. Roadway drainage shall NOT be blocked or diverted. The shoulders, ditches, roadside,
drainage facilities and pavement shall be kept in an operable condition satisfactory to the
VDOT. Necessary precautions shall be taken by the Contractor to insure against
siltation of adjacent properties, streams, etc., in accordance with VDOT's current
standards or as prescribed by VDOT's Environmental Manual and VDOT's
Representative.
F. Where Contractors' efforts to control erosion have been demonstrated to be ineffective
or potentially ineffective in the opinion of the Owner, the Owner may order that the
Erosion Control Plan be amended and that additional erosion control measures be
constructed at no additional cost to the Owner.
PART 2 -PRODUCTS
2.01 MATERIALS
A. Construction Entrance shall conform to the requirements of VESCH Standard and
Specification 3.02.
B. Construction Road Stabilization shall conform to the requirements of VESCH Standard
and Specification 3.03
C. Silt fence shall conform to the requirements of VESCH Standard and Specification 3.05.
N:\46601-014TngineeringDesign\Contract_Documents\Specifications\02370_Erosion_and_Sediment_Control.doc 03/24/15
02370-2
North Fork Rivanna River Water Main Repair Erosion and Sediment Control
D. Utility Stream Crossing shall conform to the requirements of VESCH Standard and
Specification 3.25. Cofferdam Utility Crossing shall be used in accordance with the
VESCH.
E. Dewatering Structure shall conform to the requirements of VESCH Standard and
Specification 3.26.
F. Topsoiling shall conform to the requirements of VESCH Standard and Specification
3.30, to provide a suitable growth medium for final site stabilization with vegetation.
Contractor shall strip the existing top soil and stockpile it in an approved manner for
placement of final restoration, or may elect to haul in top soil from elsewhere.
G. Temporary Seeding shall conform to the requirements of VESCH Standard and
Specification 3.31.
H. Permanent Seeding shall conform to the requirements of VESCH Standard and
Specification 3.32, to permanently stabilize disturbed non-paved and non-graveled areas.
I. Straw mulch shall conform to the requirements of VESCH Standard and Specification
3.35 Mulching, and shall be utilized on all newly graded areas to protect against
washouts and erosion. Straw mulch must be anchored immediately after spreading to
prevent displacement.
1. Latex acrylic copolymer, such as Soil Sealant with coalescing agent as manufactured
by Soil Stabilization Co., Merced, CA, or approved equivalent shall be used as straw
mulch tackifier.
J. Erosion control matting shall be installed in seeded drainage swales and ditches if needed
to resist the velocity of runoff. Erosion control matting shall be from the Virginia
Department of Transportation's approved products list for the use specified, or VESCH
Standard and Specification 3.36 Soil Stabilization Blankets&Matting.
K. Other materials shall be as specified by the Virginia Erosion and Sediment Control
Handbook(VESCH), latest edition.
PART 3-EXECUTION
3.01 INSTALLATION
A. Installation of all erosion and sediment control measures shall be performed in
accordance with the VESCH.
3.02 INSPECTIONS AND MAINTENANCE
A. Inspections.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02370_Erosion and_Sediment_Control.doc 03/24/15
02370-3
North Fork Rivanna River Water Main Repair
Erosion and Sediment Control
1. Contractor shall make a visual inspection of all erosion control devices once per
week and promptly after every rain event. If such inspection reveals that additional
measures are needed to prevent movement of sediment to off-site areas, Contractor
shall promptly install additional devices as needed. Sediment controls in need of
maintenance shall be repaired promptly.
B. Device maintenance.
1. Maintenance of all erosion and sediment control measures shall be performed in
accordance with the VESCH
3.03 TEMPORARY MULCHING
A. Apply temporary mulch to areas where rough grading has been completed but final
grading is not anticipated to begin within 30 days of the completion of rough grading.
B. Straw mulch shall be applied at rate of 100 lbs./1000 ft.2 and tackified with latex acrylic
copolymer at a rate of 1 gal./1000 ft.2 diluted in a ratio of 30 parts water to 1 part latex
acrylic copolymer mix.
3.04 EROSION CONTROL MATTING
A. Erosion control matting shall be installed in all seeded drainage swales, ditches, and
slopes greater than 3 to 1 in accordance with manufacturer's instructions. The area to be
covered shall be properly prepared, fertilized, and seeded with permanent vegetation
before the blanket is applied. When the blanket is unrolled, the netting shall be on top
and the fibers in contact with the soil over the entire area. The blankets shall be applied
in the direction of water flow, and stapled. Blankets shall be placed a minimum of 3
rows (of 4 foot) wide (total approximately 12 foot width) within the drainage
swale/ditch and stapled together in accordance with manufacturer's instructions. Side
overlaps shall be a minimum of 4 inches. The staples shall be made of wire, .091 inch in
diameter or greater, U-shaped with legs 10 inches in length and a 1-1/2-inch crown.
Upper and lower ends of the matting shall be buried to a depth of 4 inches in a trench.
Erosion stops shall be created every 25 feet by making a fold in the fabric and carrying
the fold into a silt trench across the full width of the blanket. The bottom of the fold
shall be 4 inches below the ground surface. Staple on both sides of fold. Where the
matting must be cut or more than 1 roll length is required in the swale, turn down upper
end of downstream roll into a silt trench to a depth of 4 inches. Overlap lower end of
upstream roll 4 inches past edge of downstream roll, and staple.
To ensure full contact with soil surface, roll matting with a roller weighing 100 pounds
per foot of width perpendicular to flow direction after seeding, placing matting, and
N:\46601-014\Engineeringlesign\Contract_Documents\Specifications\02370_Erosion_and_Sediment_Control.doc 03/24/15
02370-4
North Fork Rivanna River Water Main Repair Erosion and Sediment Control
stapling. Thoroughly inspect channel after completion. Correct any areas where
matting does not present a smooth surface in full contact with the soil below.
3.05 REMOVAL AND FINAL CLEANUP
A. Once the site has been fully and permanently stabilized against erosion, remove sediment
control devices and all accumulated silt. Dispose of silt and waste materials in proper
manner. Re-grade all areas disturbed during this process and stabilize against erosion
with surfacing materials as specified herein.
END OF SECTION
N:k46601-014\Engineering\Design\Contract_Documents\SpecificationS02370_Emsion_and_Sediment_Control.doc 03/24/15
02370-5
North Fork Rivanna River Water Main Repair Ductile Iron Pipe and Fittings for Water
SECTION 02511
DUCTILE IRON PIPE AND FITTINGS FOR WATER
PART 1 - GENERAL
1.01 SCOPE OF WORK
A. Furnish all labor, materials, equipment, and incidentals required to install ductile iron
pipe and fittings complete as shown on the Drawings and as specified herein.
B. Installation of piping shall be in accordance with Section 02515, Water Piping
Installation.
C. Where the word "pipe" is used, it shall refer to pipe, fittings, or appurtenances unless
otherwise noted.
1.02 RELATED WORK
A. Section 02315, Excavation and Backfill.
B. Section 02316, Fill and Granular Fill Materials.
C. Section 02514, Water Piping Specialties.
D. Section 02515, Water Piping Installation.
E. Section 02516, Water Pipe Testing.
1.03 SUBMITTALS
A. Submit to the Owner shop drawings and product data required to establish compliance
with this Section.
B. Prior to shipment of pipe, submit a certified affidavit of compliance from the pipe
manufacturer stating that the pipe, fittings, gaskets, linings, and exterior coatings for this
project have been manufactured and tested in accordance AWWA and ASTM standards
and requirements specified herein.
1.04 REFERENCE STANDARDS
A. American Society for Testing and Materials(ASTM).
1. ASTM A377 - Standard Index for Specification for Ductile-Iron Pressure Pipe.
2. ASTM C150- Standard Specification for Portland Cement.
N:X46601-014\EngineerineDesign\Contract_Documents\Specifications\02511_Ductile_Iron_Pipe.doc 03/24/15
02511-1
411111111111111111111111
North Fork Rivanna River Water Main Repair Ductile Iron Pipe and Fittings for Water
3. ASTM A307 - Standard Specification for Carbon Steel Bolts and Studs 60,000 psi
Tensile Strength.
B. American National Standards Institute(ANSI).
1. ANSI B1.1 - Unified Inch Screw Threads(UN and UNR Thread Form).
2. ANSI B16.1 - Cast Iron Pipe Flanges and Flanged Fittings.
3. ANSI B18.2 - Square and Hex Bolts and Screws Inch Series Including Hex Cap
Screws and Lag Screws.
C. American Water Works Association(AWWA).
1. AWWA C104 - Cement-Mortar Lining for Ductile-lion Pipe and Fittings for
Water.
2. AWWA C110 - Ductile-Iron and Gray-Iron Fittings 3-In. through 48-In. (75MM
through 1200 mm) for Water and Other Liquids.
3. AWWA C111- Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings.
4. AWWA C150 - Thickness Design of Ductile-Iron Pipe.
5. AWWA C151 - Ductile-Iron Pipe, Centrifugally Cast for Water or Other Liquids.
D. Where reference is made to one of the above standards, the revision in effect at the time
of bid opening shall apply.
1.05 QUALITY ASSURANCE
A. All ductile iron pipe and fittings shall be from a single manufacturer, unless otherwise
approved by the Owner.
B. All ductile-iron pipe and fittings to be installed under this Contract shall be inspected and
tested at the foundry as required by the standard specifications to which the material is
manufactured. Furnish in duplicate to the Owner sworn certificates of such tests and
their results prior to the shipment of the pipe.
C. All pipe and fittings to be installed under this Contract may be inspected at the plant for
compliance with this Section by an independent testing laboratory selected by the Owner,
at the Owner's expense.
N:\46601-014\Engineering\Design\Contract_Documents\SPecificationsa02511_Ductile_Iron_Pipe.doc 03/24/15
02511-2
North Fork Rivanna River Water Main Repair Ductile Iron Pipe and Fittings for Water
D. Inspection of the pipe and fittings will also be made by the Owner after delivery. The
pipe shall be subject to rejection at any time on account of failure to meet any of the
specified requirements, even though sample pipes may have been accepted as satisfactory
at the place of manufacture. Pipe rejected after delivery shall be marked for
identification and shall be removed from the job.
E. All pipe and fittings shall be permanently marked with the following information:
1. Manufacturer, date.
2. Size, type, class, or wall thickness.
3. Standard produced to (AWWA, ASTM, etc.).
1.06 DELIVERY, STORAGE, AND HANDLING
A. Care shall be taken in loading, transporting and unloading to prevent injury to the pipe
or coatings. Under no circumstances shall the pipe be dropped or skidded against each
other. Slings, hooks, or pipe tongs shall be padded and used in such a manner as to
prevent damage to the exterior surface or internal lining of the pipe.
B. Materials, if stored, shall be kept safe from damage. The interior of all pipes, fittings,
and other appurtenances shall be kept free from dirt or foreign matter at all times.
C. Pipe shall not be stacked higher than the limits recommended by its manufacturer. The
bottom tier shall be kept off the ground on timbers, rails, or concrete. Stacking shall
conform to manufacturer's recommendations.
PART 2- PRODUCTS
2.01 GENERAL
A. Joints shall be as shown on the Drawings and as specified. If not shown or specified,
provide push-on or mechanical joints for buried pipe and flanged joints for above-grade
pipe.
B. Conform to AWWA C151 for material, pressure class, dimensions, tolerances, tests,
markings, and other requirements.
C. Use Special Thickness Class 52 for pipe 6 inches in diameter and larger, unless
otherwise shown or specified.
D. Ductile iron pipe and fittings shall have a cement mortar lining and asphaltic seal coat in
accordance with AWWA C104.
N:\46601-014\Engineering\Design\C ontract Documents\Specifications' 25I1_Ductile_Iron_Pipe.doc 03/24/15
02511-3
■r.r.
North Fork Rivanna River Water Main Repair Ductile Iron Pipe and Fittings for Water
E. Unless otherwise specified, ductile iron pipe and fittings shall receive a shop-applied
exterior asphaltic coating. Field repair of damaged pipe coating shall be allowed.
However, if, in the opinion of the Owner, the coating damage is beyond repair, the pipe
shall be replaced at the expense of the Contractor. Unless otherwise noted, field applied
coating material shall be compatible with or equal to the shop applied material.
2.02 MECHANICAL JOINT PIPE AND FITTINGS
A. Mechanical joint pipe.
1. Mechanical joint pipe shall conform to AWWA C151 with joint accessories
conforming to AWWA C111.
2. Glands shall be ductile iron.
3. Gaskets shall be plain-tipped rubber.
4. Assembly bolts and nuts shall be high-strength, low alloy steel.
B. Mechanical joint fittings.
1. Mechanical joint fittings shall conform to AWWA C110 with accessories conforming
to AWWA C111.
2. Pipe fittings shall be cast iron or ductile iron with a pressure rating of 350 psi.
3. Fitting glands shall be cast iron for cast iron fittings and ductile iron for ductile iron
fittings.
4. Gaskets shall be plain-tipped rubber.
5. Assembly bolts and nuts shall be high-strength, low alloy steel.
2.03 PUSH-ON JOINT PIPE AND FITTINGS
A. Push-on joint pipe.
1. Push-on joints shall conform to AWWA C151 and AWWA C111.
2. Gaskets shall be molded rubber.
3. Each plain end shall be painted with a circular stripe to provide a guide for visual
check that joint is properly assembled.
B. Fittings.
1. Push-on joint pipe shall be provided with mechanical joint fittings.
N:k16601-014\Engineering\Design\Contract_Documents\.Specifications'A2511_Ductile_Iron_Pipe.doc 03/24/15
02511-4
North Fork Rivanna River Water Main Repair Ductile Iron Pipe and Fittings for Water
2.04 RESTRAINED JOINT PIPE AND FITTINGS
A. Restrained joints shall be achieved by using mechanical joint pipe with mechanical joint
restraint or push-on restrained joint pipe.
B. Restrained pipe shall conform to applicable requirements of AWWA C151. Restrained
fittings shall conform to applicable requirements of AWWA C110 or AWWA C153.
C. Joints shall be suitable for 350 psi working pressure and be fabricated of heavy ductile
iron casting.
D. Bolts and nuts shall conform to ASTM A307, Grade B.
E. Restraining gaskets shall not be allowed.
F. Mechanical joint restraint shall be EBAA Iron, Inc., Megalug Series 1100, as specified in
the Owner's Approved Products List found in Appendix A.
G. Push-on restrained joint pipe shall provide flexible, restrained, push-on joints utilizing a
shop applied retainer weldment on the spigot end of the pipe and a ductile iron and
rubber ring locking mechanism, inserted after assembly of the bell. All push-on
restrained joint parts and mechanisms shall be provided by a single manufacturer for the
expressed purpose of providing restrained joints, and shall be compatible with the
system used. Field repair or modification of the push-on restraint system shall not be
allowed. Push-on restrained joint pipe shall be in accordance with the Owner's
Approved Products List found in Appendix A.
H. Push-on restrained joint pipe shall be provided with mechanical joint fittings restrained
with Mega-Lug Series 1100
PART 3 - EXECUTION
3.01 PIPE INSTALLATION
See Section 02515, Water Piping Installation.
3.02 PIPE TESTING
See Section 02516, Water Pipe Testing.
END OF SECTION
N:\46601-014\Engineering\Design\Contract_Documents\Specifications0025I 1_Ductile_Iron_Pipe.doc 03/24/15
02511-5
North Fork Rivanna River Water Main Repair Copper Pipe and Tubing
SECTION 02512
COPPER PIPE AND TUBING
PART 1 - GENERAL
1.01 SCOPE OF WORK
A. This Section specifies the basic materials and methods of installation for copper pipe and
tubing. Specific uses and applications are specified in other Sections and/or on the
Drawings.
B. All service line work shall be performed in accordance with the Albemarle County
Service Authority (ACSA) Construction Specifications and these Technical
Specifications. In case of conflict, the more stringent requirement shall apply.
1.02 RELATED WORK
A. Section 02315, Excavation and Backfill.
B. Section 02515, Water Piping Installation.
C. Section 02516, Water Pipe Testing.
1.03 SUBMITTALS
A. Submit to the Owner, shop drawings and product data required to establish compliance
with this Section.
1.04 REFERENCE STANDARDS
A. American Society for Testing and Materials(ASTM).
1. ASTM B42 - Standard Specification for Seamless Copper Pipe, Standard Sizes.
2. ASTM B62 - Standard Specification for Composition Bronze or Ounce Metal
Castings.
3. ASTM B75 - Standard Specification for Seamless Copper Tube.
4. ASTM B88 - Standard Specification for Seamless Copper Water Tube.
B. American Society of Mechanical Engineers (ASME).
1. ASME B16.26 - Cast Copper Alloy Fittings for Flared Copper Tubes.
N:46601-014\Engineering\Design\Contract_Documents\Specifications`02512_Copper_Pipe_and_Tubing.doc 03/24/15
02512-1
r
•
North Fork Rivanna River Water Main Repair Copper Pipe and Tubing
C. American National Standards Institute(ANSI).
1. ANSI/AWWA C800 -Underground Service Line Valves and Fittings.
PART 2 - PRODUCTS
2.01 TUBING AND PIPE
A. Soft copper tubing furnished for 1-inch through 2-inch diameters for water service
piping shall be Type K in accordance with ASTM B88 and ANSI/AWWA C800. B.
2.02 FITTINGS
A. Type CF-6, 125 lb., flared type copper unions, ASME B 16.26. Fitting shall conform to
AWWA C800, latest edition and shall contain no lead.
PART 3- EXECUTION
3.01 WATER SERVICE PIPING
A. Water service piping and fittings shall be installed in accordance with applicable
requirements of AWWA C600.
B. Copper tubing joints shall be square end cut with all fins and burrs removed. Tubing
shall be handled carefully, with all dented, gouged, or otherwise damaged tubing
replaced with undamaged tubing. Ends of the tubing and the inside of fittings and
couplings shall be cleaned with a wire brush and/or abrasive prior to joining.
C. The longest commercially available length of service line shall be used with no unions
(e.g., for 1-inch, only 1 union will be allowed for each 100-foot section). Unions shall
be made with flare-type couplings.
END OF SECTION
N:\46601-014\Engincering\DesignContract_Documents\Specifications`02512_Copper_Pipe_and_Tubing.doc 03/24/15
02512-2
North Fork Rivanna River Water Main Repair Valves,Hydrants and Appurtenances
SECTION 02513
VALVES, HYDRANTS,AND APPURTENANCES
PART 1 GENERAL
1.01 SCOPE OF WORK
A. Furnish all labor, materials, equipment, and incidentals required, and install complete and
ready for operation, all valves, hydrants and appurtenances as shown on the Drawings.
1.02 RELATED WORK
A. Section 02315, Excavation and Backfill.
B. Section 02511, Ductile Iron Pipe and Fittings for Water.
1.03 DESCRIPTION OF SYSTEMS
A. All of the equipment and materials specified herein are intended to be standard for use in
controlling the flow of water.
1.04 QUALIFICATIONS
A. All of the types of valves, hydrants and appurtenances shall be from manufacturers listed
on the Approved Products list found in Appendix A. The equipment shall be designed,
constructed, and installed in accordance with the best practices and methods and shall
comply with these Specifications as applicable.
1.05 SUBMITTALS
A. Copies of all materials required to establish compliance with these Specifications shall be
submitted. Submittals shall include at least the following:
1. Certified drawings showing all important details of construction and dimensions.
2. Descriptive literature, bulletins, and/or catalogs of the equipment.
3. The total weight of each item.
4. A complete bill of materials for each item.
\46601-014\EngineerineDesign�Contract_Documents\Specifications`02513_Valves_Hydrants.doc 03/24/15
02513-1
.rrrrrrrrr
North Fork Rivanna River Water Main Repair Valves,Hydrants and Appurtenances
1.06 OPERATING INSTRUCTIONS
A. Operating and maintenance instructions shall be furnished to the Owner. The
instructions shall be prepared specifically for this installation and shall include all required
cuts, drawings, equipment lists, descriptions, etc., that are required to instruct operating
and maintenance personnel unfamiliar with such equipment.
1.07 TOOLS
A. Special tools, if required for normal operation and maintenance, shall be supplied with
the equipment.
PART 2- PRODUCTS
2.01 GENERAL
A. All valves, hydrants and appurtenances shall be of the size shown on the Drawings and as
far as possible all items of the same type shall be from one manufacturer.
B. All valves, hydrants and appurtenances shall have the name of the manufacturer, flow
directional arrows, and the working pressure for which they are designed cast in raised
letters upon some appropriate part of the body.
C. All valves shall open left (counterclockwise).
D. Extension stems for valves shall be made from Type 304 stainless steel. Stem guides
shall be provided as necessary to support extension stems.
E. Interior coatings are to be NSF 61 approved for potable water use and lead free.
2.02 GATE VALVES
A. Resilient seated gate valves.
1. Four- through 24-inch resilient seated gate valves shall be in accordance with
AWWA C509 with a working pressure of 300 psi. The valve shall be iron wedge
and the valve seat fully encapsulated with molded rubber. Valves shall have
mechanical joint ends in accordance with ANSI/AWWA C111/A21.11, unless
otherwise specified or shown on the Drawings. Gate valves shall be one make and
shall open by a counterclockwise rotation of the valve stem with a two (2) inch
square operating nut. Operating nuts placed greater than seven (7) feet below
finished ground shall be equipped with approved operating nut extensions to meet
the minimum depth requirements. Gate valves installed in access vaults, pumping
stations, etc., shall be equipped with handwheels. The stuffing boxes shall be
equipped with 0-ring seals. Valves shall have iron bodies, and shall be fully bronze
N:k46601-014\Engineering\Design\Contract_Docwnents\Specifications`r02513_Valves_Hydrants.doc 03/24/15
02513-2
North Fork Rivanna River Water Main Repair Valves,Hydrants and Appurtenances
mounted. The interior and exterior coatings shall be NSF 61 approved for potable
water use. Gate valves shall have one "0" ring above and one "0" ring below the
stem thrust collar. The thrust collar shall be lubricated with NSF approved oil to
assure positive operation in opening and closing.
2. Gate valves shall be in accordance with the Owner's Approved Products List found
in Appendix A.
B. Cut-off valves.
1. Two inch and smaller gate valves shall be inside screw, solid bronze, tapered seat,
double disc construction and rated for 200 psi working pressure.
2. Two inch gate valves shall be provided with a 2 inch operating nut.
2.03 TAPPING SLEEVES AND TAPPING VALVES (TEMP. CONNECTION)
A. Tapping sleeves shall be of stainless steel, split-sleeve type designated for working
pressure not less than 200 psi. The seal of the tapping sleeve shall be mechanical joint or
low lead 2.5% or less and conforming to current regulations. Flanges shall be stainless
steel per AWWA C207 Class D with 150 lb. drilling and recessed for tapping valves per
MSS-SP60. Nuts and bolts shall be Type 304 stainless steel. Sleeves shall be as
manufactured by and in accordance with the Owner's Approved Products List found in
Appendix A.
B. Tapping valves shall conform to the requirements specified above for gate valves except
that one end shall be flanged and one mechanical. Tapping valves shall be provided with
an oversized opening to permit the use of full-sized cutters.
2.04 VALVE BOXES, EXTENSION SHAFTS, AND OPERATING NUTS
A. All buried valves shall be provided with extension shafts, operating nuts, and valve boxes
as follows:
1. Extension shafts shall be Type 304 stainless steel and the operating nut shall be 2
inches square. Shafts shall be designed to provide a factor of safety of not less than
4. Operating nuts shall be pinned to the shafts. Top of the operating nut shall be
located no greater than three(3) feet below finished grade.
2. Each valve on underground piping shall be provided with a 3-piece, screw-type
adjustable cast iron valve box. Valve boxes shall have a round shaft with 5 1/4
inside diameter, and a coat of bituminous paint applied to both surfaces. Covers
shall be cast iron with "WATER" integrally cast. Valve boxes shall be adjusted
flush with the finish grade.
N:\46601-014\Engineering\Design\ContTact_Documents\.Specifications`02513_Valves_Hydrants.doc 03/24/15
02513-3
.r .
North Fork Rivanna River Water Main Repair Valves,Hydrants and Appurtenances
Valve boxes shall be as manufactured by those listed in the Approved Products List
found in Appendix A. The base shall enclose the valve cover and operating nut of
the valve and shall be oval. Barrel length shall be adapted to the depth of cover.
In remote areas, valve boxes shall extend six (6) inches above finished grade and
have a witness post securely placed next to the box.
The witness post shall consist of a 4"x4"x60" concrete post (3,000 psi minimum
concrete) embedded 24" deep in the ground with a stamped bronze metal tag
permanently mounted on top which displays the type of valve and horizontal
distance to the valve.
2.05 SAMPLING STATION
A. Sampling station shall be a below-grade style installed in a valve box and provided with a
removable portable sampling rod and carrying case equal to Kupferle Foundry #92VB.
The bury depth of the sampling station shall be 3 feet with a '/ inch FIP inlet and all
brass waterway. All working parts shall be brass and be removable from above ground
for maintenance with no digging. Exterior pipe shall be brass. A drain hole in station
bottom shall be open and drain to a dry gravel pit. The sampling station shall be
provided with a removable protective PVC cap for connection to a quick coupling with
the removable portable sampling rod. The portable sampling rod shall be all brass.
Sampling station shall be provided with a '/4" copper water service, corporation stop
shut-off valve in a separate valve box and installed in accordance with the Standard
Detail.
PART 3- EXECUTION
3.01 BURIED VALVES INSTALLATION
A. Buried valves and boxes shall be installed in conformance with AWWA Standard C504,
as applicable, and as specified herein. Valves shall be set with the operating nut
vertically aligned in the center. Valves shall be set on a concrete foundation block and
supported by tamping select fill material at the sides of the valve.
B. Valve boxes shall be installed vertically, centered over the operating nut, and the
elevation of the top shall be adjusted to conform to the finished surface of roadway or
other surface at the completion of the contract. Boxes shall be adequately supported
during backfilling to maintain vertical alignment.
3.02 TAPPING VALVES AND SLEEVES
A. Tapping sleeves shall be installed per manufacturer's instructions.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications'02513_Valves_Hydrants.doc 03/24/15
02513-4
North Fork Rivanna River Water Main Repair Valves,Hydrants and Appurtenances
B. Installations shall be made under pressure and the flow of water through the existing
main shall be maintained at all times. The diameter of the tap shall be a minimum of 1/4-
inch less than the inside diameter of the branch line.
C. The entire operation shall be conducted by workmen thoroughly experienced in the
installation of tapping sleeves and valves.
D. The location and depth of the existing mains to be tapped shall be verified. Confirm that
the proposed position for the tapping sleeve will be satisfactory and no interference will
be encountered such as the occurrence of existing utilities or of a joint or fitting at the
location proposed for the connection. No tap shall be made closer than 5 feet from a
pipe joint unless otherwise approved by the Owner.
E. Tapping valves shall be supplied with a 2-inch square operating nut set in a vertical
position. The valve shall be provided with an oversized seat to permit the use of full-
sized cutters.
F. Tapping sleeves and valves shall be set squarely centered on the main to be tapped.
Adequate support shall be provided under the sleeve and valve during the tapping
operation. Thrust blocks shall be provided behind all tapping sleeves. Proper
compaction of supporting backfill around and under the valve and sleeve is mandatory.
3.03 INSPECTION AND TESTING
A. Valves and hydrants shall be tested in conjunction with testing of the water mains as
specified. Operation shall be satisfactory to the Owner in all respects.
B. During testing any defective valve or appurtenance shall be adjusted, removed, and
replaced, or otherwise made acceptable to the Owner.
C. Various regulating valves and other appurtenances shall be tested to demonstrate their
conformance with the specified operational capabilities and any deficiencies shall be
corrected, or the device replaced or otherwise made acceptable to the Owner.
END OF SECTION
N:\46601-014\Engineering\Design\Contract_Documents'Specificationsh02513_Valves_Hydrants.doc 03/24/15
02513-5
North Fork Rivanna River Water Main Repair Water Piping Specialties
SECTION 02514
WATER PIPING SPECIALTIES
PART 1 - GENERAL
1.01 SCOPE OF WORK
A. Furnish all labor, materials, equipment, and incidentals required to install, complete, and
ready for operation. Test all piping specialties concurrent with the pipe section within
which installed.
B. All service line work shall be performed in accordance with the Albemarle County
Service Authority (ACSA) Construction Specifications and these Technical
Specifications. In case of conflict, the more stringent requirement shall apply.
1.02 RELATED WORK
A. Piping materials and systems are included in other Sections of Division 02.
B. Section 02513, Valves, Hydrants, and Appurtenances.
C. Section 02515, Water Piping Installation.
D. Section 02516, Water Pipe Testing.
1.03 SUBMITTALS
A. Submit shop drawings and product data for all piping specialties specified in this
Section.
B. Submit operating and maintenance data as required.
1.04 REFERENCE STANDARDS
A. American Society for Testing and Materials(ASTM).
1. ASTM A126 — Standard Specification for Gray Iron Casting for Valves, Flanges
and Pipe Fittings.
2. ASTM A307 - Standard Specification for Carbon Steel Bolts and Studs, 60,000 psi
Tensile Strength.
N:\46601-014\Engineering\DesignContract_Documents\Specifications'02514_Water_Piping_Specialties.doc 03/24/15
02514-1
North Fork Rivanna River Water Main Repair Water Piping Specialties
3. ASTM A325 - Standard Specification for Strength Bolts, Steel, Heat Treated,
120/105 ksi Minimum Tensile Strength.
4. ASTM A536—Standard Specification for Ductile Iron Castings.
B. American National Standards Institute (ANSI).
1. ANSI B1.1 - Unified Inch Screw Threads(UN and UNR Thread Form).
2. ANSI B18.2 - Square and Hex Bolts and Screws Inch Series Including Hex Cap
Screws and Lag Screws.
C. American Society of Mechanical Engineers (ASME).
1. ASME B2.1 - Specifications, Dimensions, Gauging for Taper and Straight Pipe
Threads(except dry seals).
2. ASME B16.1 - Cast Iron Pipe Flanges and Flanged Fittings Class 25, 125, 250 and
800.
3. ASME B16.5 - Pipe Flanges and Flange Fittings.
D. American Welding Society(AWS).
1. AWS B3.0 - Welding Procedure and Performance Qualifications.
E. American Water Works Association(AWWA).
1. AWWA C110 - Ductile-Iron and Gray-Iron Fittings, 3-in. Through 48-in. (75mm
through 1200mm), for Water and Other Liquids.
2. AWWA C111 - Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings.
1.05 QUALITY ASSURANCE
A. All materials shall be new and unused.
B. Install piping to meet requirements of local codes.
C. Provide manufacturer's certification that materials meet or exceed minimum
requirements as specified.
\46601-014\Engineering\Design\Contract_Documents\Specifications`02514_Water_Piping_Specialties.doc 03/24/15
02514-2
North Fork Rivanna River Water Main Repair Water Piping Specialties
D. Coordinate dimensions and drilling of flanges with flanges for valves, pumps, and other
equipment to be installed in piping systems. Bolt holes in flanges to straddle vertical
centerline.
PART 2 - PRODUCTS
2.01 MATERIALS AND EQUIPMENT
A. The use of a manufacturer's name and/or model number is for the purpose of establishing
the standard of quality and general configuration desired.
B. Materials and products shall be of the sizes and types shown on the Drawings or as
noted herein. As far as possible, materials and products of the same type shall be
identical and shall be from one manufacturer.
C. Materials and products shall have the name of the manufacturer, nominal size, flow
directional arrows (if applicable), working pressure for which they are designed, and
standard referenced specifications cast in raised letters or indelibly marked upon some
appropriate part of the body.
D. Unless otherwise noted, piping specialties shall have a minimum working pressure of 300
psi or be of the same working pressure as the pipe they connect to, whichever is higher
and suitable for the pressures noted where they are installed.
2.02 UNIONS
A. Unions shall be brass or bronze unions for joining nonferrous pipe; malleable brass or
bronze-seated iron or steel unions for joining ferrous pipe.
2.03 DIELECTRIC CONNECTORS
A. Dielectric pipe fittings/insulators and unions shall be used to prevent galvanic action
wherever valves or piping of dissimilar metals connect. This shall be particularly the
case for copper, brass, and bronze piping connecting to cast iron or steel piping systems.
B. Dielectric unions shall be used for 2-inch and smaller connections. Steel union nuts shall
meet ASTM A575 requirements. The steel or ductile iron connection end shall have a
steel body and shall have accurately machined taper tapped pipe threads in accordance
with ASME B2.1. The copper connection end shall meet requirements of ASTM B88.
Dielectric unions shall be rated for at least 300 psi at 210 degrees F.
C. Dielectric flange unions shall be used for connections 2-1/2-inches and larger. Cast iron
flanges shall meet ASTM A126; the copper solder end shall meet ASTM B62 and the
N:46601-014\Engineering\Design Contract_Documents\Specifications`i2514_Water Piping_Specialties.doc 03/24/15
02514-3
orimmirmimerommeraw
North Fork Rivanna River Water Main Repair Water Piping Specialties
pipe thread shall meet ASME B2.1. Dielectric flange unions shall be rated for at least
175 psi at 210 degrees F.
D. Dielectric unions and flange unions shall be as manufactured by Epco Inc., Cleveland,
OH, or equal.
E. Flange insulating kits shall be as manufactured by PSI, or equal.
2.04 MISCELLANEOUS ADAPTERS
A. Special adapters may be required between different types of pipe and/or fittings to
provide proper connection. Some of these may be indicated on the Drawings or
specified with individual types of pipe or equipment. Provide all adapters as required,
whether specifically noted or not, to ensure proper connection between various types of
pipe, to structures and between pipe and valves, gates, fittings, and other appurtenances.
B. Adapters shall be suitable for direct burial when installed below grade, with proper
dielectric insulation. If metallic (not stainless steel or galvanized), adapters shall be
painted with two (2) coats of Coal Tar Epoxy.
2.05 FLEXIBLE CONNECTORS
A. Sleeve couplings.
1. Flexible couplings shall be of a gasketed, sleeve type. Each coupling shall consist of
a middle ring, two (2) followers, two (2) wedge section gaskets and sufficient track
head steel bolts to properly compress the gaskets. Couplings shall be of the type to
match piping in which installed. Couplings shall be in accordance with the
Approved Products List found in Appendix A.
2. Nuts and bolts.
a. Provide bolts and bolt-studs in accordance with ASTM A307 and ANSI B1.1
with hexagonal or square heads, coarse thread fit, threaded full length with ends
chamfered.
b. Project ends 1/4-inch beyond surface of nuts.
c. Hexagonal nuts with dimensions in accordance with ANSI B18.2 and coarse
threads in accordance with ANSI B1.1.
3. Middle ring of each mechanical coupling shall have a thickness at least equal to that
specified for size of pipe on which coupling is to be used and shall not be less than
NI:`46601-014`EngineerineDesignContract_Documents\Specifications`02514_Water_Piping_Specialties.doc 03/24/15
02514-4
North Fork Rivanna River Water Main Repair Water Piping Specialties
10 inches long for pipe 30 inches and larger and not less than 7 inches long for pipe
under 30 inches in diameter.
a. Omit pipe stop from inner surface of middle rings of couplings whenever
necessary to permit removal of valves, flow meters, and other installed
equipment.
b. Provide pipe stops in other couplings.
4. Clean and shop prime with manufacturer's standard rust inhibitive primer.
5. Furnish gaskets of a composition suitable for exposure to the fluid service.
6. Where shown on the Drawings, anchor sleeve-coupled joints with harness bolts.
a. Joint harness bolts shall be of sufficient length, with harness lugs placed so that
coupling can be slipped at least in one direction to clear joint. Provide
harnesses of sufficient number and strength to withstand test pressure.
b. Each harness shall have a minimum of 2 3/4-inch diameter bolts.
7. Similar insulation type couplings shall be provided at the face of buildings, between
different type metals or where otherwise noted.
2.06 SOLID SLEEVES
1. Solid Sleeves for connection to existing water mains shall be mechanical joint fittings
with mechanical joint restraint.
1. Mechanical joint fittings shall conform to AWWA C110 with accessories conforming
to AWWA C111.
2. Pipe fittings shall be cast iron or ductile iron with a pressure rating of 350 psi.
3. Fitting glands shall be cast iron for cast iron fittings and ductile iron for ductile
iron fittings.
4. Gaskets shall be plain-tipped rubber.
5. Assembly bolts and nuts shall be high-strength, low alloy steel.
2.07 METER ASSEMBLY
A. General
N:\46601-014EngineerinOesign\Contract_Documents\Specifications`02514_Water_Piping_Specialties.doc 03/24/15
02514-5
I �
North Fork Rivanna River Water Main Repair Water Piping Specialties
1. Following installation of the new meter setting the ACSA will provide a meter for
installation by the Contractor. Contractor shall coordinate with the ACSA to ensure
that the proper laying length for the meter is provided. The old meter shall be
returned to the ACSA. The old meter setting, box, and materials shall be removed
and properly disposed of by the Contractor, and the site restored.
B. 5/8" to 1" Service Meter Assembly
1. Service meters from 5/8" to 1" shall be installed in accordance with ACSA detail W-
6 Typical Service Lateral Installation. Meter boxes shall be in accordance with
ACSA detail W-7 Typical Meter Boxes (5/8"-1" Meters). Assembly parts and
products shall be in accordance with the Approved Products List found in Appendix
A. Meter box lids shall be provided with a 1-3/4" diameter touch read hole. Flared
fittings shall be used in meter assemblies. Brass fittings shall contain no lead.
2.08 SERVICE SADDLES
A. Service saddles for ductile iron pipe shall conform to the requirements of AWWA C800
with a working pressure of 200 psi. The saddle assembly shall be brass or bronze with a
single, full-width stainless steel strap and tapered AWWA threads.
B. Service saddles for 4- through 12-inch outlets where the outlet size is not greater than
1/2 the size of the main pipe shall have ductile iron bodies and a neoprene circular cross
section 0-ring gasket confined within the body. Outlet shall be AWWA C110 flange or
AWWA C111 mechanical joint as required for the application. Straps shall be alloy
steel, minimum 1/4-inch by 1-1/2-inch in cross section and fabricated with 3/4-inch
threaded ends.
C. Service saddles shall be as manufactured by and in accordance with the Owner's
Approved Products List found in Appendix A.
2.09 CORPORATION STOPS
A. Corporation stops and quarter-bend couplings for 3/4-inch through 2-inches diameter
water service lines shall be manufactured in accordance with AWWA C800. Inlet
threads shall be AWWA/CC taper threads. Quarter-bend coupling outlet shall be flared
copper connection. Brass fittings shall contain no lead. All corporation stops shall have
ball style valve and have a pressure rating of 300 psi.
B. Corporation stops shall be as manufactured by and in accordance with the Owner's
Approved Products List found in Appendix A.
N:\46601-014\Engineering\DesignContract_Documents\Specifications`+02514_Water_Piping_Specialties.doc 03/24/15
02514-6
North Fork Rivanna River Water Main Repair Water Piping Specialties
2.10 COPPERSETTERS
A. Coppersetters shall be manufactured in accordance with ANSI/AWWA C900 with a
minimum seven inch rise. The coppersetter shall have a lock-winged angle ball valve and
appropriate flared copper connection for joining copper service tubing on supply side.
Customer side shall have a plain angle ball valve with a multi-purpose connection. Brass
fittings shall contain no lead.
B. Coppersetters shall be as manufactured by and in accordance with the Owner's
Approved Products List found in Appendix A.
2.11 FLANGED ADAPTERS
A. Flanged adapter connections for plain end pipe at fittings, valves, and equipment shall be
Dresser Style 127 or 128, or equal by ITT/Smith-Blair.
PART 3-EXECUTION
3.01 GENERAL
A. All dirt, scale, weld splatter, water and other foreign matter shall be removed from the
inside and outside of all pipe and sub-assemblies prior to installing.
B. All pipe joints and connections to equipment shall be made in such a manner as to
produce a minimum of strain at the joint.
C. All connections to existing water mains shall be made with mechanical joint fittings and
mechanical restraining devices.
D. Install piping in a neat manner with lines straight and parallel or at right angles to walls
or column lines and with risers plumb. All work shall be accomplished using recognized
methods and procedures of pipe fabrication and in accordance with the latest revision of
applicable ANSI/AWWA Standards.
1. Use full length of pipe except where cut lengths are necessary. Do not spring or
deform piping to make up joints.
2. Pipe shall be cut square, not upset, underside, or out-of-round. Ends shall be
carefully beveled and cleaned before being installed. Bending of pipe is not
permitted. Use fittings for all changes in direction.
3. Reducers shall be eccentric to provide for drainage from all liquid-bearing lines and
facilitate air removal from water lines.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`132514_Water_Piping_Specialties.doc 03/24/15
02514-7
North Fork Rivanna River Water Main Repair Water Piping Specialties
4. Verify the locations and elevations of any existing piping and manholes before
proceeding with work on any system. Any discrepancies between the information
shown on the Drawings and the actual conditions found in the field shall be reported
at once to the Owner. If the above provision has not been complied with, no claim
for extra payment will be considered.
5. Where lines of lower service rating tie into services or equipment of higher service
rating the isolation valve between the two shall conform to the higher rating.
6. Mitering of pipe to form elbow is not permitted.
7. All piping interiors shall be thoroughly cleaned after installation and kept clean by
approved temporary closures on all openings until the system is put in service.
Open pipe ends shall be subjected to re-cleaning and re-testing.
8. End caps on pre-cleaned pipe shall not be removed until immediately before
assembly. All open ends shall be capped immediately after completion of
installation.
E. Installation of Sleeve Couplings
1. Prior to installation of sleeve couplings, the pipe ends shall be cleaned thoroughly
for a distance of at least 12 inches. Soapy water may be used as a gasket lubricant.
A follower and gasket, in that order, shall be slipped over each pipe to a distance of
about 6 inches from the end, the middle ring shall be placed on the already installed
pipe and shall be inserted into the middle ring flair and brought to proper position in
relation to the pipe already installed. The gaskets and followers shall then be
pressed evenly and firmly into the middle ring flares.
2. After the bolts have been inserted and all nuts have been made up finger tight,
diametrically opposite nuts shall be progressively and uniformly tightened all around
the joint, preferably by use of a torque wrench of the appropriate size and torque for
the bolts.
3. The correct torque as indicated by a torque wrench shall not exceed 75 ft.lbs. for
5/8-inch bolts and 90 ft.lbs. for 3/4-inch bolts.
4. If a wrench other than a torque wrench is used, it should be no longer than 12 inches
so that when used by the average person the above torque values shall not be
exceeded.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02514_Water_Piping_Specialties.doc 03/24/15
02514-8
North Fork Rivanna River Water Main Repair Water Piping Specialties
5. To prevent sleeve couplings from pulling apart under pressure, a suitable harnessing
or flange clamp assembly shall be provided and installed.
3.02 TESTING
A. Testing of pipelines, including valves, appurtenances, and piping specialties, is specified
in Section 02516 Water Pipe Testing. Furnish all labor, testing plugs or caps, pressure
pumps, pipe connections, gauges, and all other equipment required to complete the tests
as specified.
B. Repair faulty joints, remove defective pipe, valves, fittings, and specialties, and replace as
required. Retest.
END OF SECTION
N:\46601-014\Engineering\DesignC ontract_Documents\Specifications'02514_Water_Piping_Specialties.doc 03/24/15
02514-9
North Fork Rivanna River Water Main Repair Water Piping Installation
SECTION 02515
WATER PIPING INSTALLATION
PART 1 - GENERAL
1.01 SCOPE OF WORK
A. Contractor shall provide all labor, materials, equipment and incidentals as shown,
specified, and required to install and test all piping, fittings, and specialties. The Work
includes, but is not limited to, the following:
1. All types and sizes of piping except those specified under other Sections.
2. Supports, restraints, and thrust blocks.
3. Pipe encasements.
4. Work on or affecting existing piping.
5. Testing.
6. Cleaning.
7. Installation of all jointing and gasketing materials, specialties, flexible couplings,
mechanical couplings, harnessed and flanged adapters, sleeves, tie rods, and all other
Work required to complete the piping installation.
1.02 RELATED WORK
A. Section 02315, Excavation and Backfill.
Bs. Section 02511, Ductile Iron Pipe and Fittings for Water.
C. Section 03300, Cast-In-Place Concrete.
1.03 QUALITY ASSURANCE
A. All pipe to be installed under this Contract may be inspected at the place of manufacture
for compliance with the Specifications by an independent testing laboratory provided by
the Owner. The Contractor shall require the manufacturer's cooperation in these
inspections. The cost of inspection of all pipe approved for this Contract will be borne
by the Owner.
B. The Owner will inspect the pipe after delivery. The pipe shall be subject to rejection at
any time due to failure to meet any of the specified requirements herein, even though
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02515_Water_Piping_Installation.doc 03/24/15
02515-1
North Fork Rivanna River Water Main Repair Water Piping Installation
pipes may have been accepted as satisfactory at the place of manufacture. Pipe rejected
after delivery shall be marked for identification and shall be removed from the job.
C. Reference standards. Comply with applicable provisions and recommendations of the
latest edition of the following, except as otherwise shown or specified.
1. AWWA C600 - Installation of Ductile-Iron Water Mains and Their Appurtenances.
1.04 SUBMITTALS
A. Shop drawings. Submit for approval the following:
1. Full details of piping, specialties, joints, and connections to existing piping,
structures, equipment, and appurtenances.
B. Certificates. Submit certificates of compliance with referenced standards.
C. Record Documents. Submit Project Record Documents in accordance with these
specifications and prior to award of Substantial Completion.
1.05 PRODUCT DELIVERY, STORAGE, AND HANDLING
A. Handle all pipe, fittings, specialties, and accessories carefully with approved handling
devices in accordance with the manufacturer's recommendations and to the satisfaction
of the Owner. Do not drop or roll material off trucks. Do not otherwise drop, roll, or
skid piping.
B. Store pipes and fittings on heavy wood blocking or platforms so they are not in contact
with the ground. Pipe shall not be stacked higher than the limits recommended by the
manufacturer and shall conform to the manufacturer's recommendations. Pipe and
fittings strung out for installation within five (5) working days may be placed in contact
with the ground.
C. Unload pipe, fittings, and specialties opposite to or as close to the place where they are
to be installed as is practical to avoid unnecessary handling. Keep pipe interiors
completely free from dirt and foreign matter.
D. Inspect delivered pipe for cracks, gouges, chips, dents, or other damages and
immediately remove damaged pipe from site.
PART 2 -PRODUCTS
2.01 MATERIALS
A. Refer to applicable Pipe Sections for material specifications.
N:k16601-014\Engineering\Design\Contract_Documents'Specifications'02515_Water_Piping_Installation.doc 03/24/15
02515-2
North Fork Rivanna River Water Main Repair Water Piping Installation
B. Pipe marking.
1. Cast or paint material, type, and pressure designation on each piece of pipe or fitting
4 inches in diameter and larger.
2. Pipe and fittings smaller than 4 inches in diameter shall be clearly marked by
manufacturer as to material, type, and rating.
C. Trace wire. Tracer wire shall be AWG No. 10, single-conductor solid copper with 600-
volt insulation designed to meet U.S.E. requirements for buried service.
D. Warning tape. Warning tape shall have a minimum 5.0 mil overall thickness. The
warning tape, including labeling, shall not contain any dilutants, pigments, or other
contaminants, and shall resist degradation by elements encountered in the soil. The
warning tape for water service installations shall be color-coded blue and imprinted with
the words, "Caution-- Water Line Buried Below."
PART 3- EXECUTION
3.01 INSTALLATION
A. General.
1. Care shall be taken in loading, transporting, and unloading to prevent injury to the
pipe, linings, or coatings. Pipe or fittings shall not be dropped. All pipe and fittings
shall be examined before laying and no piece shall be installed which is found to be
defective. Any damage to the pipe linings or coatings shall be repaired as directed.
Handling and laying of pipe and fittings shall be in accordance with the
manufacturer's instructions and as specified herein.
2. If there is a conflict between manufacturer's recommendations and the Drawings or
Specifications, request instructions from the Owner before proceeding.
3. Prior to excavation, other utilities and underground facilities shall be located to
confirm location, proper depth, and clearances. Care shall be taken in excavating to
prevent damage to underground structures, utilities, and adjacent properties. When
approaching and crossing such installations, a combination of installation methods
may be used. Trenching equipment shall not be used within 2 feet of existing utilities
and within the distances from existing structures indicated on the plans.
4. All mains and services shall be installed true to the horizontal and vertical alignment
indicated on the Plans, or as otherwise directed by the Owner. The Contractor shall
make no deviations to the proposed horizontal and/or vertical alignment of the mains
or services unless otherwise directed to do so by the Owner. In such cases where
the proposed horizontal and/or vertical pipeline alignment will cause conflict with
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02515_Water_Piping_Installation.doc 03/24/15
02515-3
North Fork Rivanna River Water Main Repair Water Piping Installation
other utilities or structures, or result in less than the specified minimum clearance or
cover, the Owner shall be notified and the pipeline relocated as directed.
5. All pipe shall be sound and clean before laying. When laying is not in progress,
including lunchtime, the open ends of the pipe shall be closed by watertight plugs or
other approved means.
6. The trench shall be excavated to a depth required so as to provide a uniform and
continuous bearing and support for the pipe. Blocking will not be permitted except
where installation of concrete encasement follows. Trench bedding and backfill shall
be in accordance with the Detail Drawings.
7. Wherever it is necessary to deflect the pipe from a straight line, either in vertical or
horizontal plane, to avoid obstructions or to plumb the line for valve installation, or
where long-radius curves are permitted, the amount of deflection allowed shall not
exceed seventy-five (75) percent of the allowed deflection in AWWA C600 or
seventy-five (75) percent of the manufacturer's allowable deflection, whichever is
less. The following table shall be used as a guideline. In no case shall these limits be
exceeded.
Longitudinal Deflection of Push On Joint Ductile Iron Pipe
Nominal Deflection Maximum Offset Approx. Radius of Curve Produced by Succession of
Pipe Size Angle (inches) Joints(feet)
(inches)
L= 18 feet L=20 feet L= 18 feet L=20 feet
8 3.75 14 16 275 305
12 3.75 14 16 275 305
16 2.25 8 9 458 509
18 2.25 8 9 458 509
20 2.25 8 9 458 509
24 2.25 8 9 458 509
30 2.25 8 9 458 509
36 2.25 8 9 458 509
Longitudinal Deflection of Mechanical Joint Ductile Iron Pipe
Nominal Deflection Approx. Radius of Curve Produced by
Pipe Size Angle Maximum Offset(inches) Succession of Joints(feet)
(inches)
L= 18 feet L=20 feet L= 18 feet L= 20 feet
8 3.75 15 16.5 275 305
12 3.75 15 16.5 275 305
16 2.25 10 11 393 436
18 2.25 8 9 458 509
20 2.25 8 9 458 509
24 1.50 6.75 7.5 688 764
N:\46601-014\Engineering\Design'Contract_Documents\Specifications`02515_Water_Piping_Installation.doc 03/24/15
02515-4
North Fork Rivanna River Water Main Repair Water Piping Installation
8. Where pipe cutting is required, the cutting shall be done by abrasive saw, leaving a
smooth cut at right angles to the axis of the pipe. Any damage to the lining shall be
repaired to the satisfaction of the Owner. Field cuts shall only be made in pipe that
has been gauged full length. Field cut ends shall be in accordance with the
manufacturer's instructions.
9. Pipe and fittings shall be installed in accordance with the requirements of applicable
reference standards. Solid sleeves shall be used only where approved by the Owner.
10. Rights-of-way and easements.
a. The Contractor shall confine construction operations to the immediate vicinity of
the project location as shown on the Plans, and in no case shall the Contractor
encroach beyond the limits of the Owner's property, easements, or rights-of-
way. The Contractor shall further use due care in placing construction tools,
equipment, excavated materials, and pipeline facility materials and supplies to
cause the least possible damage to property and the least interference with
traffic. The placing of such tools, equipment, and materials shall be subject to
the approval of the Owner. Any damage resulting from the placement of
equipment and materials or construction operation occurring outside of
designated work areas shall be the sole responsibility of the Contractor. The
Contractor shall make satisfactory settlement for any damage directly with the
property owner involved.
b. The Contractor shall conduct the construction in such a manner to cause the
least inconvenience to the citizens of the area, thereby maintaining good public
relations. The Contractor shall not unnecessarily interfere with the use of any
public or private improvements, including landscaping; nor shall the Work
unnecessarily damage such improvements. The Contractor shall repair any
damage to such improvements to pre-construction condition, or as otherwise
directed by the Owner.
c. The Contractor shall use care in protecting existing property irons and
monuments adjacent to the working area. If a property iron or monument must
be removed to install new facilities, the Contractor shall retain the services of a
properly licensed and registered Land Surveyor to immediately replace it after
construction of the new facilities.
11. Work within VDOT rights-of-way.
a. Permits. The Owner will obtain and pay for all permits required to complete the
Work.
b. The Contractor shall comply with all provisions of all permits required by the
governing authorities at his own expense. The Contractor's responsibility under
this paragraph may include, but is not limited to, the following:
N:'46601-014\Engineering\DesignContract_Documents\Specifications`432515_Water_Piping_lnstailation.doc 03/24/15
02515-5
North Fork Rivanna River Water Main Repair Water Piping Installation
1) Constructing and removing temporary facilities or structures.
2) Providing details of construction methods.
3) Providing detailed construction schedules.
4) Reimbursing the applicable authority for all expenses incurred by them in
connection with the Work.
5) Traffic maintenance.
6) Coordination of scheduling with the authority.
7) Necessary clean up and restoration.
c. Maintenance of traffic.
1) The Contractor shall provide maintenance of traffic within the construction
area for the duration of the construction period, including during any
temporary suspension of Work. Maintenance of traffic shall conform to the
current editions of the Manual on Virginia Traffic Control Devices, Virginia
Work Area Protection Manual, Virginia Department of Transportation Road
and Bridge Specifications, and the Virginia Department of Transportation
Guidelines for Temporary Traffic Control. The Contractor shall provide a
traffic control plan to VDOT as required for obtaining the VDOT Land Use
Permit for all work.
2) The Owner may provide a detailed Traffic Maintenance Plan for portions of
the Work to be performed under this contract. If a Traffic Maintenance Plan
is provided, the Contractor is required to conform to this plan. The Owner
may require that the Contractor submit a Traffic Maintenance Plan prior to
commencing work on a particular portion of the project. If the Contractor is
asked to submit such a plan, work must not commence on the portion of the
project covered by the plan until approval of the Traffic Maintenance Plan by
the Owner.
3) The amount of roadway closure shall be approved by VDOT and the Owner
and be limited to the immediate work area and shall be in accordance with
the above-mentioned manuals and specifications.
d. Maintenance of ingress and egress. The Contractor shall strive to maintain, at all
times during the execution of the Work, continuous ingress and egress to all affected
parcels and traveled ways. When ingress and egress to affected parcels must be
blocked due to the direct execution of the Work, 24-hours advance notice must be
given to the affected property owner. In no case shall the blocking of ingress and
egress be allowed for more than 24 consecutive hours.
N:k16601-014\Engineering\Design\Contract_Documents\Specifications`02515_Water_Piping_Installation.doc 03/24/15
02515-6
North Fork Rivanna River Water Main Repair Water Piping Installation
e. Construction within VDOT rights-of-way shall be subject to the approval and
issuance of a Land Use Permit by VDOT. The Owner will obtain the VDOT Land
Use Permit. Contractor shall at all times conduct his work and operations in
accordance with the issued Permit and the Virginia Department of Transportation
Road and Bridge Specifications. If required by VDOT, the Contractor shall submit
for approval specific details of construction methods proposed for Work within
VDOT rights-of-way.
B. Above-grade pipe installation.
1. All above-grade pipe shall be flanged unless otherwise shown or specified.
2. Flanged joints shall be made using gaskets, bolts, bolt studs with a nut on each end,
or studs with nuts where the flange is tapped. The number and size of bolts shall
conform to the same ANSI standard as the flanges.
3. Bolts in flanged joints shall be tightened alternately and evenly as per manufacturer's
recommendations.
4. Sleeve-type couplings shall be installed in accordance with the procedures
recommended by the manufacturer.
5. All pipe and appurtenances connected to equipment shall be supported in such a
manner as to prevent any strain being imposed on the equipment. When
manufacturers have indicated requirements that piping loads shall not be transmitted
to their equipment, submit a certification stating that such requirements have been
complied with.
6. Sleeves of proper size shall be installed for all pipes passing through floors or walls.
Where indicated on the Drawings or required for liquid or gas-tightness, the sleeve
shall be sealed with a mechanical seal similar to Link-Seal, as manufactured by
Thunderline Corporation, or approved equal.
7. Concrete inserts for hangers and supports shall be furnished and installed as
recommended by the manufacturer, as shown on the Drawings, or as specified
herein. The inserts shall be set in accordance with the requirements of the piping
layout and their locations verified from approved piping layout drawings and the
structural drawings.
C. Buried piping installation.
1. Separation of water mains and sewers.
a. Parallel installations.
N:k16601-014\Engineering\Design\Contract_Documents\Specifications'02515_Water_Piping_Installation.doc 03/24/15
02515-7
North Fork Rivanna River Water Main Repair Water Piping Installation
I) Under normal conditions water mains shall be laid at least 10 feet
horizontally from a sewer or sewer manhole. The distance shall be measured
edge-to-edge.
2) Under unusual conditions when local conditions prevent a horizontal
separation of 10 feet, the water main may be laid closer to a sewer or sewer
manhole provided that:
a) The bottom(invert) of the water main shall be at least 18 inches above the
top (crown) of the sewer;
b) Where this vertical separation cannot be obtained, the sewer shall be
constructed of AWWA approved water pipe, pressure tested in place without
leakage prior to backfilling; and
c)The sewer manhole shall be of watertight construction and tested in place.
b. Crossing Installation
1) Under normal conditions water mains crossing sewers shall be laid to provide
a separation of at least 18 inches between the bottom of the water main and
the top of the sewer whenever possible.
2) Under unusual conditions when local conditions prevent a vertical separation
described above, the following construction shall be used:
a) Sewers passing over or under water mains shall be constructed of AWWA
approved ductile iron water pipe, pressure tested in place without leakage
prior to backfilling
b) Water mains passing under sewers shall, in addition, be protected by
providing:
(1) A vertical separation of at least 18 inches between the bottom of the
sewer and the top of the water main;
(2) Adequate structural support for the sewers to prevent excessive
deflection of the joints and the settling on and breaking of the water
main; and
(3) That the length of the water main be centered at the point of the
crossing so that joints shall be equidistant and as far as possible from
the sewer.
c. No water pipes shall pass through or come in contact with any part of a sewer
manhole.
2. Separation of potable water mains and other utilities.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02515_Water_Piping_Installation.doc 03/24/15
02515-8
North Fork Rivanna River Water Main Repair Water Piping Installation
a. Potable water mains shall have a minimum parallel separation of five (5) feet
from gas lines where practical. In special cases this may be dropped to three (3)
feet with approval of the gas company. All other utilities shall have a minimum
edge-to-edge separation of twelve(12) inches.
b. At all crossings, provide a minimum vertical separation of twelve (12) inches
between potable water mains and gas mains or "dry"utilities.
3. Pipe bedding.
a. Bed pipe as specified below and in accordance with the Drawings.
b. Trench excavation, backfill, and bedding materials shall conform to the
requirements of Section 02315 Excavation and Backfill, and Section 02316 Fill
and Granular Fill Materials and the Standard Detail Drawings.
c. Excavate trenches below the pipe bottom by the amount specified. Remove all
loose and unsuitable material from the trench bottom.
d. Carefully and thoroughly compact all pipe bedding with hand-held compactors.
e. No pipe shall be brought into position until the preceding length has been bedded
and secured in its final position.
4. Laying pipe.
a. Conform to manufacturer's instructions and requirements of the reference
standards where applicable.
b. Install all pipe accurately to line and grade shown on the Drawings unless
otherwise approved by the Owner. Remove and re-lay pipes that are not laid
correctly.
c. Slope piping uniformly between elevations shown.
d. Ensure that ground water level in trench is at least six (6) inches below bottom
of pipe before laying piping. Do not lay pipe in water. Maintain dry trench
conditions until jointing and backfilling are complete. Protect and keep pipe
interiors and fittings clean.
e. Start laying pipe at lowest point and proceed towards the higher elevations,
unless otherwise approved by the Owner.
f. Place bell and spigot pipe so that bells face the direction of laying, unless
otherwise approved by the Owner.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02515_Water_Piping_Installation.doc 03/24/15
02515-9
e..
North Fork Rivanna River Water Main Repair Water Piping Installation
g. Field cut pipe, where required, with a machine specially designed for cutting
piping. Make cuts carefully, without damage to pipe or lining, and with a
smooth end at right angles to the axis of pipe. Cut ends on push-on joint shall be
tapered and sharp edges filed off smooth. Flame cutting will not be allowed.
h. Inspect interior of all pipe and fittings and completely clean all dirt, gravel,
debris, or other foreign material from pipe interior and joint recesses before it is
moved into the trench. Bell and spigot mating surfaces shall be thoroughly wire
brushed and wiped clean and dry immediately before the pipe is laid.
i. Carefully examine all pipe, fittings, and specials for cracks, damage, or other
defects while suspended above the trench before installation. Immediately
remove defective materials from site.
j. Excavate around joints in bedding and lay pipe so that the barrel bears uniformly
on the bedding material.
k. Touch up protective coatings in a satisfactory manner prior to backfilling.
1. On steep slopes, take measures to prevent movement of the pipe during
installation.
5. Below grade water crossing
a. Pipes to be installed underneath a bed of stream or body of water shall be
performed with open cut pipeline installation using cofferdams. Pipe shall be
encased in concrete the entire width of the stream bank and in accordance with
the Standard Details and as shown on the plans.
b. Exercise care to avoid flotation of pipe when placing concrete around pipe
during concrete encasement.
6. Jointing pipe.
a. Ductile iron mechanical joint pipe.
1) Wipe the socket, plain end, and adjacent areas clean immediately before
making joint. Make certain that cut ends are tapered and sharp edges are
filed off smooth.
2) Place the gland on the plain end with the lip extension toward the plain end.
3) Lubricate the plain end and gasket with soapy water or an approved pipe
lubricant in accordance with AWWA C111, and slip the gasket onto the plain
end of the joint assembly with the narrow edge of the gasket toward the plain
end.
N:\46601-014\Engineering\DesignContract_Documents\Specifications`02515_Water_Piping_Installation.doc 03/24/15
02515-10
North Fork Rivanna River Water Main Repair Water Piping Installation
4) Insert the pipe into the socket and press the gasket firmly and evenly into the
gasket recess. Keep the joint straight during assembly.
5) Push gland toward socket and center it around pipe with the gland lip against
the gasket.
6) Insert bolts and hand-tighten nuts.
7) Make deflection after joint assembly, if required, but prior to tightening bolts.
Alternately tighten bolts 180 degrees apart to seat the gasket evenly. The
bolt torque shall be in accordance with the manufacturer's recommendations.
b. Ductile iron push-on joint pipe.
1) Prior to assembling the joints, the last 8 inches of the exterior surface of the
spigot and the interior surface of the bell shall be thoroughly cleaned with a
wire brush, except where joints are lined or coated with a special protective
lining or coating.
2) Rubber gaskets shall be wiped clean and flexed until resilient. Refer to
manufacturer's instructions for procedures to ensure gasket resiliency when
assembling joints in cold weather.
3) Insert gasket into joint recess and smooth out the entire circumference of the
gasket to remove bulges and to prevent interference with the proper entry of
the spigot of the entering pipe.
4) Immediately prior to joint assembly, apply a thin film of approved lubricant
to the surface of the gasket that will come in contact with the entering spigot
end of pipe. Contractor may, at his option, apply a thin film of lubricant to
the outside of the spigot of the entering pipe.
5) For assembly, center spigot in the pipe bell and push pipe forward until it just
makes contact with the rubber gasket. After gasket is compressed and
before pipe is pushed or pulled all the way home, carefully check the gasket
for proper position around the full circumference of the joint. Final assembly
shall be made by forcing the spigot end of the entering pipe past the rubber
gasket until it makes contact with the base of the bell. When more than a
reasonable amount of force is required to assemble the joint, the spigot end
of the pipe shall be removed to verify the proper positioning of the rubber
gasket. Gaskets that have been damaged shall not be reused.
6) Maintain an adequate supply of gaskets and joint lubricant at the site at all
times when pipe jointing operations are in progress.
N:\46601-014\Engineering\DesignContract_Documents\Specifications`A2515_Water_Piping_Installation.doc 03/24/15
02515-11
North Fork Rivanna River Water Main Repair Water Piping Installation
c. Proprietary joints. Pipes that use proprietary joints shall be installed in strict
accordance with the manufacturer's instructions.
7. Trace wire shall be installed with all water mains and appurtenances. The trace wire
shall be ten (10) gauge minimum (American Wire Gauge) solid copper with
thermoplastic insulation recommended for direct burial. The wire shall be secured to
the buried pipe and shall extend continuously and unbroken, from point of access to
point of access. The ends of the wire shall terminate with a minimum of six(6) feet
of wire, coiled, remaining available at all access points.
Contractor shall perform a continuity test on all tracer wire in the presence of the
Owner. If the tracer wire is found to be not continuous after testing, Contractor
shall repair or replace the failed wire.
8. All buried pipe fittings shall be ductile iron, restrained joint type.
a. All ductile iron pipe to be cut for insertion into fittings shall be gauged full
length.
9. Plugs.
a. Install AWWA specified mechanical joint type plugs into all bells at dead ends,
tees, or crosses and cap all spigot ends where shown on the Drawings.
b. Fully secure and block all plugs and caps installed for pressure testing to
withstand the specified test pressure.
c. Where plugging is required for phasing of the Work or for subsequent
connection of piping, install AWWA specified mechanical joint type plugs.
10. Thrust restraint.
a. All tees, valves, fittings, plugs, bends, and caps shall be restrained to prevent any
movement. For new water main installations, restraint shall be achieved by using
joint restraint in the form of mechanical joint restraint or restrained joint pipe.
Restrained lengths of pipe shall be in accordance with the manufacturer's
recommendations.
b. A concrete thrust block shall be placed at all connections to existing water
mains.
11. Backfilling.
a. Conform to the applicable requirements of Section 02315, Excavation and
Backfill and applicable Detail Drawings.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02515_Water_Piping_Installation.doc 03/24/15
02515-12
North Fork Rivanna River Water Main Repair Water Piping Installation
b. Place backfill as construction progresses. Backfill by hand and use power
tampers until pipe is covered by at least 1 foot of fill.
D. Water service taps.
1. General.
a. Individual water services and multiple branch services shall be provided from the
main to each water meter in accordance with the Drawings. Such laterals shall
be Type K soft copper tubing for all services 2 inches and less, installed at a
minimum depth of 36 inches from the main line to a meter setting below finished
grade. Contractor shall notify the ACSA 48 hours in advance of water service
taps so that an ACSA Inspector may be present to observe the tap.
b. All connections shall be made by wet taps unless approved otherwise. Service
connections shall be made perpendicular to the main and shall run straight to the
meter.
c. All water meter boxes and vaults shall be located a minimum of 12 inches and a
maximum of 36 inches directly behind the curb or as directed by the Owner.
Where no curb exists, meter boxes and vaults shall be installed in readily
accessible locations beyond the limits of street surfacing, walks, and driveways
as directed by the Owner. Water meter boxes and vaults shall not be placed in
streets, parking areas, or obstructed by fencing or buildings. Exceptions to these
conditions will be at the direction of the Owner.
d. Warning tape and 10-gauge tracer wire shall be installed with each service
lateral. Warning tape shall be installed 12 inches above service piping and shall
be continuous over the length of the service lateral. Tracer wire shall be installed
with the service piping and shall terminate in a loop within the meter box or
vault.
2. The Contractor shall make service taps to new water mains after the mains have
been successfully tested and disinfected in accordance with the Specifications.
3. Taps in ductile iron water mains.
a. The maximum size of direct taps without a fitting, tapping sleeve, or saddle for
ductile iron water mains shall be as follows:
4" Main 3/4"Tap
6"Main 1"Tap
8"Main 1-1/4"Tap
10"— 16"Main 1-1/2"Tap
b. Tapping sleeves and valves shall be used on all 4-inch and larger taps.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications\02515_Water_Piping_Installation.doc 03/24/15
02515-13
North Fork Rivanna River Water Main Repair Water Piping Installation
c. The maximum size saddle outlet shall be limited to 1/2 the water main diameter
with a maximum outlet diameter of 3 inches.
d. Tapping saddles may be used on exposed ductile iron mains at the discretion of
the Owner. Maximum saddle outlet size shall be limited to 1/2 the water main
diameter with a maximum diameter of 12 inches.
e. Service taps shall be a minimum of 24 inches apart and located at the 10 or 2
o'clock position on the main. No burned taps will be allowed. No taps are
allowed on a fire hydrant line. No tapping shall be made where rodding is
placed.
f. Corporation stops threaded into iron pipes, fittings, or specials shall have their
threads wrapped in Teflon tape or approved equal prior to assembly.
g. Service taps for ductile iron mains encased in polyethylene shall be performed in
accordance with AWWA C105 and AWWA C600. Polyethylene tape shall be
used to protect the polyethylene sheet or repair any cuts or abrasions as a result
of direct or saddle taps.
4. Where a service lateral must cross a sanitary sewer, the bottom of the service lateral
within 10 feet of the point of crossing shall be at least 12 inches above the top of the
sewer.
E. Water Main Taps
1. Preparation
a. The minimum distance that a tap shall be offset from a joint in the main is either
four (4) feet or two (2) times the diameter of the main being tapped, whichever
is greater. The Contractor shall expose the main in either direction of the tap to
ensure that this requirement is met.
b. The Contractor shall schedule a test pit prior to ordering the tapping sleeve to
verify the horizontal and vertical location, the outside diameter and the pipe
material of the waterline prior to. The Owner shall be notifies three business
days in advance of the test pit.
c. The tapping sleeve shall be approved by the Owner prior to being ordered and
the tapping contractor must be approved by Owner prior to the tap.
d. Tapping procedures shall be in accordance with the manufacturer's published
recommendations.
2. Pressure Test of Tapping Sleeve and Valve
a. Prior to starting the tap, the tapping sleeve and valve shall be subjected to a
pressure test to confirm that they do not leak. The standard test shall be a
hydrostatic pressure test with a test pressure of two hundred (200) psi or one
NM6601-014\Engineering\Design\Contract_Documents'.Specifications`02515_Water_Piping_Installation.doc 03/24/15
02515-14
North Fork Rivanna River Water Main Repair Water Piping Installation
and one half(1.5) times the anticipated working pressure of the line, whichever
is greater for a duration of thirty (30) minutes. No pressure drop is allowed in
the test.
b. If the contractor is approved by the Owner to conduct pneumatic testing and if
the manufacturer of the tapping sleeve recommends pneumatic testing of the
tapping sleeve then the contractor may conduct a pneumatic air test at thirty-five
(35) psi for a duration of five (5) minutes in lieu of the hydrostatic test. No
pressure drop is allowed in the test.
F. Transitions from one type of pipe to another.
1. Provide all necessary adapters, specials, and connection pieces required when
connecting different types and sizes of pipe or connecting pipe made by different
manufacturers.
G. Closures.
1. Provide all adapters, sleeves, specials, or other closure pieces shown on the
Drawings or required to complete the Work.
3.02 WORK AFFECTING EXISTING PIPING
A. Location of existing piping.
1. Locations of existing piping shown on the Drawings should be considered approximate.
2. Contractor shall determine the true location of existing piping to which connections are
to be made, and location of other facilities which could be disturbed during earthwork
operations, or which may be affected by Contractor's Work in any way.
B. Repair of water mains.
1. Joint leaks of cast iron pipe and ductile iron pipe shall be repaired by using a bell joint
leak repair clamp as specified.
2. Main breaks or punctures shall be repaired with a full circle repair clamp as specified.
3. Main splits or blowouts shall be repaired by replacing the damaged section with like pipe
material with pipe couplings at each end. (Damaged cast iron sections shall be replaced
with ductile iron pipe.)
4. For old cast iron pipe to ductile iron pipe, use a pipe coupling with different end
diameters sized specifically for the pipe material and pipe outside diameter at each end.
5. Disinfect materials used to facilitate water main repairs in accordance with Section
02516 Water Pipe Testing.
N:W6601-014\Engineering\Design\Contract_Documents\Specifications`\02515_Water Piping_Installation.doc 03/24/15
02515-15
r
•
North Fork Rivanna River Water Main Repair Water Piping Installation
C. Water service line repairs.
1. A water service line severed between the water main and the water meter shall be
repaired using new Type K copper tubing and brass flared joint fittings.
2. A corporation stop pulled out of a ductile iron pipe shall have a full circle repair clamp
placed over the old tap hole. A new tap shall be made and a new corporation stop
installed on the water main.
3.03 TESTING OF PIPING
A. Test in accordance with Section 02516 Water Pipe Testing.
END OF SECTION
N:\46601-014\Engineering\Design\Contract_Documents'.Specifications'02515_Water_Piping_Installation.doc 03/24/15
02515-16
North Fork Rivanna River Water Main Repair Water Pipe Testing
SECTION 02516
WATER PIPE TESTING
PART 1 - GENERAL
1.01 SCOPE OF WORK
A. This Section specifies the general requirements for disinfecting and testing the piping
systems shown on the Drawings and specified elsewhere in these Specifications.
1.02 RELATED WORK
A. Piping materials and systems are included in other Sections of Division 02.
B. Section 02513, Valves, Hydrants, and Appurtenances.
C. Section 02515, Water Piping Installation.
1.03 SUBMITTALS
A. Submit detailed description of filling and testing procedures including, but not limited to,
the following:
1. Schedule of test sections and piezometric test elevations in accordance with the
requirements of this Section.
2. Type and location of bulkheads; provisions for thrust restraint.
3. Proposed sources of water and points of introduction into the pipeline.
4. Proposed equipment and methods for admitting test water and filling and dewatering
the pipeline.
5. Proposed sequence of activities.
6. Proposed methods and details for testing pipe, joints, closures, etc., installed after
completion of hydrostatic tests.
B. Test records.
1. Maintain records of all tests performed.
2. Test records shall include:
N:\46601-014\Engineering\Design\Contract_Documents\.Specifications\025 t 6_Water_Pipe_Testing.doc 03/24/15
02516-1
A.
North Fork Rivanna River Water Main Repair Water Pipe Testing
a. Date of testing.
b. Identification of piping tested.
c. Test fluid.
d. Test pressure.
e. Signature of contractor.
3. If leaks are found, they shall be noted on the record, and then repaired. After repair,
retest as specified for original test.
4. Submit test records to Owner within 24 hours of testing.
1.04 GENERAL REQUIREMENTS
A. General.
1. Test all piping except as otherwise authorized by the Owner.
2. All testing will be performed in accordance with ANSI/AWWA C600 and C651.
The Contractor shall notify the Owner 48 hours in advance of testing.
3. Provide all testing apparatus, including pumps, hoses, gauges, and fittings.
4. Unless otherwise noted, pipelines shall hold specified test pressure for two (2)hours.
5. Repair and retest pipelines that fail to hold specified test pressure or which exceed
the allowable leakage rate.
6. Unless otherwise specified, test pressures required are at the highest elevation of the
pipeline section being tested.
7. Conduct all tests in the presence of the Owner's representative.
1.05 TEST PRESSURE
A. Hydrostatic test. Test pressure shall be 300 psi unless otherwise specified.
N:46601-0141Engineering\Design\Contract_Documents\Specifications\02516_Water_Pipe_Testing.doc 03/24/15
02516-2
North Fork Rivanna River Water Main Repair Water Pipe Testing
PART 2 - PRODUCTS
2.01 TEST FLUIDS
A. Hydrostatic test. Potable water shall be used as the test fluid for all potable water line
testing.
2.02 TEST EQUIPMENT
A. Hydrostatic test. Testing shall be performed in accordance with AWWA C600
1. Water: Of sufficient capacity to deliver the required test pressure.
2. Strainer: On inlet side of the pump to prevent foreign matter from entering the
system.
3. Valves: Shall be provided on the suction and discharge side of the pump.
4. Heater: To allow heating of the test fluid when elevated temperatures are required
for test.
5. Relief valve: Set at a pressure to relieve at 20 to 25 percent above the required test
pressure.
6. Pressure gauge(s): Capable of reaching 50 percent over the test pressure. These
should be located at the pump discharge and any other place deemed convenient by
the Contractor.
7. Pressure gauges and relief valves shall be checked for accuracy before use in test
procedures.
PART 3-EXECUTION
3.01 SAFETY
A. All tests shall be performed under the direct supervision of the Contractor and in the
presence of a representative of the Owner.
B. Restrict personnel in the test area to those involved in the test.
C. Safety glasses must be worn throughout testing.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications002516_Water_Pipe_Testing.doc 03/24/15
02516-3
North Fork Rivanna River Water Main Repair Water Pipe Testing
3.02 HYDROSTATIC TEST
A. Hydrostatic testing shall be performed in accordance with AWWA C600. This test
specification shall be used to hydrostatically test piping systems for structural integrity
and leaks. The test shall be performed at ambient temperature unless otherwise
specified.
B. Hydrostatic pressure test.
1. All newly installed water mains or any valved section thereof shall be hydrostatically
tested. Backfilling and compaction shall be completed before testing unless
otherwise required or approved by the Owner.
2. The water mains shall be tested for leakage by the Contractor at his own expense in
the presence of the Owner. All tests shall be conducted in a manner to minimize as
much as possible any interference with the Contractor's Work or progress. A
maximum of 2,500 linear feet of water main may be tested at one time, unless
otherwise approved by the Owner.
3. No permanent connections shall be made to the potable water system to fill or
pressurize the waterline being tested. If a temporary connection is made to the
potable water system in order to fill the line being tested, then the potable water shall
flow through an RWSA approved backflow prevention device prior to entering the
line being tested. This temporary connection must be terminated before the
pressurization of test line begins.
4. Each section of water main between adjacent valves shall be tested separately. The
maximum differential pressure across any valve during testing shall not exceed the
test pressure recommended by the valve manufacturer, or as specified by the Owner.
The Contractor shall provide all temporary bulkheads and thrust restraint to isolate
the water main test section, and shall provide all long solid sleeves necessary to
make the permanent connection to the system at no additional cost.
5. The Contractor shall notify the Owner when the Work is ready for testing and tests
shall be made as soon thereafter as practicable under the direction of the Owner.
Personnel for reading meters, gauges or other measuring devices will be furnished by
the Owner, but all other labor, equipment and materials shall be furnished by the
Contractor, unless otherwise specified.
6. Testing of the pipelines shall not be made until at least 7 days have elapsed after all
concrete thrust blocking has been installed.
7. The Owner reserves the right to check the completed pipeline for vertical alignment
prior to filling with water and testing. The Contractor shall not allow water in any
pipelines without the express written permission of the Owner
N:4601-014\Engineering\Design\Contract_Documents\Specifications`02516_Water_Pipe_Testing.doc 03/24/15
02516-4
North Fork Rivanna River Water Main Repair Water Pipe Testing
8. All air valves shall be installed as indicated on the Drawings and individually checked
for proper operation prior to filling the water main for testing. If for any reason it is
necessary to drain the water main, the Contractor shall take all precautions required
to ensure the safety of personnel entering and inspecting the water main. When
draining the water main, all air valves shall be rechecked for proper operation. This
is required to avoid the formation of a vacuum lock which could prevent the water
from properly draining and become a hazard to men working within the pipeline if
released. Pipelines containing large orifice valves shall be filled at a maximum rate
of one foot per second.
9. Each valved section of pipe shall be slowly filled with potable water expelling all air.
If necessary, Contractor shall install corporation stops to assist in air removal.
Backflow prevention device acceptable to the Owner shall be used whenever non-
disinfected pipelines are being filled from a potable water source or main.
10. Specified test pressure shall be applied by means of a pump connected to the pipe in
a manner satisfactory to the Owner. The water and container used in pressurizing
the main to be tested shall be properly disinfected in accordance with AWWA C651.
11. All exposed pipe, fittings, and appurtenances shall be examined after pressurization
of pipeline. Any visible leaks shall be repaired.
12. The section of pipeline under test will be considered to have successfully completed
this test if applied pressure does not vary by more than five (5) psi during the two-
hour test duration.
C. Leakage test.
1. All newly installed water mains or any valved portion thereof shall be subjected to a
leakage test conducted concurrently with the hydrostatic pressure test. A maximum
of 2,500 feet of water main shall be tested at one time, unless otherwise approved by
the Owner.
2. Leakage shall be defined as the quantity of water that must be supplied to a newly
installed pipeline, or valved section thereof to maintain pressure within five (5) psi
of the test pressure specified.
N:\46601-014\Engineering\DesignContract_Documents\Specifications`02516_Water_Pipe_Testing.doc 03/24/15
02516-5
rn■rror.
North Fork Rivanna River Water Main Repair Water Pipe Testing
3. Allowable leakage in gallons per hour for ductile iron pipe shall be determined by the
most recent AWWA Standard C-600. D. Current formula is as follows:
L= SDP112
148,000
L=Allowable leakage(gal./hr.)
S =Length of pipe being tested(ft.)
D=Nominal pipe diameter(in.)
P =Average test pressure(lbs./in.2)
4. All hydrants, air relief valves, meters, or other appurtenances within the test section
shall be valved-off during testing to prevent possible damage.
5. If any test of installed pipe discloses leakage greater than that allowed, the
Contractor shall, at his own expense, determine the sources of leaks and remedy all
deficiencies as necessary. The installed pipe shall be retested in accordance with the
test procedures above until leakage is within acceptable limits.
3.03 DISINFECTION OF POTABLE WATER PIPING
A. No permanent connections shall be made to the potable water system for the purpose of
flushing and disinfecting new water lines. A temporary connection with an Owner
approved backflow prevention device shall be utilized and provided by the Contractor to
deliver and flush potable water to and from the new waterline. Utilizing a portable pump
with check valves is one method of preventing backflow and achieving the high flows
that are needed to adequately flush large diameter waterlines.
B. Preliminary Flushing - The water line shall be thoroughly flushed with potable water
prior to disinfection to remove any debris that may have entered the line during
construction. The flushing velocity in the line shall not be less than two and one half
(2.5) feet per second. Flushing should continue until the volume of water that has
passed through the waterline is at least two and one half(2.5) times the volume of the
waterline being disinfected and the results of a bag test show no debris. If a bag test
shows any debris, then flushing shall continue until a bag test shows no debris.
It is the Contractor's responsibility to ensure that the wastewater generated by flushing
activities is disposed of in a responsible manner that is in accordance with all applicable
environmental regulations.
C. All newly installed water piping shall be disinfected in accordance with Virginia
Department of Health Waterworks Regulations and AWWA C651, latest revisions.
Disinfection method shall be by the continuous feed method. The tablet method shall
not be used. Contractor shall be responsible for all aspects of disinfection, sampling, and
testing at his own expense.
N:V16601-014\EngineerineDesign\Contract_Documents\Specifications\02516_Water_Pipe_Testing.doc 03/24/15
02516-6
North Fork Rivanna River Water Main Repair Water Pipe Testing
1. Continuous feed method.
a. Potable water shall be introduced into the pipeline at a constant flow rate
protected by an approved backflow prevention device. Chlorine shall be added
at a constant rate to this flow so that the chlorine concentration in the water in
the pipe is at least 50 mg/l.
b. The chlorinated water shall remain in the pipeline at least 24 hours, after which
the chlorine concentration in the water shall be at least 10 mg/l.
c. Valves and hydrants and other appurtenances shall be operated during the
disinfection process to be sure that they are disinfected as well.
D. Final Flushing - Following the chlorination period, flush the disinfectant from the piping
with potable water. All treated water flushed from the lines shall be disposed of by
discharging to the sanitary sewer system or other approved means. Provide a minimum
of 2 business days advance notice to the RWSA and ACSA prior to discharging to any
sanitary sewer system. No discharge to any storm sewer or natural watercourse will be
allowed without first dechlorinating the flushed water to a chlorine residual of 1 mg/I or
less.
E. Following final flushing, two (2) water samples for bacteriological test shall be collected
for each 1,200 feet of pipe disinfected, including one set from the end of the line.
Samples shall be taken 24 hours apart. Two consecutively tested samples must indicate
the absence of coliform contamination. Should the tests indicate the presence of
coliform contamination, the Contractor shall repeat the entire disinfection procedure
until two consecutive tests indicate the absence of coliform contamination. All cost for
re-disinfection, sampling, and testing will be at the Contractor's expense. Water samples
for total coliform shall be analyzed by a laboratory that is state certified for total
coliform analyses.
F. Disinfection shall also include hydrants, fittings, taps, tubing, and all other specials used
at connections to existing water mains. These shall be thoroughly disinfected
immediately prior to installation by emersion or spraying with a water solution
containing 250 mg/1 chlorine.
G. It is the Contractor's responsibility to ensure their operations do not contaminate the
public water supply. If, at any time, the water in the existing system becomes
contaminated, the Contractor shall be held financially accountable for any corrective
action taken by the Owner, as well as for cost of defending and settlement of all claims
resulting from Contractor's negligence, including, but not limited to, costs and
attorney's fees.
END OF SECTION
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02516_Water_Pipe_Testing.doc 03/24/15
02516-7
North Fork Rivanna River Water Main Repair Seeding,Topsoiling,Fertilizing and Mulching
SECTION 02911
SEEDING, TOPSOILING, FERTILIZING AND MULCHING
PART 1 - GENERAL
1.01 SCOPE OF WORK
A. Furnish all labor, materials, equipment, and incidentals required to place topsoil, finish
grade, and apply lime, fertilizer, seed, and mulch. Maintain all seeded areas as specified
herein, including all areas disturbed by the Contractor.
1.02 RELATED WORK
A. Section 02230, Clearing and Grubbing.
B. Section 02315, Excavation and Backfill.
C. Section 02370, Erosion and Sediment Control.
1.03 SAMPLES AND APPROVAL OF MATERIAL
A. Samples of all materials shall be submitted for inspection and acceptance upon request.
PART 2 -PRODUCTS
2.01 MATERIALS
A. Topsoil shall be applied in accordance with VESCH Standard and Specification 3.30
Topsoiling, where the existing soil is too coarse, dense, shallow, acidic, or contaminated
to foster vegetation.
1. Topsoil shall be fertile, friable, natural topsoil typical of topsoil of the locality, and
shall be obtained from a well-drained site that is free of flooding. It shall be without
admixture of subsoil or slag and free of stones, lumps, plants or their roots, sticks,
clay, peat, and other extraneous matter. Topsoil shall not be placed while in a frozen
or muddy condition. Topsoil delivered to the site shall have pH between 6.0 and 7.0
and shall contain not less than 3 percent organic matter as determined by loss of
ignition of moisture-free samples dried at 100 degrees Celsius.
B. Fertilizer shall be commercially mixed free flowing granules or pelleted fertilizer, 10-10-
10 (N-P205-K2O) grade for lawn and naturalized areas. Fertilizer shall be delivered to
the site in original unopened containers each showing the manufacturer's guaranteed
analysis conforming to applicable state fertilizer laws. At least 40 percent of the nitrogen
in the fertilizer used shall be in slowly available(organic) form.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`02911_Seeding_Topsoiling_Fertilizing_and_Mulching.doc 03/24/15
02911-1
r
North Fork Rivanna River Water Main Repair Seeding,Topsoiling,Fertilizing and Mulching
C. Seeding shall be performed in accordance with VESCH Standard and Specification 3.31
Temporary Seeding, or 3.32 Permanent Seeding, as applicable.
1. Seed shall be labeled in accordance with USDA Rules and Regulations under the
Federal Seed Act and shall comply with the requirements of the Virginia Erosion and
Sediment Control Handbook standard. Seed shall be furnished in sealed bags or
containers bearing the date of the last germination, which date shall be within a
period of 6 months prior to commencement of planting operations. Seed shall be
from same or previous year's crop; each variety of seed shall have a purity of not less
than 85 percent, a percentage of germination not less than 90 percent, shall have a
weed content of not more than 1 percent and contain no noxious weeds.
2. Seed mix for permanent seeding shall be in strict accordance with the VESCH. All
temporary seeding shall be as per VESCH. Seed shall be accompanied by an
affidavit for seed conforming to Section 244.02 (c) of Virginia Department of
Transportation Road and Bridge Specifications, latest edition.
3. The seed shall be furnished and delivered pre-mixed in the proportions specified
above. The manufacturers for each seed type shall submit a manufacturer's
certificate of compliance to the specified mixes. These certificates shall include the
guaranteed percentages of purity, weed content and germination of the seed, and
also the net weight and date of shipment. No seed may be sown until the Contractor
has submitted the certificates.
4. Seed shall be delivered in sealed containers bearing the dealer's guaranteed analysis.
D. Straw mulch shall be as specified in Section 02370, Erosion and Sediment Control and
the VESCH.
E. Mulch for hydroseeding operations shall be a specially processed cellulose fiber
containing no growth or germination inhibiting factors. It shall be manufactured in such
a manner that after addition and agitation in slurry tanks with water, the fibers in the
material become uniformly suspended to form a homogeneous slurry. When sprayed on
the ground, the material shall allow absorption and percolation of moisture. Each
package of the cellulose fiber shall not contain in excess of 10 percent moisture and shall
be marked by the manufacturer to show the air-dry weight content.
F. Mulch tacking agent shall be as specified in Section 02370, Erosion and Sediment
Control and the VESCH.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications'02911_Seeding_Topsoiling_Fecrilizing_and_Mulching.doc 03/24/15
02911-2
North Fork Rivanna River Water Main Repair Seeding,Topsoiling,Fertilizing and Mulching
PART 3- EXECUTION
3.01 APPLICATION
A. Acceptable topsoil shall be placed to a minimum compacted depth of 6 inches on all
disturbed areas.
B. For all areas to be seeded:
1. Fertilizer (10-10-10) shall be applied at the rate of 40 pounds per 1,000 square feet
and lightly worked in by approved methods.
2. Seed mix shall be applied at a rate of 20 pounds per 1,000 square feet.
3. Mulch shall be applied at the rate of 40 pounds per 1,000 square feet.
C. The application of fertilizer may be performed hydraulically in one operation with hydro-
seeding and fiber mulching. The Contractor is responsible for cleaning all structures and
paved areas of unwanted deposits of the hydroseeded mixture.
3.02 INSTALLATION
A. Previously established grades as shown on Drawings shall be maintained in a true and
even condition.
B. The topsoil shall be carefully prepared by scarifying or harrowing and hand raking after it
has been spread. All stiff clods, lumps, roots, litter, and other foreign material shall be
removed from the loamed area and disposed of by the Contractor. The areas shall also
be free of smaller stones in excessive quantities as determined by the Owner. The whole
surface shall then be rolled with a hand roller weighing not more than 100 pounds per
foot of width. During the rolling, all depressions caused by settlement of rolling shall be
filled with additional loam and the surface shall be re-graded and rolled until a smooth
and even finished grade is created.
C. Seeding, mulching, and conditioning shall only be performed during those periods within
the seasons that are normal for such work as determined by the weather and locally
accepted practice.
D. Schedules for seeding and fertilizing must be submitted to the Owner for approval prior
to the work. Seeding as specified herein shall be accomplished between the period of
April 1 to May 31 or August 16 to October 15. Seeding during the periods from
October 16 to March 31 and from June 1 to August 15 shall only be undertaken upon
approval of the Owner.
E. Seeding shall be done within 5 days following soil preparation. Seed shall be applied at
the rates and percentages indicated.
N:'46601-014\Engineering\DesignContract_Documents\Specifications\02911_Seeding_Topsoiling_Fertilizing_and_Mulching.doc 03/24/15
02911-3
North Fork Rivanna River Water Main Repair Seeding,Topsoiling,Fertilizing and Mulching
F. Slopes whose vertical height is less than 20 feet but more than 5 feet shall be seeded in 2
equal increments. Slopes whose vertical height is 5 feet or less may be seeded in one
operation. Slopes greater than 2H:1 V shall be protected by erosion control matting
acceptable to the Owner.
G. In order to prevent unnecessary erosion of newly topsoiled and graded slopes and
unnecessary siltation of drainage ways, the Contractor shall carry out seeding and
mulching as soon as he has satisfactorily completed a unit or portion of the project or
when 1,000 square feet of ground surface has been disturbed. When protection of newly
topsoiled and graded areas is necessary at a time which is outside of the normal seeding
season, the Contractor shall protect those areas by whatever means necessary as
approved by the Owner and shall be responsible for prevention of siltation in the areas
beyond the limit of Work.
H. When newly graded sub-grade areas cannot be topsoiled and seeded because of season
or weather conditions and will remain exposed for more than 30 days, the Contractor
shall protect those areas against erosion and washouts by whatever means necessary such
as straw applied with a tar tack, wood chips, or by other approved measures. Prior to
application of topsoil, any such materials applied for erosion control shall be thoroughly
incorporated into the sub-grade by disking. Fertilizer shall be applied prior to spreading
of topsoil.
I. On slopes, the Contractor shall protect against washouts by an approved method. Any
washout that occurs shall be re-graded and re-seeded at the Contractor's expense until a
good sod is established.
3.03 MAINTENANCE AND PROVISIONAL ACCEPTANCE
A. The Contractor shall maintain seeded areas, re-seeding if and when necessary, until a
good, healthy, uniform growth is established over the entire area seeded.
B. The Owner will inspect all work for provisional acceptance at the end of a 10-week
maintenance period upon receiving written request from the Contractor at least 10 days
prior to the anticipated date of inspection.
C. A satisfactory stand will be defined as a section of turf of 1,000 square feet or larger that
has:
1. No bare spots larger than three square feet.
2. No more than 10 percent of total area with bare spots larger than 1 square foot.
3. Not more than 15 percent of total area with bare spots larger than 6 square inches.
N:V16601-014\Engineering\Design\Contract_Documents\Specifications`02911_Seeding_Topsoiling_Fertilizing_and_Mulching.doc 03/24/15
02911-4
North Fork Rivanna River Water Main Repair Seeding,Topsoiling,Fertilizing and Mulching
3.04 GUARANTEE PERIOD AND FINAL ACCEPTANCE
A. The Contractor shall guarantee all seeded areas for not less than 1 full year from the
time of acceptance by Owner.
END OF SECTION
NM6601-014\Engineering\Design\Contract_Documents\Specifications\D2911Seeding_Topsoiling_Fertilizing_and_Mulching.doc 03/24/15
02911-5
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
SECTION 03300
CAST-IN-PLACE CONCRETE
PART 1 - GENERAL
1.01 SCOPE OF WORK
A. Furnish all labor and materials required and install cast-in-place concrete complete as
shown on the Drawings and as specified herein.
1.02 RELATED WORK (N/A)
1.03 SUBMITTALS
A. Submit to the Owner shop drawings and product data including the following:
1. Sources of cement, pozzolan, and aggregates.
2. Air-entraining admixture. Product data including catalog cut, technical data, storage
requirements, product life, recommended dosage, temperature considerations, and
conformity to ASTM standards.
3. Water-reducing admixture. Product data including catalog cut, technical data,
storage requirements, product life, recommended dosage, temperature
considerations, and conformity to ASTM standards.
4. High-range water-reducing admixture (plasticizer). Product data including catalog
cut, technical data, storage requirements, product life, recommended dosage,
temperature considerations, retarding effect, slump range, and conformity to ASTM
standards.
5. Concrete mix for each formulation of concrete proposed for use including
constituent quantities per cubic yard, water-cementitious materials ratio, concrete
slump, type, and manufacturer of cement.
B. Certifications.
1. Certify admixtures used in the same concrete mix are compatible with each other
and the aggregates.
1.04 REFERENCE STANDARDS
A. American Society for Testing and Materials(ASTM).
N:\46601-014\Engineering\DesignContract_Documents\.Specifications433300_Cast_in_Place_Concrete.doc 03/24/15
03300-1
MIL
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
1. ASTM C31 - Standard Practice for Making and Curing, Concrete Test Specimens in
the Field.
2. ASTM C33 - Standard Specification for Concrete Aggregates.
3. ASTM C39 - Standard Test Method for Compressive Strength of Cylindrical
Concrete Specimens.
4. ASTM C94 - Standard Specification for Ready-Mixed Concrete.
5. ASTM C143 - Standard Test Method for Slump of Hydraulic Cement Concrete.
6. ASTM C150 - Standard Specification for Portland Cement.
7. ASTM C231 - Standard Test Method for Air Content of Freshly Mixed Concrete by
the Pressure Method.
8. ASTM C260 - Standard Specification for Air-Entraining Admixtures for Concrete.
9. ASTM C494 - Standard Specification for Chemical Admixtures for Concrete.
10. ASTM C1017 - Standard Specification for Chemical Admixtures for use in
Producing Flowing Concrete.
B. American Concrete Institute(ACI).
1. ACI 304R- Guide for Measuring, Mixing, Transporting and Placing Concrete.
2. ACI 305R- Hot Weather Concreting.
3. ACI 306.1 - Standard Specification for Cold Weather Concreting.
4. ACI 318 - Building Code Requirements for Structural Concrete.
5. ACI 350R- Environmental Engineering Concrete Structures.
C. Where reference is made to one of the above standards, the revision in effect at the time
of bid opening shall apply.
1.05 QUALITY ASSURANCE
A. Reinforced concrete shall comply with ACI 318, the recommendations of ACI 350R and
other stated requirements, codes, and standards. The most stringent requirement of the
codes, standards, and this Section shall apply when conflicts exist.
B. Only one (1) source of cement and aggregates shall be used on any single structure.
Concrete shall be uniform in color and appearance.
N:kt6601-014\EngineerineDesign\Contract_Documents\Specifications`03300_Cast_in_Place_Concrete.doc 03/24/15
03300-2
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
PART 2 - PRODUCTS
2.01 MATERIALS
A. Cement: Domestic Portland cement complying with ASTM C150 — Type II. Cement
brand shall be subject to approval and one brand shall be used throughout the Work.
B. Supplemental cementitious material: Ground granulated blast-furnace slag.
1. Meet ASTM C989(Grade 120).
2. Blend with Portland cement meeting requirements of ASTM C595 Type IS or IS
(MS).
3. Supplier: Blue Circle Cement, Inc., Product: NewCem, or approved equal.
C. Fine aggregate: Washed inert natural sand conforming to the requirements of ASTM
C33.
D. Coarse aggregate: Well-graded crushed stone or washed gravel conforming to the
requirements of ASTM C33. Grading requirements shall be as listed in ASTM C33
Table 3 for the specified coarse aggregate size number. Limits of deleterious substances
and physical property requirements shall be as listed in ASTM C33 Table 3 for severe
weathering regions. Size numbers for the concrete mixes shall be as shown in Table 1
herein.
E. Water: Potable water, free from injurious amounts of oils, acids, alkalis, salts, organic
matter, or other deleterious substances.
F. Admixtures: Admixtures shall be free of chlorides and alkalis (except for those
attributable to water). When it is required to use more than one admixture in a concrete
mix, the admixtures shall be from the same manufacturer. Admixtures shall be
compatible with the concrete mix including other admixtures.
1. Air-entraining admixture: The admixture shall comply with ASTM C260.
Proportioning and mixing shall be in accordance with manufacturer's
recommendations.
2. Water-reducing agent: The admixture shall comply with ASTM C494, Type A.
Proportioning and mixing shall be in accordance with manufacturer's
recommendations.
3. High-range water-reducer (plasticizer): The admixture shall comply with ASTM
C494, Type F and shall result in non-segregating plasticized concrete with little
bleeding and with the physical properties of low water/cement ratio concrete. The
treated concrete shall be capable of maintaining its plastic state in excess of 2 hours.
N:\46601-014\Engineering sign\Contract_Documents\Specifications`fi3300_Cast_in_P1ace_Concrete.doc 03/24/15
03300-3
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
Proportioning and mixing shall be in accordance with manufacturer's
recommendations.
4. Admixtures causing retarded or accelerated setting of concrete shall not be used
without written approval from the Owner. When allowed, the admixtures shall be
retarding or accelerating water reducing or high range water reducing admixtures.
G. Sheet curing materials: Waterproof paper, polyethylene film, or white burlap-
polyethylene sheeting all complying with ASTM C171.
2.02 MIX
A. Development of mix design and testing shall be by an independent testing laboratory
acceptable to the Owner engaged by and at the expense of the Contractor.
B. Select proportions of ingredients to meet the design strength and materials limits
specified in Table 1 and to produce concrete having proper placability, durability,
strength, appearance, and other required properties. Proportion ingredients to produce
a homogenous mixture that will readily work into corners and angles of forms and
around reinforcement without permitting materials to segregate or allowing excessive
free water to collect on the surface.
C. The design mix shall be based on standard deviation data of prior mixes with essentially
the same proportions of the same constituents or, if such data is not available, be
developed by a testing laboratory engaged by and at the expense of the Contractor.
Acceptance of mixes based on standard deviation shall be based on the modification
factors for standard deviation tests contained in ACI 318. The water content of the
concrete mix, determined by laboratory testing, shall be based on a curve showing the
relation between water cementitious ratio and 7- and 28-day compressive strengths of
concrete made using the proposed materials. Four (4) or more points shall determine
the curves, each representing an average value of at least 3 test specimens at each age.
The curves shall have a range of values sufficient to yield the desired data, including the
specified design strengths as modified below, without extrapolation. The water content
of the concrete mix to be used, as determined from the curve, shall correspond to
strengths 16 percent greater than the specified design strength. The resulting mix shall
not conflict with the limiting values for maximum water cementitious ratio and net
minimum cementitious content as specified in Table 1 below.
D. Compression tests: Provide testing of the proposed concrete mix to demonstrate
compliance with the specified design strength requirement in conformity with the above
paragraph.
E. Entrained air, as measured by ASTM C231, shall be as shown in Table 1 below.
1. If the air-entraining agent proposed for use in the mix requires testing methods other
than ASTM C231 to accurately determine air content, make special note of this
requirement in the admixture submittal.
NM6601-014\Engineering\Design\Contract_Documents\Specificationss43300_Cast_in_Place_Concrete.doc 03/24/15
03300-4
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
F. Slump of the concrete as measured by ASTM C143, shall be as shown in Table 1 below.
If a high-range water-reducer (plasticizer) is used, the slump indicated shall be that
measured before plasticizer is added. Plasticized concrete shall have a slump ranging
from 7 to 10 inches.
G. Proportion admixtures according to the manufacturer's recommendations. Two (2) or
more admixtures specified may be used in the same mix provided that the admixtures in
combination retain full efficiency and have no deleterious effect on the concrete or on the
properties of each other.
TABLE 1
CONCRETE MIX REQUIREMENTS
Design Fine Coarse Water
Class Strength Cement Aggregate Aggregate
(1) (2) (3) (4) (3) (4)
A3 3000 psi 588 Ib/cu yd 1362 Ib/cu yd 1811 lb/cu yd 33.5 gal/cu yd
A4 4000 psi 635 lb/cu yd 1219 lb/cu yd 1811 lb/cu yd 33.5 gal/cu yd
Flowable Fill 30 psi -- -- -- --
W/C AE Slump
Class Ratio Fly Ash Range WR HRWR Range
(5) (6) (7) (8) Inches
A3 0.56 -- 6 +/- 2% -- -- 1-5"
A4 0.45 -- 6+/- 1% -- -- 2-4"
Flowable Fill -- -- -- -- -- --
NOTES:
(1) Minimum compressive strength in psi at 28 days.
(2) Min. amount of Type I or Type II Portland Cement per ASTM C 150
(3) Saturated surface dry weight
(4) #57 size manufactured and tested for acceptance by ASTM C33 and The Virginia
Department of Transportation Road and Bridge Specifications.
(5) Max. water-cementitious ratio by weight.
(6) AE is percent air-entrainment. AE admixtures to meet or exceed requirements of
ASTM C-260 and AASHTO M-154.
(7) WR is water-reducer admixture. WR admixtures to meet or exceed requirements
of ASTM C-494 and AASHTO M-194.
(8) HRWR is high-range water-reducer admixture. HRWR admixtures to meet or
exceed requirements of ASTM C-494 Types A&F and AASHTO M-194 Types A
&F.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications\03300_Cast_in_PlaceConcrete.doc 03/24/15
03300-5
MIL
•
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
2.03 CONCRETE ENCASEMENT
A. Concrete encasement shall be VDOT Class A3 concrete.
2.04 FLOWABLE BACKFILL
A. Existing water mains identified to be abandoned shall be filled with flowable backfill by
the Contractor at no additional cost to the Owner.
B. Flowable backfill shall be in accordance with VDOT Special Provision for Flowable
Backfill.
PART 3- EXECUTION
3.01 MEASURING MATERIALS
A. Concrete shall be composed of Portland cement, blast-furnace slag, fine aggregate,
coarse aggregate, water, and admixtures as specified and shall be produced by a plant
acceptable to the Owner. All constituents, including admixtures, shall be batched at the
plant except a high-range water reducer may also be added in the field.
B. Measure materials for batching concrete by weighing in conformity with and within the
tolerances given in ASTM C94 except as otherwise specified.
C. Measure the amount of free water in fine aggregates within 0.3 percent with a moisture
meter. Compensate for varying moisture contents of fine aggregates. Record the
number of gallons of water as batched on printed batching tickets.
D. Admixtures shall be dispensed either manually using calibrated containers or measuring
tanks, or by means of an automatic dispenser approved by the manufacturer of the
specific admixture.
1. Charge air-entraining and chemical admixtures into the mixer as a solution using an
automatic dispenser or similar metering device.
2. Inject multiple admixtures separately during the batching sequence.
3.02 MIXING AND TRANSPORTING
A. Concrete shall be ready-mixed concrete produced by equipment acceptable to the
Owner. Hand mixing will not be permitted. Equip each transit-mix truck with a
continuous, non-reversible, revolution counter showing the number of revolutions at
mixing speeds.
B. Ready-mix concrete shall be transported to the site in watertight agitator or mixer trucks
loaded not in excess of their rated capacities as stated on the nameplate.
N:\46601-014\Engineering\Design�Contract_Documents\SPecificationA3300_Cast_in_Place_Concrete.doc 03/24/15
03300-6
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
C. The Owner must direct any addition of water. Added water shall be incorporated by
additional mixing of at least 35 revolutions. All added water shall be metered and the
amount of water added shall be shown on each delivery ticket.
D. Re-tempering (mixing with or without additional cement, aggregate, or water) of
concrete or mortar that has reached initial set will not be permitted.
E. Furnish a delivery ticket for ready-mixed concrete batch. Each ticket shall provide a
printed record of the weight of cement and each aggregate as batched individually.
Clearly indicate the weight of fine and coarse aggregate, cement and water in each batch,
the quantity delivered, and the time any water is added. Show the time of day batched
and time of discharge from the truck
F. Temperature control.
1. In cold weather, do not allow the as-mixed temperature of the concrete and
concrete temperatures at the time of placement in the forms to drop below 40
degrees F.
2. If water or aggregate has been heated, combine water with aggregate in the mixer
before cement is added. Do not add cement to mixtures of water and aggregate
when the temperature of the mixture is greater than 90 degrees F.
3. In hot weather, cool ingredients before mixing to maintain temperature of the
concrete below the maximum placing temperature of 90 degrees F. If necessary,
substitute well-crushed ice for all or part of the mixing water.
3.03 PLACING AND COMPACTING
A. Placing.
1. Verify that all formwork completely encloses concrete to be placed and is securely
braced prior to concrete placement. Remove ice, excess water, dirt, and other
foreign materials from forms. Confirm that reinforcement and other embedded
items are securely in place. Have a competent workman at the location of the
placement who can assure that reinforcing steel and embedded items remain in
designated locations while concrete is being placed. Sprinkle semi-porous sub-
grades or forms to eliminate suction of water from the mix. Seal extremely porous
sub-grades in an approved manner.
2. Deposit concrete as near its final position as possible to avoid segregation due to re-
handling or flowing. Place concrete continuously at a rate that ensures the concrete
is being integrated with fresh plastic concrete. Do not deposit concrete that has
partially hardened or has been contaminated by foreign materials or on concrete that
has hardened sufficiently to cause formation of seams or planes of weakness within
the section. If the section cannot be placed continuously, place construction joints
as specified or as approved.
N:W6601-014\Engineering\Design\Contract_Documents\Specifications`A3300_Cast_in_P1ace_Concrete.doc 03/24/15
03300-7
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
3. Pumping of concrete will be permitted. Use a mix design and aggregate sizes
suitable for pumping.
4. Remove temporary spreaders from forms when the spreader is no longer useful.
Temporary spreaders may remain embedded in concrete only when made of
galvanized metal or concrete and if prior approval has been obtained.
5. Slabs.
a. After suitable bulkheads, screeds, and jointing materials have been positioned,
the concrete shall be placed continuously between construction joints
beginning at a bulkhead, edge form, or corner. Each batch shall be placed into
the edge of the previously placed concrete to avoid stone pockets and
segregation.
b. Avoid delays in casting. If there is a delay in casting, the concrete placed after
the delay shall be thoroughly spaded and consolidated at the edge of that
previously placed to avoid cold joints. Concrete shall then be brought to
correct level and struck off with a straightedge. Bullfloats or darbies shall be
used to smooth the surface, leaving it free of humps or hollows.
B. Compacting.
1. Consolidate concrete by vibration, puddling, spading, rodding, or forking so that
concrete is thoroughly worked around reinforcement, embedded items, and
openings, and into corners of forms. Puddling, spading, etc., shall be continuously
performed along with vibration to eliminate air or stone pockets that may cause
honeycombing, pitting, or planes of weakness.
3.04 CURING AND PROTECTION
A. Protect all concrete work against injury from the elements and defacements of any nature
during construction operations.
B. Curing methods.
1. Curing methods for concrete surfaces: Cure concrete to retain moisture and
maintain minimum temperature at the surface for a minimum of 2 days after
placement. Curing methods to be used are as follows:
a. Sheet material curing: Cover entire surface with sheet material. Securely
anchor sheeting to prevent wind and air from lifting the sheeting or entrapping
air under the sheet. Place and secure sheet as soon as initial concrete set
occurs.
N:\46601-014\Engineering\Design\Contract_Documents\Specifications`03300_Cast_in_P1ace_Concrete.doc 03/24/15
03300-8
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
b. Liquid membrane curing: Apply over the entire concrete surface except for
surfaces to receive additional concrete. Curing compound shall NOT be placed
on any concrete surface where additional concrete is to be placed, or where
concrete sealers or surface coatings are to be used. Application shall be in
compliance with the manufacturer's recommendations.
C. Finished surfaces and slabs shall be protected from the direct rays of the sun to prevent
checking and crazing.
D. Cold weather concreting.
1. "Cold weather" is defined as a period when for more than 3 successive days, the
average daily outdoor temperature drops below 40 degrees F. The average daily
temperature shall be calculated as the average of the highest and the lowest
temperature during the period from midnight to midnight.
2. Discuss a cold weather work plan with the Owner. The discussion shall encompass
the methods and procedures proposed for use during cold weather including the
production, transportation, placement, protection, curing, and temperature
monitoring of the concrete. The procedures to be implemented upon abrupt changes
in weather conditions or equipment failures shall also be discussed. Cold weather
concreting shall not begin until the work plan is acceptable to the Owner.
E. Hot weather concreting.
1. "Hot weather" is defined as any combination of high air temperatures, low relative
humidity, and wind velocity that produces a rate of evaporation estimated in
accordance with ACI 305R, approaching or exceeding 0.2 lbs./sq.ft./hr.
2. Concrete placed during hot weather, shall be batched, delivered, placed, cured, and
protected in compliance with the recommendations of ACI 305R and the additional
requirement specified herein.
a. Temperature of concrete being placed shall not exceed 90 degrees F. Every
effort shall be made to maintain a uniform concrete mix temperature below this
level.
3. Discuss with the Owner a work plan describing the methods and procedures
proposed to use for concrete placement and curing during hot weather periods.
Hot weather concreting shall not begin until the work plan is acceptable to the
Owner.
N:\46601-014\EngineerineDesign\Contract_Documents\Specificationsb3300_Cast_in_PlaceConcrete.doc 03/24/15
03300-9
rirmoommismomminimielimmor
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
3.05 INSPECTION AND FIELD TESTING
A. The batching, mixing, transporting, placing, and curing of concrete may be subject to the
observation and testing by the Owner at any time.
B. The Owner may have cores taken from any questionable area in the concrete work for
determination of concrete quality. The results of tests on such cores shall be the basis
for acceptance, or rejection of the concrete work. The costs for all testing to
demonstrate compliance with the Specifications shall be the responsibility of the
Contractor.
C. The Contractor shall cooperate in obtaining cores by allowing free access to the work
and permitting the use of incidental equipment as may be required. The Contractor shall
also repair all core holes. Cores for testing shall not be taken until concrete has aged a
minimum of 60 days.
D. Routine Testing — All cast-in-place concrete shall be tested at the Contractor's expense
and in accordance with the following requirements:
1. Slump: On each transit truck batch until measured slump is consistent with
specifications and every fourth transit truck batch thereafter. Perform additional
tests when concrete consistency appears to change.
2. Air Content: With each slump test.
3. Concrete Temperature: With each Slump and Air Content test.
4. Compression Test Specimens: Cast one set of four standard cylinder specimens for
each 50 cubic yards or fraction thereof, for each concrete mixture used.
Compression Test specimens shall be formed from composite samples taken in
accordance with ASTM C 172.
5. Compressive Strength Tests: Compressive strength tests shall be conducted on test
specimens in accordance with ASTM C 39. Test one set of two laboratory-cured
specimens at 7 days and one set of two specimens at 28 days. A compressive-
strength test shall be the average compressive strength from a set of two specimens
obtained from the same composite sample and tested at age indicated.
NOTE: Concrete not within the specified limits of slump, air content, and temperature
shall not be used in the work.
The strength of concrete will be considered satisfactory when the average compressive
strength test results equal or exceeds the specified compressive strength and no
individual strength test result falls below the specified compressive strength by more than
500 psi
N:'46601-014\EngineerineDesign\Contract_Documents\Specifications\03300_Cast_in_Place_Concrete.doc 03/24/15
03300-10
.
North Fork Rivanna River Water Main Repair Cast-in-Place Concrete
3.06 FAILURE TO MEET REQUIREMENTS
A. When the tests on specimens of concrete fall below the specified strength, the Owner will
permit check tests for strengths to be made by means of typical cores drilled from the
structure in compliance with ASTM C42 and C39 at the Contractor's expense. In the
case of cores not indicating adequate strength, the Owner, in addition to other recourses,
may require, at the Contractor's expense, the replacement of those portions of the
concrete work that fail to develop the required strength.
END OF SECTION
N:\46601-014\Engincering\Design\Contract_Documents\Specifications`03300_Cast_in_Place_Concrete.doc 03/24/15
03300-11
APPENDIX A
Approved Products List
Water Pipe, Fittings & Appurtenances
Ductile Iron Pipe& C.I. or D.I.Fittings
1. U.S. Pipe&Foundry Co.
2. Atlantic States Cast Iron Pipe Co.
3. American Cast Iron Pipe Co.
Fittings
1. Tyler: with D.I. T-bolts or Corten steel bolts
2. Standard International:with Corten steel bolts
3. Union Foundry Co.
4. Star Pipe Products
Copper Pipe
1. Must be soft Type "K" copper with standard waterworks flare fittings only, except for factory-
tested subcomponent joints.
Marking Tape
1. Allen Systems: min. 3"wide, stamped"water" (blue)
2. Harris Industries,Inc.: min. 3"wide, stamped "water"(blue)
Conductive Wire
1. Must be 10-gauge or larger, insulated copper wire.
Repair Clamps
1. Romac: SS Series repair clamp
2. Hymax: EZ-Max Plus repair clamp
3. Ford: FS2 Series repair clamp(must be wide range)
Bell Joint Leak Clamp
1. Smith-Blair Style 274
Transition/Repair Couplings
1. Hymax: 2000 Series
2. Romac: 501 Series
3. Romac: XR 501 Series
4. MJ Repair Sleeves by Tyler, Standard International,Union Foundry, and Star Pipe Products.
Restrained Joints, 12" and larger
1. EBAA Iron, Inc.: Megalug Series 1100
2. U.S. Pipe and Atlantic States, TR FLEX®
3. American Flex-Ring®
Restrained Joints,less than 12"
1. EBAA Iron,Inc.: Megalug Series 1100
Valves & Appurtenances
Gate Valves
1. U.S.Pipe: Metroseal 250 resilient seated gate valve (4" and larger)
2. American Flow Control: Series 2500 resilient wedge valve(2"and larger)
*Brass fittings shall contain no lead. Page Al of A3 03/24/15
MIL
3. Kennedy: Ken-Seal II resilient wedge gate valve(4" and larger)
4. Mueller: Series 2360 resilient wedge gate valve
5. American AVK: Series 45 resilient wedge gate valve
Tapping Valves
1. American Flow Control: Series 2500
2. Kennedy: Ken-Seal II resilient wedge gate valve(4" and larger)
3. Mueller: Series T-2360 resilient wedge gate valve
4. Clow
Tapping Sleeves
1. Mueller: Catalog No. H-615
2. American Flow Control: mechanical joint tapping sleeve
3. Clow
4. Romac: Model SST,or SST III(stainless steel)
5. Ford: Model FAST(stainless steel)
6. PowerSeal Pipeline Products Corp.:Powersleeve Model 3490,or PowerMJ Model 3490MJ
7. Smith-Blair, Inc.: Model 663 (all stainless steel; mechanical joint outlet option is also
approved).
8. Cascade: Model CST-EX
Valve Boxes
1. Bingham&Taylor: Fig.No.4906(genuine Buffalo style)with standard cover;extensions- Fig.
No.4905-X, Oval Base -Fig.No.4909-D.
2. Capitol Foundry: cast iron screw type Pattern No. 3101-3107/3112/3151-52; standard cover
with 1-1/2" lip
3. East Jordan Iron Works: 8550 Series,Two Piece Screw Type with 6800 Valve Box Drop Lids.
Valve Box Base number 85605160
Valve Box Risers
1. East Jordan Iron Works: 8500, lock-in set screw required.
2. Acheson: valve box adjusting rings,AVAR-10 through AVAR-40
*Brass fittings shall contain no lead. Page A2 of A3 03/24/15
Service Laterals*
Corporation Stops
1. Mueller: Catalog No. 13-25000
2. Ford: Model No. FB600-4
3. A.Y.McDonald: Model 4701B
Service Saddles
1. Romac: Style 202S Painted Saddle with stainless steel straps
2. Ford: Style FS202 with wide stainless steel band(4 bolts)
3. Smith-Blair,Inc. Model 317 with stainless steel straps
Quarter-Bend Couplings
1. Mueller: Catalog No.H-15069(3/4",1")
2. Mueller: Catalog No. H-15068(1-1/2",2")
3. Ford: Model No. L02-33 (3/4")
4. Ford: Model No.L02-44(1")
5. Ford: Model No.L02-66(1-1/2")
6. Ford: Model No. L02-77(2")
7. A.Y.McDonald 4776S
Meter Coppersetters
1. Ford: Model No. VV 72(5/8"x3/4")
2. Ford: Model No. VV 74(1")
3. A.Y.McDonald: Model No. 20-209 WWDD33,20-412 WWDD44
4. Ford: Model No. VBB77-12B-11-77
5. Mueller: Model No.13-2423 (1-1/2",2"). Laying length for meter varies with specific meter size
— coordinate with ACSA prior to installation.
6. A.Y.McDonald: Series 20, horizontal style (1",5/8"x3/4"), high bypass(1-1/2" &2")
Flared Fittings
1. Ford: Grip Joint
2. Mueller: Model 110
3. A.Y.McDonald: "T" Series
Miscellaneous Fittings
1. Mueller: brass cap for plugging flared copper,Catalog No.H-15540
Meter Boxes(5/8" and 1")
1. For grass areas: Carson: 2200 Series(plastic)
2. For paved areas: Bingham&Taylor: BTPMS 20X24 Arched Meter Pit with BTA-3C Cast Iron
Frame and Cover
Meter Vaults(1-1/2"and larger)
1. The Clear Flow Co.: Precast concrete meter vaults; Type 3652 1-1/2" and 2"); Type TJ-2000
(3"and 4")(available with H-20 load rating)
2. NAPPCO: Flange adaptors for ductile iron and steel pipe 2"-48"(for use in meter vaults only)
*Brass fittings shall contain no lead. Page A3 of A3 03/24/15
APPENDIX B
Standard Details
TRENCH DETAILS IN GRAVEL AREAS --1—.--TRENCH
TRENCH DETAILS IN GRASSED AREAS
WARNING TAPE 24" DEEP
COMPACTED COMMON BACKFILL
r i•l! r r!• r r l r� r r. r � f� •T:,•r_$�ti •r.•���......... ..... .. . . ..
a;.• • r • !• • • r•!a • •• •r r r•.��7�s��•.•www•w...'.'.'.'.'.'.'..'.'.'.'.'.'.'.'.'.'. / A ///
!If1lflf1lIfl7.!! f11lf •—._•.-•�•�•.�._•.�•.�, ..•••. • •.. ..... • •.•
•
•
•
•
.'. ' • ..... ....• •••••
•'r•' •r•'r•'r•'r•'r1
•
\ ► eie ri.": 10-1.1;'....• ...... ....... .....'/\;
\ ��� f=ea;j�j�j�•: . ..... . ... ........ ....'/\\/ 42" MIN. COVER
\� ;_ :_ _:•.•.•.. :.. ...... ...... . .... .../\/ 48" MIN.
VDOTOR 21 B / =1:f,: : lili.. ........ ..•• •••• /\
#21A ,• • • :0;,•,-"7:1711. \AT 16" GATE VALVES
STONE COMPACTED TO \\/ -'' 'r'''"'''�''' -'"1' " _ _ =/ . AND IN CSX R/W
95% / 11 ./I I'I�I I—III' I—)IIII=III\
MAX. DENSITY •
/f / r��-� •r����'r•'r••r� I II--
TOII I /
PLACED IN 6 LIFTS, 'L• _-•_--•�--�!---!--_•-�
ORIGINAL GRADE. .-.•--•-•-•-•-•- _ �•---
VelifU••%• -I 1-I I IVI-VIII—I I I
.f•r =•�•�•=•
$" II I I I IIIA
Or( •'„111•��•, -
10 GAUGE I-111 - III 1-IIIl 1I-
•'•'''''''
TRACE WIRE •-•-•-•--•-•-•-• — _
►���•r •61��r r •r4.rl•r r — III=
COMPACTED
- -,.r_
WATER IINITIAL BACKFILL
I=11111
=
.� MAIN latter PLACE BEDDING
te•�irititj t 414;707411/4 STONE TO PIPE SPRINGLINE
r a..a..•` fs..a..•..
VDOT #57 STONE
;��0�0.04►���;c/ . � � , 4" MIN. #57 STONE
BEDDING AND BACKFILL ,. � � ���►� � � 'Y� Y� BEDDING
NOTES:
1. THIS DETAIL APPLICABLE FOR DEPTHS LESS THAN 14 FEET. SEE PLANS FOR MODIFICATIONS IN
DEEPER TRENCHES.
2. BACKFILL SHALL BE COMPACTED IN 6” LIFTS.
3. WHEN PIPE PLACED ON STABLE SOIL, SCRAPE THE BOTTOM OF THE TRENCH, REMOVE ALL
STONES TO ENSURE THE PIPE DOES NOT REST ON ROCK, THEN COMPACT THE SOIL. BELL HOLES
SHALL BE PROVIDED FOR EACH JOINT TO ENSURE THAT THE PIPE BARREL WILL BE FLAT ON
TRENCH BOTTOM.
4. FOR PAVEMENT RESTORATION REQUIREMENTS SEE VDOT DETAIL
LUP-OCPR.
VIAILIVJA
WHITMAN, REQUARDT Drawing No.
& ASSOCIATES, LLP
loo Kraft Drive,Sults laoo,Bl.eksbur1,VA .4o6o TRENCH BED DETAIL TB
Scale: NTS
N:\46601-005\CADD\Civil\details\Pressure_Pipe_Trench_Bed_Detail.dwg Feb 26, 2014 - 8:17am
STREAM OR RIVER
///// //�/j\
\ \\ •
48" MIN.
PIPE AS SHOWN
ON PLAN
D p' .
LENGTH AS SHOWN ON PLANS
PROFILE
CONCRETE
PER SPECIFICATIONS
•
PIPE BELL
MARVA
WHITMAN, R E Q U A R D T Drawing No.
& ASSOCIATES, LLP
,loo Kraft Drive,Suit.lam BlackaburB,VA 24060 CONCRETE PIPE ENCASEMENT CE-01
Scale: NTS
—k
1 360 DEG. SWIVEL
a .
1 i" BALL VALVE % ,I
BRASS PIPE VALVE BOX
TEST ` P o ,
VALVE PORTABLE SAMPLING STATION
TESTING ROD1
o,''. / 'i
BRASS FEMALE
VALVE ACUATOR ° i" PIPE
r
i % i
�/ A 1 I l i/ iii
41. imp 411151WMAYlicalli
III AtC> ,-**P111-10-17
0.2\ v. 1111P 41. Or 41) OP 0 C
" CORP S OP
ft
�.AO* �. tt
�.C i" FIP INLET
PVC DEBRIS �.�-4.�-�.
COVER
2'X2'X2' DRY GRAVEL PIT
VDOT#57 STONE
VIIMIRMIT
WHITMAN, REQUARDT Drawing No.
& ASSOCIATES, LLP
,7oo Kraft Drive,Suite taco,Blacksburg,VA 24060 SAMPLING STATION
SS-01
Scale: NTS
EXIST. 12' WATER MAIN
RESTRAINED MECHANICAL JOINT
FITTINGS PER THE PLANS
I L MIN. c7'5:
1 c ' I
6' 9'
MIN. MIN.
SAWCUT AND BEVEL
EXISTING WATER MAIN
(4) 3/4' DIA STAINLESS STEEL
12' MIN. THREADED ROD (TYP)
ANCHORED IN CONCRETE
NOTES
I. CONCRETE THRUST COLLAR DIMENSION, L, SHALL BE EQUAL WIDTH AND HEIGHT,
CENTERED AROUND EXISTING PIPE, AND IN ACCORDANCE WITH TABLE I BELOW.
2. EMBED FOUR THREADED RODS A MINIMUM OF 9 INCHES INTO CURED
4000 PSI CONCRETE WITH HILTI HIT-HY /50 MAX SD INJECTABLE
MORTAR, IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
3. TEST PRESSURE - 300 PSI
T ABLE /
PIPE DIAMETER, L. VOL
INCH FT CY
6INCH 5 I
12 INCH 9 3
lijim sit ja
WHITMAN, REQUARDT Drawing No.
& ASSOCIATES, LLP
1700 Kraft Drive.Suite l=oo,Blacksburg.VA=.�� CONCRETE THRUST COLLAR
TC-01
Scale: NTS
N:\46601-014\CADD\Civil\DETAILS\Concrete thrust collar detail.dwg Mar 23, 2015 — 2:51 pm
•
45' MAX.
;>jIui_
MAX. 41
5' MAX
PLUG X11 J
11 is 4 ..--i ce`%
\.%i
FOR ALL BENDS FOR TEE OR WYE FITTINGS
WIDEN TRENCH TO
%
, z'y ;;;/�: i\�%i• ce AACCOMMODATE %%%��� /
IF' MIN. REQUIRED.
iiBEDDING AS
" iVrii% REQUIRED �•�II • 4
_
tP � _
•
45' MIN. 45PLUGiik06.i.v
MIN ��
T
SECTION 1 -1 a"° Tam SECTION 2-2
aze av {ter, cv.w. a•ro•
L H T L H 7
90 2.30 2.50*3.01 0.24
4'8 V 43 2.00 2.25 2.60 0.15 2.00 2.25 2.50 0.15
221/2 1.50 2.00 2.52 0.10
111/4 1.50 2.00 2.50 0.10
60 aes 3.15 3.21 0.45
4e 2.55 2.66 2.n 0.26
6' 221/2 1.66 2.16 2.89 0.13 3.16 2.w Zee 0.32
111/4 1.66 2.16 2.870.13
90 4.83 3.63 3.42• 0.63
10•a ir 221/2 2.333.33 2.5°56 Lee 00..24 3.53 4,00 zee au
111/4 1.63 2.33 2.84 0.16
90
16• 45
22 1/2
11 1/4 _
90
15'
1 1/4t
THE FOLLOWING SHALL BE USED WHEN
TEST PRESSURE=300 PSI
PIPE DEGREE BEND DIMENSIONS
SIZE OF BEND (FEET)
L H T
6" 45 3.53.52
1. USE 2500 psi CONCRETE
2. NO CONCRETE SHALL BE POURED ON ANY PART OF THE JOINT.
3. THE ENGINEER SHALL BE RESPONSIBLE TO VERIFY THE TYPE AND SIZE OF ALL THRUST BLOCKS.
REVISION May 2009 DRAWING NUMBER:
DATE: CONCRETE THRUST BLOCKS
SCALE: NOT TO WATER 2
SCALE RIVANNA WATER AND SEWER AUTHORITY
A
PLACE 5' CONCRETE "WITNESS" POST IN
REMOTE AREAS AS DIRECTED. MARKER
LOCATION MAY BE SUBJECT TO HIGHWAY
oo DEPARTMENT APPROVAL.
FINISHED GRADE
,,,,„
1 %, err
12 MIN
I 1`//,%/'- --
_
II
II
z - II /—ADJUSTABLE VALVE BOX W/ LID
N 11 BINGHAM & TAYLOR FIG. NO. 4905
2.4_ (SCREW TYPE) OR APPROVED
z N _J___ u - - EQUAL
N I I �
_J _g_ _ _ _ .. _
M.J. GATE VALVE
d = ] C = }
WATER { _ ] C = } LINE3
d •
d : ] �n I I _ ]„
_� . , _
2500 P.S.I. 0
CONCRETE b' a 2'x 2' BEARING AREA.
THRUST BLOCK
, • . Q
. c.
n
a •
c
NOTE : IN REMOTE AREAS, VALVE BOXES SHALL EXTEND SIX (6) INCHES ABOVE GRADE.
REVISION
May 2009 DRAWING NUMBER:
DATE: TYPICAL GATE VALVE
SCALE: NOT TO WATER 6
SCALE RIVANNA WATER AND SEWER AUTHORITY
4
REINFORCEMENT TO BE NO. 3 C-1" `0'-1"
STEEL RODS,SECURLY HELD
IN CAGES BY SPOT WELDED
NO. 4 WIRES ATACHED TO ALL
BARS APPROXIMATELY 8" FROM
EACH END TO INSURE PROPER
PLACING 0'-4"
1111
NO. 3 STEEL RODS
4 PLACES
36"
GROUND LINE
1:64`: ILtr' 'OI Olwi
24" 3000 PSI CONCRETE
11
REVISION REVISION Feb.2009 DRAWING NUMBER:
DATE: CONCRETE VALVE MARKER
SCALE: NOT TO WATER 12
SCALE RIVANNA WATER AND SEWER AUTHORITY
•
1" COMPRESSION x 3/4" MALE PIPE COUPLING
OR APPROVED EQUAL
1��X10: Q IO��1S
1;
TYPCOPKE " "
SOFT PER
FOR USE ON ATTACHED SINGLE FAMILY
RESIDENTIAL SERVICES OR DUAL RESIDENTIAL
'.� AND IRRIGATION SERVICES.
HZ
1"xt"x1" TEE
or
EI 0 (f) MM.
11111/7
NO SWEATED FITTINGS
DUAL SERVICE
1" COMPRESSION x 3/4" MALE PIPE COUPLING
OR APPROVED EQUAL
1" TYPE "K"
SOFT COPPER .
i IE,NIDI Q II� �S
FOR USE ON DETACHED SINGLE FAMILY
RESIDENTIAL SERVICE WHERE AN IRRIGATION
-C METER IS NOT PROVIDED.
SINGLE SERVICE R
NOTE:
1) SADDLES SHALL BE USED ON PVC PIPE.
i----CAST IRON LID
FINISHED GRADE
VaiggINEnt±: 1= =II.II f ' 1. 11,
I. 10"--15"-\ tit
LLOCKWING Ill METER
BALL
i.1 BOX
VALVE =11 _
(INLETUE '
36" MIN.
OUTLET) I�f �, 1 COPPERSETTER
I I �_-
1/4 BEND COUPLING 111
Wr •�'�II(IF REWIRED) ' A 1"\
�� --"" METER
'� e
t;
BRICK AS
NECESSARY
CORPORATION STOP
TYPICAL SERVICE LATERAL INSTALLATION
N TS
FIG. W-6
TD-9 ACSA W-6
a
.
N
4-
w O
a. I- a I-2
FM u ir, „, E-
i� : 1
leilir
k/t!j •j is •0.01 p .
k�;%; ;s.`. 11.010• W 0
1 ? r to . -, ,,... 0.001 z D
>..., 00001 0
i •:;�,`i.. 00110. Q a
•.- 0.004 0 _w
S• .�4i 1 �1,uv�j 1� ,,,111` Hi E
i 11111
e 0
,;,..: 1
O
.....-- ti w
J
CC
ft•„- til Q
min 2
i w
CO
J
Q
2
t----y i 1
-:, i
. m
. ia z
i W. 1 .s• .
''''.....7". ..r..".”. W L
P
•
0 z
0 Y V B
• 351 2
i z 1 1
:I
Modified Mud Trap Notes:
1) Drainage Area = 2.6 Acres.
2) Wet Storage Area:
a) Depth =4 Feet
b) Side slopes= 2:1
3) Modified traps shall not be used in areas where rock or some other hard surface prevents the full and
uniform depth anchoring of the barrier.
4) An effort shall be made to locate the barrier at least 5 to 7 feet beyond the base of slopes with grades
greater than 7%.
5) Wire fence reinforcement for silt fence shall be a minimum of 14 gauge and shall have a maximum mesh
spacing of 6 inches.
6) The wire shall extend a minimum 4 inches into the ground and must be fastened securely to the upslope
side of the posts using heavy duty wire staples at least one inch long, tie wires or hog rings.
7) If wooden stakes are utilized for modified mud trap construction, they must have a minimum diameter of
3 inches when oak is used and 5 inches when pine is used. Wooden stakes must have a minimum
length of 5 feet.
8) If steel posts (standard "U" or"T" section) are utilized for the modified mud trap construction, they must
have a minimum weight of 1.33 pounds per linear foot and shall have a minimum length of 5 feet.
9) Support posts or stakes for this type of application shall be placed a Maximum 10-feet apart(see Plate
3.05-1)except within the wet storage area. The wet storage area shall have the posts or stakes placed
a Maximum 3-feet apart for added support.
10)Silt fence shall conform to the construction specifications for"extra strength"found in table 3.05-B and
shall be cut from a continuous roll to avoid joints.
11)The fabric shall be entrenched a minimum 8" in depth and back filled with clean soil. The soil shall be
compacted to 95 % over the filter fabric.
12)The height of the silt fence shall be a minimum of 34 inches above the original ground and shall not
exceed 48 inches above ground elevation.
13)The outlet for the modified mud trap shall consist of a stone section of the wire—supported silt fence
located at the low point or point of concentration for storm flows. For drainage areas from 1 to 3 acres,
the measure shall consist of the wire-supported silt fence installed with an opening from 4 to 8 feet wide
located in the low point or point of concentration for storm flows. The opening shall have a combination
of course aggregate and riprap installed to provide for filtering/detention as well as outlet stability. The
smaller stone shall be VDOT#3, #357 or#5 Course Aggregate (smaller stone sizes will enhance filter
efficiency) and riprap shall be "Class I." Filter cloth which meets the physical requirements noted in Std.
& Spec. 3.19, RIPRAP shall be placed at the stone-soil interface to act as a "Separator." The crest of
the stone outlet must be at least 1.0 foot below the top of the Wire-supported silt fence to ensure that the
flow will travel over the stone and not over the fence. The outlet shall be configured as noted in Plate
3.13-2.
14)Maintenance:
a) Silt fence shall be inspected immediately after each rainfall and at least daily during prolonged
rainfall. Any required repairs shall be made immediately.
b) Close attention shall be paid to the repair of damaged silt fence resulting from end runs and
undercutting.
c) Should the fabric on a silt fence decompose or become ineffective prior to the end of the expected
usable life and the barrier is still necessary, the fabric shall be replaced promptly.
d) Sediment shall be removed and the trap restored to its original dimensions when the sediment has
accumulated to one half of the design volume of the wet storage or eminent failure is evident.
Sediment removal from the area shall be deposited in a suitable area and in such a manner that it
will not erode and cause sedimentation problems.
e) Stone shall be regularly checked to ensure that filtration performance is maintained. Stone choked
with sediment shall be removed and cleaned or replaced.
f) The structure shall be checked regularly to ensure that it is structurally sound and has not been
damaged by erosion or construction equipment. The height of the stone outlet shall be checked to
ensure that its center is at least 1 foot below the top of the fence.
g) Temporary structures shall be removed when they have served their useful purpose, but not before
upslope area has been permanently stabilized.
ALBEMARLE COUNTY MODIFIED MUD TRAP DETAIL (MMT), 2 of 2
r ''
-"41111111%147/
CV Z
CX
O
`� '2, ,-,..,„ El L2114, = LL,
. ( TY
"to 'N4lhalleil
'4 b- 'f i( w-,w
`_"Ar ___,,, iii, w,, wiliiip
CL If/
o0* , \,,,, (Y w
-4-77 . .. - 4011111s, .
41 116 Ak VAinras' .._ .
W 4%iiii.._ e'-,,,,, --,,*,,
fx
co,
LU v
co
N
I I d.
Q
rm
OZ*
Q
opumiiiii %oil
1gi‘iii 1
0
z
O
^Op- a
W
M
N
O CO r
W
U
t
4W
IX
0
Z N. .8 =