HomeMy WebLinkAboutSDP201600069 Review Comments Major Amendment, Final Site Plan 2017-03-22Phone 434-296-5832 County of Albemarle Department of Community Development 401 McIntire Road, Charlottesville, VA, 22902 Memorandum To: Craig Kotarski (craig.kotarski(a�timmons.com) From: Sarah Baldwin � - Division: Planning Date: March 22, 2017 -Revision Subject: SDP 201600069 Woodbrook Elementary Addition -Major Fax 434-972-41 ?6 The County of Albemarle Planning Division will recommend approval of the plan referenced above once the following comments have been satisfactorily addressed (The following comments are those that have been identified at this time. Additional comments or conditions may be added or eliminated based on further review.): [Each comment is preceded by the applicable reference, which is to the Subdivision/Zoning Ordinances unless otherwise specified.] I i=t the Major Site Plan (SDP1996-28in a "Previous Site Plans" notes. Revision acknowledged. 12.5.20,k,l)] Existing sev✓er an;1 drainage facilities; Proposed setver and drainage Fristing and proposed utilities. Verify that all existing and P C ; � F>,- < r t r h, .°: n. Provide their o.vner, deed hook and l.age n!irnber iif applicak�lr ! Revision Acknowledged. [32.5.2(n)] Existing and proposed improvements. Please provide a breakdown of the additional square footage of structures on the front page notes and provide the square footage on subsequent sheets. Clarify the height of the additions. Revision 2: Are all proposed buildings (including the gym) 19' in height? Please provide square footages for individual buildings. Additionally, has the square footage total changed? Please confirm that the "art space" has been removed and the "stage/dining area" expanded with appropriate square footage. 4. [32.5.2(n)) Existing and proposed improvements. Provide the ioc tion of a; iy 1.,;,u-,osed outcu;,r lighting including b!lilding mounted lid hts. All outdoor lighting shall comply with the requirements of section 4.17 Revision Acknowledged. [32.6.2(k) & 4.17] Outdoor lighting. If any external lighting fixtures are proposed, provide the (;.amen level of each proposed fixture Revision Acknowledged. 6. [32.6.2(k) 8. 4.17] Outdoor lighting. if an exterior lighting fixture is proposed, provide the following standard lighting note: `Each outdoor luminaire equipped with a lamp that emits 3,000 ormare initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to reflect light away fron) adjoining residential districts and away from adjacent roads. The spillover of lighting from luminaires onto public is I I I I- 4ial or rural areas zoning districts shall not exceed one-half foot-candle. Revision Acknowledged. 7. [32.7.9.4(b] Existing I r(:es.. Lon ervaticn Area The plan shows multir)le "existing vegetation areas"along the property lines adjacent to residerti: is required to be approved by the agent to ertisure the trees rem<:.: Revision Acknowledged. 8. [32.7.9.7] Screening. The screening/buffer along the proposed parking lot is inadequate. A minimum of 20 foot depth planting strip/vegetation should be provided containing staggered evergreens 15 feet on center is required. It is suggested that the buffer/screening be above this amount due to the proximity of the parking areas to the residential lots. Alternative screening types may be proposed and approved by the agent. Partially addressed. Revision 2. Continue landscaping along the 7 parking spaces moved to the front of the bus loop. It is also suggested that evergreens be continued within the existing buffer area adjacent to the existing parking area adjacent to residential. [Corrrment]. Playground equipment, playing fields and paved play areas all seem to be removed, except for the ball field. At a field visit, these is recommended that sorne type ,)F outdoor recreation area be maintained; Revision Acknowledged. 10. [Comment] This site plan amendment cannot be approved until ACSA grants final approval of water and sewer plans. Revison 2. Additional comments from Engineering and Fire/Rescue are attached. ACSA and VDOT comments will be forwarded when received. Revision 2 Comments: 11. [4.17.4(b)1] Lighting Standards. The spillover from lighting cannot exceed .5 foot candles adjacent to public roads or residential property. Provide spillover adjacent to the bus loop and Idlewood Drive. 12. 32.6.2(k) & 4.17] Outdoor lighting. No lighting sheet beyond the stage/dining area for the rest of the property (i.e., the gym or additional classroom space) was shown. Please provide lighting information for the remainder of the property. Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office. The Code may be found on the County Attorney's website which may be found under "Departments and Services" at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within six (6) months after the date of this letter the application shall be deemed to have been voluntarily withdrawn by the developer. Please contact Sarah Baldwin in the Planning Division by using sbaldwin(a-)-albemarle.org or 434-296- 5832 ext. 3313 for further information. Review Comments for SDP201600069 MajorAmendment Project Name: I Woodbrook Elementary School Addition - Major Date Completed: Tuesday: March 21.2017 Department/Division1Agency: Review Status: Reviewer:BobbyJocz _E1CDD Engineering Requested Changes [;omments for Plans Uated 2115!2017 1)Existing water line easement is insufficient in width if to be used as easement for future stormwater sewer. All drainage easements must be a minimum 20' wide. Please correct. [From Rev 1] 2)Ensure proposed slopes steeper than 3:1 must have low maintenance (not grass) ground cover specified on the plan {Design Manual, Section 8). Low maintenance cover should extend over entire slope area- Please correct_ [From Rev 1] 3)Provide detail for VDOT standard CG -11 as referenced for fire access road intersection- 4)Provide date of topography survey/field verification- All topography should be at least field verified within the last year. 5)Sheet C1-3 has no information on it. Please remove if not utilized. 6)VDOT approval must be provided for any plan effecting the ROW_ This includes the fire department access road tying into Idlewood Drive, and the section of drainage pipe planned on Brookmere Drive. 7)Storm stormsewer profiles are missing for structures-, SWM B — 204, 200 — 204, SWM B — 213, and 211 — 204- Please provide, 8)Provide entire extent of existing and proposed stormsewer pipes in profiles and calculations. Review Comments for SDP2O16OOO69 !MajorAmendment Project !*lame: Woodbrook Elementary School Addition - Major Date Completed: Saturday; February 25; 2017 Department/DivisionfAgency: Review Status: Reviewer: Robbie Gilmer Fire Rescue Requested Changes 0 Based on plans dated 215117. 1. Relocate the FDC on the gym so that its located across from the hydrant_ 2. Relocate the FDC on the rear classrooms so that its located on the north east corner and visible from the hydrant. • •• do • do 608 Preston Avenue Suite 200 P 434.295.5624 TI M M O N S GROUP Charlottesville,VA 22903 F 434.295.8317 YOUR VISION ACHIEVED THROUGH OURS. www.timmons.com February 16, 2017 Albemarle County Attn: Alexander J. Morrison, P.E. Albemarle County Service Authority 168 Spotnap Road Charlottesville, VA 2291 I RE: Site Plan Technical Review: Woodbrook Elementary School Add.- Major Site Plan Amendment SDP-2016-00069 Review#I We have reviewed all of your comments from January 5, 2017 and made the necessary revisions. Please find our responses to the comments below in bold lettering. The below underlined items apply to this site. 1. This site plan is within the Authority's jurisdictional area for: a. Water and sewer b. Water only c. Water only to existing structure d. Limited service 2. A 6-inch water line is located approximately(on site)distant. 3. Fire flow from, nearest public hydrant, located distant from this site plan, is Gpm +20 psi residual. 4. An (Unknown-Private) inch sewer line is located approximately(on site) distant. 5. An industrial Waste Ordinance survey form must be completed. 6. No improvements or obstructions shall be placed within or future easements. 7. And plans are currently under review 8. And plans have been received and approved. 9. No plans are required 10. Final water and sewer plans are required for our review and approval prior to granting final site plan approval. I I. Final site plan may/may not be signed. 12. RWSA approval for water and/or sewer connections. 13. City of Charlottesville approval for sewer. Comments: • Water construction plan review by the ACSA is required at this stage. Acknowledged. • RWSA Wastewater Capacity Certification required if the overall development will produce more than 40,000 GPD in wastewater flow. This project will not result in an increase greater than 40,000 gpd. CIVIL ENGINEERING I ENVIRONMENTAL I SURVEYING I GIS I LANDSCAPE ARCHITECTURE I CONSTRUCTION SERVICES More need to be saved. Replacement trees need to be evergreen to better screen the ugly bus parking lot from view. Evergreen and deciduous trees have been added along Idlewood Drive to screen the bus loop. See sheet L 1.0. 3. Inadequate screening of school parking lots/bus parking from view of residents on Brentwood and Idlewood. The few trees included in site plan are trees that lose their leaves. Thus, no screening is available for significant periods of time during the year. More evergreens/bushes are needed. Evergreen and deciduous trees have been added along Idlewood Drive to screen the bus loop. See sheet L 1.0. 4. Many trees were planted in memory of school children and staff who passed away. They need to be left standing or replaced with appropriate re commemoration. Commemorative trees and identifying markers will be cataloged and preserved or replaced as required to accommodate construction. 5. No screening of school from houses #2907 and 2009 (along gym side of school). Screening is needed to keep lights from shining into homes and to hide large (unattractive)gym from view. Trees, bushes, including evergreens, are needed. A vegetative buffer of mostly evergreen trees and shrubs has been added around the proposed playground in order to better screen nearby homes on Idlewood Drive from the school grounds and building. 6. No plan for replacing swings and basketball court are seen on plans. These are heavily used by entire Rio/29 community. Per county comprehensive plan, Neighborhood 2 (Woodbrook area) has no green space other than the school grounds. Residents are directed to Meadow Creek Trail and Penn Park...too far for many in the area. There are no basketball courts/play ground equipment from Woodbrook to Dunlora. Many in community drive here to play. One consistent group coming here is an Hispanic group of men to play soccer on Sunday morning. They bring their children and current configuration of playground allows them to play and supervise their children. This loss is a major community loss. The plan has been revised to specify a basketball court with both standard I 0' goals, as well as an 8' and 9' goal. The existing play equipment will be relocated to the indicated area adjacent to the proposed bus loop. 7. Presentations to Woodbrook neighbors shows the gym reconfigured to make it appear less massive from the street view. That plan is not clear on the school site plans or was it omitted? These design features remain. Architectural elevations will be included within the separate, building permit documents. We have included 16 copies of the plans for your review with this submittal. If you have any questions or comments, please feel free to give me a call at 434.327.1690. Sincerely, Clint Shifflett, PE Project Engineer • Show the existing water meter and add abandonment notes. Existing water meter and abandonment notes have been added to the plans. See Sheet C2.3. • Existing and proposed fixture counts will be required to size the water meter. Fixture counts will be provided with the following submittal. The fixture counts are still being finalized by the architect. • RWSA does not have utilities in the immediate vicinity of the school; however, if the expansion will increase sewage flow by 40,000 gallons per day or more, a flow capacity certification will be required by RWSA prior to final approval. This project will not result in an increase greater than 40,000 gpd. We have included the revised site plan to for your review. If you have any questions or comments, please feel free to give me a call at 434.327.1690. Sincerely, (1. Clint Shifflett, PE Project Engineer •••*O.. El 'R 608 Preston Avenue Suite 200 P 434.295.5624 TIM M O N S GROUP Charlottesville,VA 22903 F 434.295.8317 YOUR VISION ACHIEVED THROUGH OURS. www.timmons.com February 16 2017 Rivanna Water and Sewer Authority Attn: Victoria Fort, PE 695 Moores Creek Lane Charlottesville,VA 22902 RE:Woodbrook Elementary School Add.- Major Site Plan Amendment SDP-2016-00069 Review#I We have reviewed all of your comments from December 21, 2016 and made the necessary revisions. Please find our responses to the comments below in bold lettering. 1. I saw in the November 30, 2016 Site Review Memo that there is a site plan under review for the Woodbrook ES Addition. RWSA does not have utilities in the immediate vicinity of the school; however, if the expansion will increase sewerage flow by 40,000 gallons per day or more, a flow capacity certification will be required by RWSA prior to final approval. This expansion will not result in a sewerage flow increase greater than 40,000 gpd• We have submitted the revised site plan for your review. If you have any questions or comments, please feel free to give me a call at 434.327.1690. Sincerely, Clint Shifflett, PE Project Engineer CIVIL ENGINEERING I ENVIRONMENTAL I SURVEYING I GIS I LANDSCAPE ARCHITECTURE I CONSTRUCTION SERVICES • • • • 608 Preston Avenue P 434.295.5624 Suite 200 F434.295.8317 TIMMONS GROUP Charlottesville,VA 22903 www.timmons.com YOUR VISION ACHIEVED THROUGH OURS. February 14, 2017 Commonwealth of VA Dept. of Transportation Attn: Adam Moore 1601 Orange Road Culpeper, VA 22701 RE:Woodbrook Elementary School Add. - Major Site Plan Amendment SDP-2016-00069 Review#I We have reviewed all of your comments from January 3, 2017 and made the necessary revisions. Please find our responses to the comments below in bold lettering. The Department of Transportation, Charlottesville Residency Transportation and Land Use Section, has reviewed the above reference plan as submitted by Timmons Group, dated 21 November 2016, and offers the following comment. • Will the proposed improvements coincide with increased enrollment? If so, provide updated traffic/trip information. Based on this information we may have traffic signal related comments. A traffic study has been conducted. We will email you the traffic study directly for your review. If you have any questions or comments, please feel free to give me a call at 434.327.1690. Sincerely, Clint Shifflett, PE Project Engineer CIVIL ENGINEERING I ENVIRONMENTAL I SURVEYING I GIS I LANDSCAPE ARCHITECTURE I CONSTRUCTION SERVICES . . ....a. AP • 608 Preston Avenue Suite 200 P 434.295.5624 TI M M O N S GROUP Charlottesville,VA 22903 F 434.295.8317 YOUR VISION ACHIEVED THROUGH OURS. www.timmons.com February 16, 2017 County of Albemarle Attn: Robbie Gilmer Fire Rescue 401 McIntire Road Charlottesville, VA 22902 RE:Woodbrook Elementary School Add.- Major Site Plan Amendment SDP-2016-00069 Review#I We have reviewed all of your comments from December 21, 2016 and made the necessary revisions. Please find our responses to the comments below in bold lettering. Comments for Plans Dated 11/21/2016 1. Please show a second means of access for fire department. Secondary access for the fire department has been shown. See Sheet C4.0. 2. Fire hydrant spacing shall be 400' per travel way for any new construction. Fire hydrant configuration has been updated. See Sheet C4.0. 3. The new Art Space doesn't have Fire Department access to within 150' of all the first floor, please provide Fire Department access. The new art space is no longer a part of this project. 4. Confirm if the school already has a FDC already. If so, please show on the plans. The existing school does not have an FDC. The additions will be sprinkled. FDC locations have been shown on the plans. See Sheet C4.0. 5. Confirm if the school already has a Knox box on location, if not please add a note requiring a Knox Box to be added. Our bollard detail has been updated to include reference to a knox box. 6. Fire Flow test required before final approval. Please attach a copy to the final plans. A fire flow test has been requested. 7. Please add No Parking Fire plans signs to the front loop and the bus loop. No parking signs have been added to both the front and bus loops. See Sheet C4.0. We have submitted the revised site plan for your review. If you have any questions or comments, please feel free to give me a call at 434.327.1690. Sincerely, e Clint Shifflett, PE Project Engineer CIVIL ENGINEERING I ENVIRONMENTAL I SURVEYING I GIS I LANDSCAPE ARCHITECTURE I CONSTRUCTION SERVICES • ' 608 Preston Avenue suite 200 P 434.295.5624 Till M O N S GROUP Charlottesville,VA 22903 F 434.295.8317 YOUR VISION ACHIEVED THROUGH OURS. www.timmons.com February I6, 2017 County of Albemarle Attn: Sarah Baldwin Department of Community Development 401 McIntire Road Charlottesville,VA 22902 RE:Woodbrook Elementary School Add.- Major Site Plan Amendment SDP-2016-00069 Review#1 We have reviewed all of your comments from January 3, 2017 and made the necessary revisions. Please find our responses to the comments below in bold lettering. The County of Albemarle Planning Division will recommend approval of the plan referenced above once the following comments have been satisfactorily addressed (The following comments are those that have been identified at this time.Additional comments or conditions may be added or eliminated based on further review.): [Each comment is preceded by the applicable reference, which is to the Subdivision/Zoning Ordinance unless otherwise specified.] 1. [Comment]. List the Major Site Plan(SPD I 996-28in a"Previous Site Plans" notes. Major Site plan has been added to the notes. See "Site Data" Sheet C1.0. 2. [32.5.2(j,k,1)] Existing sewer and drainage facilities; Proposed sewer and drainage facilities; Existing and proposed utilities. Verify that all existing and proposed easements are shown. Provide their owner, deed book and page number(if applicable). All existing and proposed easements have been shown. 3. [32.5.2(n)] Existing and proposed improvements. Please provide a breakdown of the additional 1 � square footage of structures on the front page notes and provide the square footage on 1 subsequent sheets. Clarify the height of the additions. 111 This information has been added to the plans. See "Site Data"Sheet C1.0. 4. [32.5.2(n)] Existing and proposed improvements. Provide the location of any proposed outdoor lighting including building mounted lights.All outdoor lighting shall comply with the requirements, y, of section 4.17. \�\h h I t� ,j A photometric plan has been provided. See Sheet L3.0. xLOS �� � 'v/ 5. [32.6.2(k) &4:17] Outdoor lighting. If any external lighting fixtures are proposed provide the sv lumen level of each proposed fixture. , This information has been provided. See Sheet L3.0. 6. [32.6.2(k) &4.17] Outdoor lighting. If an exterior lighting fixture is proposed provide the following standard lighting note: "Each outdoor luminaire equipped with a lamp that emits 3,000 or more initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to reflect light away from adjoining residential districts and away from adjacent roads. The spillover of CIVIL ENGINEERING I ENVIRONMENTAL I SURVEYING I GIS I LANDSCAPE ARCHITECTURE I CONSTRUCTION SERVICES lighting from luminaires onto public roads and property in residential or rural areas zoning districts shall not exceed one-half foot-candle." This note has been added to the plans. See Sheet L3.0. 7. [32.7.9.4(b)] Existing Trees...&Conservation Area.The plan shows multiple "existing vegetation areas" along the property lines adjacent to residential.A conservation checklist is required to be approved by the agent to ensure the trees remain. A signed conservation checklist has been provided. See sheet L2.0 8. [32.7.9.7] Screening. The screening/buffer along the proposed parking lot is inadequate.A minimum of 20 foot depth planting strip/vegetation should be provided containing staggered evergreens 15 feet on center is required. It is suggested that a buffer/screening be above this amount due to the proximity of the parking areas to residential lots.Alternative screening types may be proposed and approved by the agent. The buffer has been extended to screen the entire length of the parking lot from nearby residences where there is no existing vegetative buffer. The proposed buffer has also been adjusted to fill out a 20-foot-wide planting strip and the spacing between trees has been tightened to 15 feet on-center or less. 9. [Comment]. Playground equipment, playing fields and paved areas all seem to be removed, except for the ball field.At a field visit,these areas were being utilized. It is recommended that some type of outdoor recreation area be maintained. Additional outdoor recreation areas have been provided. See Sheet C4.0. 10. [Comment] This site plan amendment cannot be approved until ACSA grants final approval of water and sewer plans.Additional comments from Engineering, Fire/Rescue, VDOT,ACSA and inspections and the public are attached. Acknowledged. Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office. The Code may be found on the County Attorney's website which may be found under `Departments and Service" at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within sex (6) months after the date of this letter the application shall be deemed to have voluntarily withdrawn by the developer. Please contact Sarah Baldwin in the Planning Division by using sbaldwin@albemarle.ord or 434- 296-5832 ext. 3313 for further information. Audrey Kocher Comments: I. Loss of trees in front to the school entrance. I understand from school presentations to Woodbrook residents, several trees would be preserved. They are old and beautiful. Trees along the existing building facade at the front entrance are to be preserved. 2. All the trees planted along Idlewood Drive during the last addition will be destroyed. • • 0 * 608 Preston Avenue Suite 200 P 434.295.5624 TIM M O N S GROUP Charlottesville,VA 22903 F 434.295.8317 YOUR VISION ACHIEVED THROUGH OURS. www.timmons.com February 16, 2017 County of Albemarle Attn: Sarah Baldwin Department of Community Development 40I McIntire Road Charlottesville, VA 22902 RE:Woodbrook Elementary School Add.- Major Site Plan Amendment SDP-2016-00069 Review#I We have reviewed all of your comments from January 3, 2017 and made the necessary revisions. Please find our responses to the comments below in bold lettering. The County of Albemarle Planning Division will recommend approval of the plan referenced above once the following comments have been satisfactorily addressed (The following comments are those that have been identified at this time.Additional comments or conditions may be added or eliminated based on further review.): [Each comment is preceded by the applicable reference, which is to the Subdivision/Zoning Ordinance unless otherwise specified.] I. [Comment]. List the Major Site Plan(SPD I 996-28in a"Previous Site Plans" notes. Major Site plan has been added to the notes. See "Site Data" Sheet C1.0. 2. [32.5.2(j,k,l)] Existing sewer and drainage facilities; Proposed sewer and drainage facilities; Existing and proposed utilities.Verify that all existing and proposed easements are shown. Provide their owner, deed book and page number(if applicable). All existing and proposed easements have been shown. 3. [32.5.2(n)] Existing and proposed improvements. Please provide a breakdown of the additional square footage of structures on the front page notes and provide the square footage on subsequent sheets. Clarify the height of the additions. This information has been added to the plans. See "Site Data" Sheet C1.0. 4. [32.5.2(n)] Existing and proposed improvements. Provide the location of any proposed outdoor lighting including building mounted lights.All outdoor lighting shall comply with the requirements of section 4.17. A photometric plan has been provided. See Sheet L3.0. 5. [32.6.2(k) &4.17] Outdoor lighting. If any external lighting fixtures are proposed provide the lumen level of each proposed fixture. This information has been provided. See Sheet L3.0. 6. [32.6.2(k) &4.17] Outdoor lighting. If an exterior lighting fixture is proposed provide the following standard lighting note: "Each outdoor luminaire equipped with a lamp that emits 3,000 or more initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to reflect light away from adjoining residential districts and away from adjacent roads.The spillover of CIVIL ENGINEERING I ENVIRONMENTAL I SURVEYING I GIS I LANDSCAPE ARCHITECTURE I CONSTRUCTION SERVICES lighting from luminaires onto public roads and property in residential or rural areas zoning districts shall not exceed one-half foot-candle." This note has been added to the plans. See Sheet L3.0. 7. [32.7.9.4(b)] Existing Trees...&Conservation Area.The plan shows multiple "existing vegetation areas" along the property lines adjacent to residential.A conservation checklist is required to be approved by the agent to ensure the trees remain. A signed conservation checklist has been provided. See sheet L2.0 8. [32.7.9.7] Screening. The screening/buffer along the proposed parking lot is inadequate.A minimum of 20 foot depth planting strip/vegetation should be provided containing staggered evergreens 15 feet on center is required. It is suggested that a buffer/screening be above this amount due to the proximity of the parking areas to residential lots.Alternative screening types may be proposed and approved by the agent. The buffer has been extended to screen the entire length of the parking lot from nearby residences where there is no existing vegetative buffer. The proposed buffer has also been adjusted to fill out a 20-foot-wide planting strip and the spacing between trees has been tightened to 15 feet on-center or less. 9. [Comment]. Playground equipment, playing fields and paved areas all seem to be removed, except for the ball field.At a field visit,these areas were being utilized. It is recommended that some type of outdoor recreation area be maintained. Additional outdoor recreation areas have been provided. See Sheet C4.0. 10. [Comment] This site plan amendment cannot be approved until ACSA grants final approval of water and sewer plans.Additional comments from Engineering, Fire/Rescue, VDOT,ACSA and inspections and the public are attached. Acknowledged. Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office. The Code may be found on the County Attorney's website which may be found under `Departments and Service" at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within sex (6) months after the date of this letter the application shall be deemed to have voluntarily withdrawn by the developer. Please contact Sarah Baldwin in the Planning Division by using sbaldwin@albemarle.ord or 434- 296-5832 ext. 3313 for further information. Audrey Kocher Comments: I. Loss of trees in front to the school entrance. I understand from school presentations to Woodbrook residents, several trees would be preserved. They are old and beautiful. Trees along the existing building façade at the front entrance are to be preserved. 2. All the trees planted along Idlewood Drive during the last addition will be destroyed. More need to be saved. Replacement trees need to be evergreen to better screen the ugly bus parking lot from view. Evergreen and deciduous trees have been added along Idlewood Drive to screen the bus loop. See sheet L I.O. 3. Inadequate screening of school parking lots/bus parking from view of residents on Brentwood and Idlewood. The few trees included in site plan are trees that lose their leaves. Thus, no screening is available for significant periods of time during the year. More evergreens/bushes are needed. Evergreen and deciduous trees have been added along Idlewood Drive to screen the bus loop. See sheet L 1.0. 4. Many trees were planted in memory of school children and staff who passed away. They need to be left standing or replaced with appropriate re commemoration. Commemorative trees and identifying markers will be cataloged and preserved or replaced as required to accommodate construction. 5. No screening of school from houses #2907 and 2009 (along gym side of school). Screening is needed to keep lights from shining into homes and to hide large (unattractive)gym from view. Trees, bushes, including evergreens, are needed. A vegetative buffer of mostly evergreen trees and shrubs has been added around the proposed playground in order to better screen nearby homes on Idlewood Drive from the school grounds and building. 6. No plan for replacing swings and basketball court are seen on plans. These are heavily used by entire Rio/29 community. Per county comprehensive plan, Neighborhood 2 (Woodbrook area) has no green space other than the school grounds. Residents are directed to Meadow Creek Trail and Penn Park...too far for many in the area. There are no basketball courts/play ground equipment from Woodbrook to Dunlora. Many in community drive here to play. One consistent group coming here is an Hispanic group of men to play soccer on Sunday morning. They bring their children and current configuration of playground allows them to play and supervise their children. This loss is a major community loss. The plan has been revised to specify a basketball court with both standard 10' goals, as well as an 8' and 9' goal. The existing play equipment will be relocated to the indicated area adjacent to the proposed bus loop. 7. Presentations to Woodbrook neighbors shows the gym reconfigured to make it appear less massive from the street view. That plan is not clear on the school site plans or was it omitted? These design features remain. Architectural elevations will be included within the separate, building permit documents. We have included 16 copies of the plans for your review with this submittal. If you have any questions or comments, please feel free to give me a call at 434.327.1690. Sincerely, Clint Shifflett, PE Project Engineer • • • • 608 Preston Avenue Suite 200 P 434.295.5624 TIM M O N S GROUP Charlottesville,VA 22903 F 434.295.8317 YOUR VISION ACHIEVED THROUGH OURS. www.timmons.com February 16, 2017 Albemarle County Attn: Alexander J. Morrison, P.E. Albemarle County Service Authority 168 Spotnap Road Charlottesville, VA 2291 I RE: Site Plan Technical Review: Woodbrook Elementary School Add.- Major Site Plan Amendment SDP-2016-00069 Review#1 We have reviewed all of your comments from January 5, 2017 and made the necessary revisions. Please find our responses to the comments below in bold lettering. The below underlined items apply to this site. I. This site plan is within the Authority's jurisdictional area for: a. Water and sewer b. Water only c. Water only to existing structure d. Limited service 2. A 6-inch water line is located approximately(on site)distant. 3. Fire flow from, nearest public hydrant, located distant from this site plan, is Gpm +20 psi residual. 4. An (Unknown-Private) inch sewer line is located approximately(on site) distant. 5. An industrial Waste Ordinance survey form must be completed. 6. No improvements or obstructions shall be placed within or future easements. 7. And plans are currently under review 8. And plans have been received and approved. 9. No plans are required 10. Final water and sewer plans are required for our review and approval prior to granting final site plan approval. I I. Final site plan may/may not be signed. 12. RWSA approval for water and/or sewer connections. 13. City of Charlottesville approval for sewer. Comments: • Water construction plan review by the ACSA is required at this stage. Acknowledged. • RWSA Wastewater Capacity Certification required if the overall development will produce more than 40,000 GPD in wastewater flow. This project will not result in an increase greater than 40,000 gpd. CIVIL ENGINEERING I ENVIRONMENTAL I SURVEYING I GIS I LANDSCAPE ARCHITECTURE I CONSTRUCTION SERVICES • Show the existing water meter and add abandonment notes. Existing water meter and abandonment notes have been added to the plans. See Sheet C2.3. • Existing and proposed fixture counts will be required to size the water meter. Fixture counts will be provided with the following submittal. The fixture counts are still being finalized by the architect. • RWSA does not have utilities in the immediate vicinity of the school; however, if the expansion will increase sewage flow by 40,000 gallons per day or more, a flow capacity certification will be required by RWSA prior to final approval. This project will not result in an increase greater than 40,000 gpd. We have included the revised site plan to for your review. If you have any questions or comments, please feel free to give me a call at 434.327.1690. Sincerely, e Clint Shifflett, PE Project Engineer • • 608 Preston Avenue P 434.295.5624 Suite 200 F 434.295.8317 T I M M O N S GROUP Charlottesville,VA 22903 www,timmons.com YOUR VISION ACHIEVED THROUGH OURS. February 14, 2017 Commonwealth of VA Dept. of Transportation Attn: Adam Moore 1601 Orange Road Culpeper,VA 22701 RE:Woodbrook Elementary School Add. - Major Site Plan Amendment SDP-2016-00069 Review#I We have reviewed all of your comments from January 3, 2017 and made the necessary revisions. Please find our responses to the comments below in bold lettering. The Department of Transportation, Charlottesville Residency Transportation and Land Use Section, has reviewed the above reference plan as submitted by Timmons Group, dated 21 November 2016, and offers the following comment. • Will the proposed improvements coincide with increased enrollment? If so, provide updated traffic/trip information. Based on this information we may have traffic signal related comments. A traffic study has been conducted. We will email you the traffic study directly for your review. If you have any questions or comments, please feel free to give me a call at 434.327.1690. Sincerely, Clint Shifflett, PE Project Engineer CIVIL ENGINEERING I ENVIRONMENTAL I SURVEYING I GIS I LANDSCAPE ARCHITECTURE I CONSTRUCTION SERVICES * "•**off lb • 608 Preston Avenue Suite 200 P 434.295.5624 TIM M O N S GROUP Charlottesville,VA 22903 F 434.295.8317 YOUR VISION ACHIEVED THROUGH OURS. www.timmons.com February 16 2017 Rivanna Water and Sewer Authority Attn: Victoria Fort, PE 695 Moores Creek Lane Charlottesville,VA 22902 RE:Woodbrook Elementary School Add.- Major Site Plan Amendment SDP-20I6-00069 Review#I We have reviewed all of your comments from December 2 I, 2016 and made the necessary revisions. Please find our responses to the comments below in bold lettering. I. I saw in the November 30, 2016 Site Review Memo that there is a site plan under review for the Woodbrook ES Addition. RWSA does not have utilities in the immediate vicinity of the school; however, if the expansion will increase sewerage flow by 40,000 gallons per day or more, a flow capacity certification will be required by RWSA prior to final approval. This expansion will not result in a sewerage flow increase greater than 40,000 gPd• We have submitted the revised site plan for your review. If you have any questions or comments, please feel free to give me a call at 434.327.1690. Sincerely, e Clint Shifflett, PE Project Engineer CIVIL ENGINEERING I ENVIRONMENTAL I SURVEYING I GIS I LANDSCAPE ARCHITECTURE I CONSTRUCTION SERVICES .40110400 • 608 Preston Avenue Suite 200 P 434.295.5624 TIM M O N S GROUP Charlottesville,VA 22903 F 434.295.8317 YOUR VISION ACHIEVED THROUGH OURS. www.timmons.com February 16, 2017 County of Albemarle Attn: Robbie Gilmer Fire Rescue 401 McIntire Road Charlottesville,VA 22902 RE:Woodbrook Elementary School Add.- Major Site Plan Amendment SDP-2016-00069 Review#I We have reviewed all of your comments from December 21, 2016 and made the necessary revisions. Please find our responses to the comments below in bold lettering. Comments for Plans Dated 11/21/2016 I. Please show a second means of access for fire department. Secondary access for the fire department has been shown. See Sheet C4.0. 2. Fire hydrant spacing shall be 400' per travel way for any new construction. Fire hydrant configuration has been updated. See Sheet C4.0. 3. The new Art Space doesn't have Fire Department access to within 150' of all the first floor, please provide Fire Department access. The new art space is no longer a part of this project. 4. Confirm if the school already has a FDC already. If so, please show on the plans. The existing school does not have an FDC. The additions will be sprinkled. FDC locations have been shown on the plans. See Sheet C4.0. 5. Confirm if the school already has a Knox box on location, if not please add a note requiring a Knox Box to be added. Our bollard detail has been updated to include reference to a knox box. 6. Fire Flow test required before final approval. Please attach a copy to the final plans. A fire flow test has been requested. 7. Please add No Parking Fire plans signs to the front loop and the bus loop. No parking signs have been added to both the front and bus loops. See Sheet C4.0. We have submitted the revised site plan for your review. If you have any questions or comments, please feel free to give me a call at 434.327.1690. Sincerely, Clint Shifflett, PE Project Engineer CIVIL ENGINEERING I ENVIRONMENTAL I SURVEYING I GIS I LANDSCAPE ARCHITECTURE I CONSTRUCTION SERVICES Phone 434-296-5832 County of Albemarle Department of Community Development 401 McIntire Road, Charlottesville, VA, 22902 Memorandum To: Craig Kotarski (craig.kotarski(a6timmons.com) From: Sarah Baldwin Division: Planning Date: January 5, 2017 Subject: SDP 201600069 Woodbrook Elementary Addition -Major Fax 434-972-4126 The County of Albemarle Planning Division will recommend approval of the plan referenced above once the following comments have been satisfactorily addressed (The following comments are those that have been identified at this time. Additional comments or conditions may be added or eliminated based on further review.): [Each comment is preceded by the applicable reference, which is to the Subdivision/Zoning Ordinances unless otherwise specified.] 1. [Comment]. List the Major Site Plan (SDP1996-28in a "Previous Site Plans" notes. 2. [32.5.26,k,Q] Existing sewer and drainage facilities; Proposed sewer and drainage facilities; Existing and proposed utilities. Verify that all existing and proposed easements are shown. Provide their owner, deed book and page number (if applicable). 3. [32.5.2(n)] Existing and proposed improvements. Please provide a breakdown of the additional square footage of structures on the front page notes and provide the square footage on subsequent sheets. Clarify the height of the additions. 4. [32.5.2(n)] Existing and proposed improvements. Provide the location of any proposed outdoor lighting including building mounted lights. All outdoor lighting shall comply with the requirements of section 4.17. 5. [32.6.2(k) & 4.17] Outdoor lighting. If any external lighting fixtures are proposed provide the lumen level of each proposed fixture. 6. [32.6.2(k) & 4.17] Outdoor lighting. If an exterior lighting fixture is proposed provide the following standard lighting note: "Each outdoor luminaire equipped with a lamp that emits 3,000 or more initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to reflect light away from adjoining residential districts and away from adjacent roads. The spillover of lighting from luminaires onto public roads and property in residential or rural areas zoning districts shall not exceed one-half foot-candle. " 7. [32.7.9.4(b] Existing Trees ... & Conservation Area. The plan shows multiple "existing vegetation areas" along the property lines adjacent to residential. A conservation checklist is required to be approved by the agent to ensure the trees remain. 8. [32.7.9.7] Screening. The screening/buffer along the proposed parking lot is inadequate. A minimum of 20 foot depth planting strip/vegetation should be provided containing staggered evergreens 15 feet on center is required. It is suggested that the buffer/screening be above this amount due to the proximity of the parking areas to the residential lots. Alternative screening types may be proposed and approved by the agent. 9. [Comment]. Playground equipment, playing fields and paved play areas all seem to be removed, except for the ball field. At a field visit, these areas were being utilized. It is recommended that some type of outdoor recreation area be maintained. 10. [Comment] This site plan amendment cannot be approved until ACSA grants final, approval of water and sewer plans. Additional comments from Engineering, Fire/Rescue, VDOT, ACSA and Inspections and the public are attached. Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office. The Code may be found on the County Attorney's website which may be found under "Departments and Services" at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within six (6) months after the date of this letter the application shall be deemed to have been voluntarily withdrawn by the developer. Please contact Sarah Baldwin in the Planning Division by using sbaldwin(abalbemarle.org or 434-296- 5832 ext. 3313 for further information. Short Review Comments Report for: SDP201600069 — Woodbrook Elementary School Addition - M. SubApplication Type: MajorAmendment Date Completed: 11/30/2016 Reviewer: Review Status: Reviews Comments: Date Completed Reviewer: Review Status: Reviews Comments: Jay Schlothauer Division: CDD Inspections Requested Changes Based on plans dated October 15, 2016. Rearrange the sidewalk at the barrier -free parking spaces so that all striped access aisles lead to curb cuts or the flush sidewalk. It must not be necessary for users of the barrier -free spaces to travel behind parked cars to access the sidewalk. 12/17/2016 Robbie Gilmer Division: Fire Rescue Requested Changes Based on plans dated 11/21/16. 1. Please show a second means of access for fire department. 2. Fire hydrant spacing shall be 400' per travel way for any new construction. 3. The new Art Space doesn't have Fire Department access to within 150' of all the first floor, Please provide Fire Department access. 4. Confirm if the school has a FDC already. If so, please show on the plans. 5. Confirm if the school already has a Knox box on location, if not please add a note requiring a Knox Box to be added. 6. Fire Flow test required before final approval. Please attach a copy to the final plans. 7. Please add No Parking Fire plans signs to the front loop and the bus loop. Date Completed: 12/21/2016 Reviewer: Bobby Jocz Division: CDD Engineering Review Status: See Recommendations Reviews Comments: Comments for Plans Dated 10/15/2016 1)The VSMP submittal will need to be approved before major amendment final approval [18-32.7.4.1]. The VSMP plan is currently under review. 2)The major amendment plan must not contain the erosion control plan or stormwater management plan. These must be separate documents, to be reviewed and bonded separately, and not part of zoning documents or zoning enforcement, or zoning letters of revision, or permanent land records, etc. they must be removed. 3)Expand Key to include annotations used throughout plan sheets. Many elements not identified including pavement hatching. 4)Remove dimensions from dumpster pad detail or match detail to proposed dumpster pad noted on site, the dimensions do not match. 5)The portion of stormsewer exiting the site from the northwest (structures 201-203), draining from SWM facility B will need to be included in a drainage easement. All drainage easements must be a minimum 20' wide. Required width: 10'+(pipe dia. or channel width) + 2'+ 2(depth-5'). The pipe, channel or structure must be within the center third of the easement [18.32, Design manual section 6]. Ensure no structures or trees will exist within easements. 6)Clarify if CG -7 curb will be used on the east side of the bus loop for access road to SWM facility B as it is used for access to the dumpster pad/enclosure. Page: 1 of 2 County of Albemarle Printed On: January 03, 2017 7)Provide line/parking space angle for angled parking spaces [18.4.12.16]. 8)BMP appears to have different configuration between grading/drainage plan and auxiliary site improvement sheets (C5.0 and C 6.0) and stormsewer drainage area sheet (C8.2). Additional BMP piping is shown, clarify which will be part of final design. 9)Layout and Utility plan (sheet C4.0) is missing some elements of the proposed stormsewer system. Specifically, at the northwest edge of the site near the proposed retaining wall, and the southwest edge of the site at the edge of the proposed parking lot extension. Please match these plans to the proposed design. 10)Bumper blocks will be needed in parking spaces where abutting a sidewalk less than 6' wide and in locations where curb does not exist [18.4.12.16]. Please note this in the plan, or revise the sidewalk dimensions. 11)Clarify what the arrow and dot symbol draining to structure 210 is representing. 12)Gutters shall be required where necessary to control or direct stormwater runoff (18-4.12.15.g). CG -6 curb and gutter will need to be provided along the inside of the island near the bus parking spaces and on the northeast side of the southwest parking lot extension. These areas are shown to be conveying stormwater as shown on drainage and grading plan sheet. 13)Revise radii labels at the south end of the bus parking lot. Currently the radii are dimensioned in inches and not feet. 14)proposed slopes steeper than 3:1 must have low maintenance (not grass) ground cover specified on the plan {Design Manual, Section 8). Low maintenance cover should extend over entire slope area. 15)Provide details for standard stormwater structures used as part of stormsewer system. (i.e. Drop inlets, surface drains, basin yard drains, doghouse manholes, junction boxes, etc.) 16)Provide basic details for proposed retaining walls (material, thickness, batter). No engineered plans are necessary for this application. 17)ldentify striping widths/lengths/details for entrance and parking lot areas. 18)Provide CG -12 curb cut for the crosswalk tying into the existing sidewalk adjacent to the parking lot on the west side of site. 19)VDOT approved entrance may be required for the access road connection to Idlewood drive. Please provide a detail of this entrance, and any required VDOT approvals. Date Completed: 12/21/2016 Reviewer: Division: RWSA Review Status: See Recommendations Reviews Comments: Sarah, I saw in the November 30, 2016 Site Review Memo that there is a site plan under review for the Woodbrook Elementary School Addition. RWSA does not have utilities in the immediate vicinity of the school; however, if the expansion will increase sewage flow by 40,000 gallons per day or more, a flow capacity certification will be required by RWSA prior to final approval. Let me know if you have any questions. Happy Holidays! Victoria Victoria Fort, P.E. Rivanna Water and Sewer Authority 695 Moores Creek Lane Charlottesville, VA 22902 (P): (434) 977-2970 ext. 205 (F): (434) 295-1146 Page: 2 of 2 County of Albemarle Printed On: January 03, 2017 COMMONWEALTH of VIRGINIA DEPARTMENT OF TRANSPORTATION 1601 Orange Road Charles A. Kilpatrick, P.E. Culpeper Virginia 22701 Commissioner January 3, 2017 County of Albemarle Department of Community Development 401 McIntire Road Charlottesville, VA 22902 Attn: Sarah Baldwin Re: Woodbrook Elementary School Add. — Major Site Plan Amendment SDP -2016-00069 Review #1 Dear Baldwin: The Department of Transportation, Charlottesville Residency Transportation and Land Use Section, has reviewed the above referenced plan as submitted by Timmons Group, dated 21 November 2016, and offers the following comment. Will the proposed improvements coincide with increased enrollment? If so, provide updated traffic/trip information. Based on this information we may have traffic signal related comments. If further information is desired, please contact Justin Dee] at 434-422-9894. A VDOT Land Use Permit will be required prior to any work within the right-of-way. The owner/developer must contact the Charlottesville Residency Transportation and Land Use Section at (434) 422-9399 for information pertaining to this process. Sincerely, Adam J. Moore, P.E. Area Land Use Engineer Charlottesville Residency VirginiaDOT.org WE KEEP VIRGINIA MOVING Service Auth6rity sm'Viv • Cmer*q TO: Sarah Baldwin FROM: Alexander J. Morrison, P.E., Civil Engineer DATE: January 5, 2017 RE: Site Plan Technical Review for: SDP201600069: Woodbrook Elementary School Addition - Major The below checked items apply to this site. X 1. This site plan is within the Authority's jurisdictional area for: X A. Water and sewer B. Water only C. Water only to existing structure D. Limited service X 2. A 6 inch water line is located approximately on site distant. 3. Fire flow from, nearest public hydrant, located distant from this site plan, is Gpm + at 20 psi residual. X 4. An (Unknown -Private) inch sewer line is located approximately on site distant. 5. An Industrial Waste Ordinance survey form must be completed. X 6. No improvements or obstructions shall be placed within existing or future easements. 7. and plans are currently under review. 8. and plans have been received and approved. 9. No plans are required. X 10. Final water and sewer plans are required for our review and approval prior to granting final site plan approval. 11. Final site plan may/may not be signed. 12. RWSA approval for water and/or sewer connections. 13. City of Charlottesville approval for sewer. X Comments: • Water construction plan review by the ACSA is required at this stage. • RWSA Wastewater Capacity Certification required if the overall development will produce more than 40,000 GPD in wastewater flow. • Show the existing water meter and add abandonment notes. • Existing and proposed fixture counts will be required to size the water meter. 168 Spotnap Road • Charlottesville • VA 22911 • Tel (434) 977-4511 • Fax (434) 979-0698 www.serviceauthority.org Sarah Baldwin From: Audrey Kocher <audreydiane1@gmail.com> Sent: Tuesday, January 03, 2017 6:46 PM To: Sarah Baldwin Subject: Woodbrook School Addition Site Plan Thank you for all your efforts to share the site plan and answer questions. Here are my concerns: 1. Loss of trees in front to the school entrance. I understood from school presentations to Woodbrook residents, several trees would be preserved. They are old and beautiful. 2. All the trees planted along Idlewood Drive during the last addition will be destroyed. More need to be saved. Replacement trees need to be evergreen to better screen the ugly bus parking lot from view. 2. Inadequate screening of school parking lots/bus parking from view of residents on Brentwood and Idlewood. The FEW trees included in site plan are trees that lose their leaves. Thus, no screening is available for significant periods of time during the year. More evergreens/bushes are needed. 3. Many trees were planted in memory of school children and staff who passed away. They need to be left standing or replaced with appropriate re commemoration. 4. No screening of school from houses #2907 and #2009 (along gym side of school). Screening is needed to keep lights from shining into homes and to hide large (unattractive) gym from view. Trees, bushes, including evergreens, are needed. 5. No plan for replacing swings and basketball court are seen on plans. These are heavily used by entire Rio/29 community. Per county comprehensive plan, Neighborhood 2 (Woodbrook area) has no green space other than the school grounds. Residents are directed to Meadow Creek Trail and Penn Park .... too far for many in the area. There are no basketball courts/play ground equipment from Woodbrook to Dunlora. Many in community drive here to play. One consistent group coming here is an Hispanic group of men to pay soccer on Sunday morning. They bring their children and current configuration of playground allows them to play and supervise their children. This loss is a major community loss. 6. Presentations to Woodbrook neighbors show the gym reconfigured to make it appear less massive from the street view. That plan is not clear on the school site plans or was it oomitted? Thank you. Respectfully, Audrey Kocher 2909 Idlewood Drive Charlottesville, VA 22901 434-978-3759