HomeMy WebLinkAboutSDP201600025 Review Comments Initial Site Plan 2016-06-09 (2)Christopher Perez
From: Victoria Fort <vfort@rivanna.org>
Sent: Wednesday, June 08, 2016 5:35 PM
To: Christopher Perez
Cc: Alex Morrison; Adam Long (adam@collins-engineering.com); 'Scott Collins' (scott@collins-
engineering.com)
Subject: SDP201600025 Briarwood Recreational Area - Initial Site Plan
Chris,
RWSA has reviewed the initial site plan for the Briarwood Recreational Area as prepared by Collins Engineering and
dated 4/25/2016 and has the following comment:
1. Show the existing RWSA 14" cast iron water main throughout the entire project area (currently ends at the
property line between TMP 32G-1 and TMP 32E -1A).
2. The western boundary of TMP 32G-1 does not match RWSA records. Please confirm the location of the property
line and whether the RWSA 14" water main continues onto the property from TMP 32E -1A (owned by RWSA).
3. No grading will be allowed on RWSA property (see above comment). If possible, grading over the water main
should be avoided to minimize impacts to the high pressure main.
4. If grading over the RWSA water main cannot be avoided, grading shall not cause cover over the water line to
exceed 8' or be reduced to less than 3.5'. Care shall be taken during grading to protect the existing main.
5. The proposed drainage Swale adjacent to the RWSA water main should be moved away from the water main
(min 10' separation).
Let me know if you have any questions.
Thanks a lot,
Victoria
Victoria Fort, P.E.
Rivanna Water and Sewer Authority
695 Moores Creek Lane
Charlottesville, VA 22902
(P): (434) 977-2970 ext. 205
(F): (434) 295-1146