HomeMy WebLinkAboutSDP201600021 Review Comments 2017-01-12Short Review Comments Report for:
SDP201600021
SubApplication Type:
Chapman Grove Baptist Church - Major
Major Amendment
Date Completed:05/19/2016
Reviewer:Johnathan Newberry CDD Planning
Review Status:Requested Changes
Reviews Comments:
Division:
Date Completed:04/05/2016
Reviewer:John Anderson CDD Engineering
Review Status:No Objection
Reviews Comments:Area of disturbance estimated <5,000 ft2. Activity is not subject to the VESCP or VSMP [17-300.A.;
17-302.A, respectively], and is not required to prepare an Erosion and Sediment Control, or SWM
plan. A Tier 3 groundwater assessment is required -ref. 17-1003 [sample Tier 3 GW Assessment
Attached].
Show stream buffer on site plan. Avoid stream buffer (ref. GIS image). (JTN - this comment taken
from JA's SP201600007 comments)
Division:
Date Completed:04/07/2016
Reviewer:Andrew Slack CDD E911
Review Status:No Objection
Reviews Comments:No objection.
Division:
Date Completed:05/02/2016
Reviewer:Jay Schlothauer CDD Inspections
Review Status:Requested Changes
Reviews Comments:Based on plans dated March 1, 2016.
Due to the total number of parking spaces, two of them must be barrier-free. Provide two barrier-free
parking spaces on the ramp side of the building. One of these spaces must be van-accessible.
Division:
Date Completed:05/11/2016
Reviewer:Margaret Maliszewski CDD ARB
Review Status:Requested Changes
Reviews Comments:1. Add the standard mechanical equipment note to the site and architectural plans. “Visibility of all
mechanical equipment from the Entrance Corridor shall be eliminated.”
2. Submit the manufacturer’s cut sheet for the proposed wall fixtures. Identify choices for all the
lighting options.
3. Add the standard lighting note to the site plan. “Each outdoor luminaire equipped with a lamp that
emits 3,000 or more initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to
reflect light away from adjoining residential districts and away from adjacent roads. The spillover of
lighting from luminaires onto public roads and property in residential or rural areas zoning districts
shall not exceed one half footcandle.”
4. Correct the plan regarding existing trees on site. Show that existing trees meet or exceed frontage
requirements or add trees to meet required quantities and sizes, with species and spacing
compatible with the character of the rural area.
5. Accurately show existing trees and shrubs on the site plan. Clearly identify all trees and shrubs to
be removed.
6. Add a tree and/or shrubs at the east end of the parking row located just north of the building.
7. Add a plant schedule to the site plan.
8. Add the standard plant health note to the plan. “All site plantings of trees and shrubs shall be
allowed to reach, and be maintained at, mature height; the topping of trees is prohibited. Shrubs and
trees shall be pruned minimally and only to support the overall health of the plant.”
9. Clarify the terrace and sidewalk connections on the site plan.
10. Revise the site plan to show the existing tree located near the front sidewalk. Show that it will be
protected with fencing during construction.
Division:
Page:1 of 3 County of Albemarle Printed On:February 03, 2017
allowed to reach, and be maintained at, mature height; the topping of trees is prohibited. Shrubs and
trees shall be pruned minimally and only to support the overall health of the plant.”
9. Clarify the terrace and sidewalk connections on the site plan.
10. Revise the site plan to show the existing tree located near the front sidewalk. Show that it will be
protected with fencing during construction.
Date Completed:05/18/2016
Reviewer:Alexander Morrison ACSA
Review Status:No Objection
Reviews Comments:
Division:
Date Completed:05/19/2016
Reviewer:Joel DeNunzio VDOT
Review Status:Requested Changes
Reviews Comments:
Division:
Date Completed:07/27/2016
Reviewer:Johnathan Newberry CDD Planning
Review Status:Requested Changes
Reviews Comments:
Division:
Date Completed:07/05/2016
Reviewer:Margaret Maliszewski CDD ARB
Review Status:Requested Changes
Reviews Comments:Please revise the plan to make the entire plan legible.
Division:
Date Completed:07/15/2016
Reviewer:Jay Schlothauer CDD Inspections
Review Status:No Objection
Reviews Comments:Based on plans revised June 20, 2016.
No further comments or conditions.
Division:
Date Completed:07/15/2016
Reviewer:Max Greene CDD Engineering
Review Status:See Recommendations
Reviews Comments:The Site plan may require a VSMP plan submitted for approval due to the Virginia State requirements
for projects considered "part of a larger common plan of development". A determination is underway
for the definition of a "Greater Plan of Development".
Division:
Date Completed:07/06/2016
Reviewer:Adam Moore VDOT
Review Status:See Recommendations
Reviews Comments:"We find this revision to be generally acceptable, provided that the following concerns are addressed
on the signature planset."
(The concerns related to standard VDOT info like ADT, route number, etc., and also to sight distance,
where additional grading may be required.)
Division:
Date Completed:08/02/2016
Reviewer:Margaret Maliszewski CDD ARB
Review Status:Approved
Reviews Comments:no further comments
Division:
Date Completed:09/01/2016
Max GreenePage:2 of 3 County of Albemarle Printed On:February 03, 2017
Reviewer:Max Greene CDD Engineering
Review Status:No Objection
Reviews Comments:
Division:
Date Completed:12/22/2016
Reviewer:Adam Moore VDOT
Review Status:Approved
Reviews Comments:
Division:
Date Completed:01/04/2017
Reviewer:Robbie Gilmer Fire Rescue
Review Status:Requested Changes
Reviews Comments:
Division:
Date Completed:01/06/2017
Reviewer:Robbie Gilmer Fire Rescue
Review Status:No Objection
Reviews Comments:
Division:
Date Completed:01/12/2017
Reviewer:Johnathan Newberry CDD Planning
Review Status:Approved
Reviews Comments:
Division:
Page:3 of 3 County of Albemarle Printed On:February 03, 2017
COUNTY OF ALBEMARLE
°f ALks Department Community Development
Planning Services Division
4.10 401 McIntire Road North Wing• Charlottesville, Virginia 22902-4596
Phone: (434) 296-5823 • Fax: (434)972-4035
Transmittal
From: JT Newberry Date: 08/24/16
To: Engineering — Ao►.. (er uv.e. 0
0 (*Ka, •b•tc Sieh 0
0 `� 0
0 0
0 0
JOB #/FILE NAME:SP-2016-0007 Chapman Grove Baptist Church and SDP201600021 Chapman
Grove Baptist Church (Major)
We are sending you the following items: N Attached or n Under separate cover
n Copy of Letter E Prints F Plans
❑ Plats ❑ Specifications n Other
# of Date Description
Copies
1 6/20/16 Sheets SP1 (Site Plan),A-1 (Phasing Plan)
1 8/1/16 Tier 3 Groundwater Assessment
These are transmitted as checked below:
® For review and comments ® For approval n Other
Remarks: Please see the enclosed correspondence from the applicant. John Anderson required the
Tier 3 report as part of his review of the Major Amendment for this site (SDP201600021). Please let
me know if Engineering requests any changes to the concept plan/amendment plan as a result of the
information shown in the Tier 3 report.
The Planning Commission unanimously recommended approval of the special use permit to the Board
of Supervisors with Condition#4 being that "No building permit shall be approved without approval
from the Virginia Department of Health."
Finally, please return these materials to me after your review. This is the only copy I have. Thanks.
Comments are due in City View or email by: 9/16/16 Signature: JT Newberry
.4400,
Johnathan Newberry
From: Stephen von Storch <svonstorch@s-vs.com>
Sent: Tuesday, August 23, 2016 10:45 AM
To: Johnathan Newberry
Cc: Gale Brown
Subject: FW:tier 3 chapman groves
Attachments: Chapman Groves Baptist Church Tier 3 assessment v 8 1 16.pdf
JT
It has been hectic here and I want to be sure I had forwarded this to you.
As Gooch predicted we are OK for Phase One with work needed for Phase Two.
Steve
From: olddomeng@ntelos.net [mailto:olddomeng@ntelos.net]
Sent: Monday, August 01, 2016 8:42 AM
To: Stephen von Storch
Subject: RE: tier 3 chapman groves
Stephen,
Attached is Tier 3 Report.
Just a couple notes for you:
Unless they want to do a daycare or school they should not be classified as a "public water system". With that
being said the well is in a horrible place (without a lot of good options for a new well). We are recommending
some testing be done on the well to make sure the water quality is good and that the water quantity is verified
before phase 2.
Doesn't look like septic needs to be changed till phase 2. It will be an engineered system with time dosing for
sure for phase 2.
I tried to write the tier 3 so it would be applicable for both phase 1 and phase 2. We might have to write an
update memo.
Best,
Mike
On Fri, 29 Jul 2016 20:13:22 +0000, Stephen von Storch<svonstorch@s-vs.com> wrote:
i
Sounds good.
Have a good weekend.
Original Message
From: olddomeng@ntelos.net [mailto:olddomeng@ntelos.net]
Sent: Friday, July 29, 2016 4:04 PM
To: Stephen von Storch
Subject: tier 3 chapman groves
Stephen,
We are in the process of proofreading the tier 3 for Chapman groves. It will go out to you on Monday.
Typically we send pdfs to the agent who then submits it to the engineering department. After engineering
review and revision we print out hard copies for all parties.
Is this OK?
Best,
Mike Craun
Old Dominion Engineering
2
COMMONWEALTH of VIRGINIA
DEPARTMENT OF TRANSPORTATION
1601 Orange Road
Culpeper. Virginia 22701
Charles A. Kilpatrick, P.E.
Commissioner
July 6, 2016
County of Albemarle
Department of Community Development
401 McIntire Road
Charlottesville, VA 22902
Attn: J.T. Newberry
Re: Chapman Grove Baptist Church
SDP -2016-00021 — Major Site Plan Amendment
SP -2016-00007 — Special Use Permit
Review #2
Dear Mr. Newberry:
The Department of Transportation, Charlottesville Residency Transportation and Land Use
Section, has reviewed the above referenced plan as submitted Stoneking Von Storch, last revised
20 June 2016, and find it to be generally acceptable, provided that the following concerns are
addressed on the signature planset. Note that revisions may be submitted via email if the
applicant wishes to address these concerns prior to producing signature copies.
1. PIease show and label VDOT right of way, ADT, and design speed on plans in addition
to route number.
2. Please note that intersection sight distance may be evaluated in an as -built scenario at the
completion of construction as it appears that because of low clearance, additional grading
may be required.
Upon submission of the appropriate signed and sealed approval copies this office will perform a
final review and, if acceptable, sign the plans. Please allow for this office to obtain two signature
copies.
A VDOT Land Use Permit will be required prior to any work within the right-of-way. The
owner/developer must contact the Charlottesville Residency Transportation and Land Use
Section at (434) 422-9399 for information pertaining to this process. If further information is
desired please contact Justin Deel at (434) 422-9894.
Sincerely,
A9044- . iqav�'
Adam J. Moore, P.E.
Area Land Use Engineer
Charlottesville Residency
VirginiaDOT_org
WE KEEP VIRGINIA MOVING
OF AI,ti.
4z? aCa te
Ilk!
4: Oft
l'tRcmnV'
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road,North Wing
Charlottesville,Virginia 22902-4596
Phone(434)296-5832 Fax(434)972-4126
May 19,2016
Stephen von Storch
P.O.Box 1332
Charlottesville,VA 22902
svonstorch(a}s-vs.com
RE: SDP201600021 Chapman Grove Baptist Church—Major Site Plan Amendment
Dear Mr.von Storch:
The Site Review Committee has reviewed the development proposal referenced above. Initial comments
for the following divisions of the Department of Community Development and other agencies, as
applicable,are attached:
Albemarle County Planning Services(Planner)
Albemarle County Engineering Services (Engineer)
Albemarle County Information Services(E911)
Albemarle County Building Inspections
Albemarle County Zoning Services
Albemarle County Architectural Review Board
Albemarle County Department of Fire Rescue (to be forwarded upon receipt)
Virginia Department of Transportation (to be forwarded upon receipt)
Virginia Department of Health(to be forwarded upon receipt)
Comments reflect information available at the time the development proposal was reviewed,and should
not be considered final. However,the Site Review Committee has attempted to identify all issues that
will be required to be resolved prior to final approval of the Major Amendment.
Please contact me at your earliest convenience if you have questions or require additional information.
Sincerely,
a,4 - NA.Qte/wer
J.T.Newberry
Planner
CC: Chapman Grove Baptist Church
c/o Gale Brown
2064 Stony Point Road
Charlottesville,VA 22911
gddent(ayahoo.com
'44001e Norio0
Albemarle County Planning Services(Planner)—J.T.Newberry,jnewberrv(a)albemarle.org
1. Please show the following changes on Sheet SP 1:
a. Section 32.5.2(a)—Please add the following general information:
i. The magisterial district(Rivanna District);
ii. Label or note the setback lines(Front—75 ft, Side—25 ft,Rear—35 ft);
iii. Note the property lies in the Entrance Corridor(EC)Overlay district;
iv. Descriptions of the previously approved special use permit and variances and their
conditions thereof. In this case,it may be easiest to add a second sheet to the major
amendment showing.PDFs of the approval letters for VA1992-030,VA2000-031 and
SP2000-061. Alternatively,you can add a note with this information.
b. Section 32.5.2(b)—Please add a note to clearly indicate the proposed use(e.g. "Church
addition in two phases amending SDP2000-129.")
c. Section 32.5.2(c)—Please update the total building and disturbed areas for each phase once the
final design is determined.
d. Section 32.5.2(m)—Please show the distance to the centerline of State Route 20 from the
entrance.
e. Section 32.5.2(n)/32.6.2(i)—Please note the material for the new parking spaces.
f. Section 32.5.2(p)—If existing landscaping does not meet minimum requirements,then please
submit a landscape plan that complies with Section 32.7.9.
g. Section 32.6.2(h)—Please add a signature panel for signature by each member of the site
review committee.
Albemarle County Engineering Services(Engineer)—John Anderson, j`anderson2cd?albemarllee.orrg
1. Area of disturbance estimated<5,000 ft2. Activity is not subject to the VESCP or VSMP [17-300.A.;
17-302.A,respectively],and is not required to prepare an Erosion and Sediment Control,or SWM
plan.
2. A Tier 3 groundwater assessment is required-ref. 17-1003 [sample Tier 3 GW Assessment].
3. Show stream buffer on site plan. Avoid stream buffer(ref.GIS image).
Albemarle County Information Services(E911)—Andy Slack,aslack(a)albemarle.org—No objection
Albemarle County Building Inspections,Jay Schlothauer,jschloth@i2albemarle.org
1. Due to the total number of parking spaces,two of them must be barrier-free. Provide two barrier-free
parking spaces on the ramp side of the building. One of these spaces must be van-accessible.
Albemarle County Zoning Services(E911)—Ron Higgins,rhigginsp)albemarle.org
1. Parking area is labeled as having "43 spaces"where there are only 39 spaces total on site.Please revise
this label and the note above it to be consistent with the parking shown.
2. Parking analysis is acceptable for pre&post expansion parking,both of which work out to slightly
more than one parking space per three seats.
3. Additional landscaping may be required for revised parking area frontage plantings.
4. VAR2000-031 included a condition that any new additions meet the front setbacks at the time of
proposal.Therefore,new additions will require a front setback of 75 feet.
Albemarle County Architectural Review Board—Margaret Maliszewski,mmaliszewski ?albemarle.org
1. Add the standard mechanical equipment note to the site and architectural plans."Visibility of all
mechanical equipment from the Entrance Corridor shall be eliminated."
2. Submit the manufacturer's cut sheet for the proposed wall fixtures. Identify choices for all the lighting
options.
3. Add the standard lighting note to the site plan."Each outdoor luminaire equipped with a lamp that
emits 3,000 or more initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to
reflect light away from adjoining residential districts and away from adjacent roads. The spillover of
lighting from luminaires onto public roads and property in residential or rural areas zoning districts
shall not exceed one half footcandle."
4. Correct the plan regarding existing trees on site. Show that existing trees meet or exceed frontage
requirements or add trees to meet required quantities and sizes,with species and spacing compatible
,44.00 Nitrirt
with the character of the rural area.
5. Accurately show existing trees and shrubs on the site plan. Clearly identify all trees and shrubs to be
removed.
6. Add a tree and/or shrubs at the east end of the parking row located just north of the building.
7. Add a plant schedule to the site plan.
8. Add the standard plant health note to the plan."All site plantings of trees and shrubs shall be allowed
to reach,and be maintained at,mature height;the topping of trees is prohibited. Shrubs and trees shall
be pruned minimally and only to support the overall health of the plant."
9. Clarify the terrace and sidewalk connections on the site plan.
10. Revise the site plan to show the existing tree located near the front sidewalk. Show that it will be
protected with fencing during construction.
Albemarle County Department of Fire Rescue—Robbie Gilmer,rgilmer(th,albemarle.org
1. No comments were provided,but their approval will be required prior to final approval(JTN).
Virginia Department of Transportation
1. No comments were provided,but their approval will be required prior to final approval(JTN).
Virginia Department of Health
1. No comments were provided,but their approval will be required prior to final approval(JTN).
COMMONWEALTH of VIRGINIA
DEPARTMENT OF TRANSPORTATION
1601 Orange Road
Culpeper Virginia 22701
Charles A. Kilpatrick, P.E.
Commissioner
May 19, 2016
Mr. J.T. Newberry
County of Albemarle
Department of Community Development
401 McIntire Road
Charlottesville, VA 22902
Re: SDP -2016-00021 Chapman Grove Baptist Church — Major Site Plan Amendment
SP -2016-00007 Chapman Grove Baptist Church — Special Use Permit
Dear Mr. Newberry:
We have reviewed the Chapman Grove Baptist Church Major Site Plan Amendment and Special
Use Permit applications, dated March 1, 2016, as submitted by Stoneking Von Storch Architects,
and have the following comment;
The Virginia Access Management Regulations (24VAC30-73-110) states that
commercial entrances may be reviewed and reconstruction, relocations, consolidation,
upgrading, or a combination of these may be required if any of the following occur; 1)
the property is being considered for rezoning or other local legislative action that
involves a change in use, 2) if the property is subject to a site plan or subdivision plat
reviw, 3) there is a change (increase) in commercial use, or 4) circulation between
adjoining properties becomes available.
It appears that there may not be adequate sight distance at this entrance. Please show
sight distance lines (Road Design Manual, Appendix F) and provided sight line
easements if necessary.
If additional information is needed concerning this project, please do not hesitate to contact me at
(434) 422-9373.
Sincere
Joel DeNunzio, P.E.
Resident Engineer
Culpeper District
low" Nrige
Z-5 ik,211r111-
All lar'
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road,North Wing
Charlottesville,Virginia 22902-4596
Phone(434)296-5832 Fax(434)972-4126
May 19,2016
Stephen von Storch
P.O. Box 1332
Charlottesville, VA 22902
svonstorch@s-vs.com
RE: SDP201600021 Chapman Grove Baptist Church—Major Site Plan Amendment
Dear Mr. von Storch:
The Site Review Committee has reviewed the development proposal referenced above. Initial comments
for the following divisions of the Department of Community Development and other agencies, as
applicable,are attached:
Albemarle County Planning Services(Planner)
Albemarle County Engineering Services(Engineer)
Albemarle County Information Services(E911)
Albemarle County Building Inspections
Albemarle County Zoning Services
Albemarle County Architectural Review Board
Albemarle County Department of Fire Rescue (to be forwarded upon receipt)
Virginia Department of Transportation (to be forwarded upon receipt)
Virginia Department of Health (to be forwarded upon receipt)
Comments reflect information available at the time the development proposal was reviewed,and should
not be considered final. However,the Site Review Committee has attempted to identify all issues that
will be required to be resolved prior to final approval of the Major Amendment.
Please contact me at your earliest convenience if you have questions or require additional information.
Sincerely, ' V14,4A4,6 Taw• •X
a,4 - Y\WAKAAA5" AiatA 61A4",t,,,a, ., „&tuA).0..A 5/11 e 4r---
J.T.Newberry
Planner
CC: Chapman Grove Baptist Church 1'19, 4c Z W,; _ n ear 6-4-a..44-‘414-6,Ac/o Gale Brown
2064 Stony Point Road V11-1 A4 situ 4 ;
Charlottesville, VA 22911
gddent@yahoo.com
7
vrrr
Albemarle County Planning Services(Planner)—J.T.Newberry,jnewberry@albemarle.org
1. Please show the following changes on Sheet SP1:
a. Section 32.5.2(a)—Please add the following general information:
i. The magisterial district(Rivanna District);
ii. Label or note the setback lines(Front—75 ft, Side—25 ft,Rear—35 ft);
iii. Note the property lies in the Entrance Corridor(EC)Overlay district;
iv. Descriptions of the previously approved special use permit and variances and their
conditions thereof. In this case,it may be easiest to add a second sheet to the major
amendment showing.PDFs of the approval letters for VA 1992-030, VA2000-031 and
SP2000-061.Alternatively,you can add a note with this information.
b. Section 32.5.2(b)—Please add a note to clearly indicate the proposed use(e.g. "Church
addition in two phases amending SDP2000-1 29.")
c. Section 32.5.2(c)—Please update the total building and disturbed areas for each phase once the
final design is determined.
d. Section 32.5.2(m)—Please show the distance to the centerline of State Route 20 from the
entrance.
e. Section 32.5.2(n)/32.6.2(i)—Please note the material for the new parking spaces.
f. Section 32.5.2(p)—If existing landscaping does not meet minimum requirements,then please
submit a landscape plan that complies with Section 32.7.9.
g. Section 32.6.2(h)—Please add a signature panel for signature by each member of the site
review committee.
Albemarle County Engineering Services(Engineer)—John Anderson,janderson2@albemarle.org
1. Area of disturbance estimated<5,000 ft2. Activity is not subject to the VESCP or VSMP[17-300.A.;
17-302.A, respectively],and is not required to prepare an Erosion and Sediment Control,or SWM
plan.
2. A Tier 3 groundwater assessment is required-ref. 17-1003 [sample Tier 3 GW Assessment].
3. Show stream buffer on site plan. Avoid stream buffer(ref. GIS image).
Albemarle County Information Services(E911)—Andy Slack, aslack@albemarle.org—No objection
Albemarle County Building Inspections,Jay Schlothauer,jschloth@albemarle.org
1. Due to the total number of parking spaces,two of them must be barrier-free. Provide two barrier-free
parking spaces on the ramp side of the building. One of these spaces must be van-accessible.
Albemarle County Zoning Services(E911)—Ron Higgins,rhiggins@albemarle.org
1. Parking area is labeled as having"43 spaces" where there are only 39 spaces total on site. Please revise
this label and the note above it to be consistent with the parking shown.
2. Parking analysis is acceptable for pre&post expansion parking,both of which work out to slightly
more than one parking space per three seats.
3. Additional landscaping may be required for revised parking area frontage plantings.
4. VAR2000-031 included a condition that any new additions meet the front setbacks at the time of
proposal. Therefore,new additions will require a front setback of 75 feet.
Albemarle County Architectural Review Board—Margaret Maliszewski,mmaliszewski@albemarle.org
1. Add the standard mechanical equipment note to the site and architectural plans. "Visibility of all
mechanical equipment from the Entrance Corridor shall be eliminated."
2. Submit the manufacturer's cut sheet for the proposed wall fixtures. Identify choices for all the lighting
options.
3. Add the standard lighting note to the site plan. "Each outdoor luminaire equipped with a lamp that
emits 3,000 or more initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to
reflect light away from adjoining residential districts and away from adjacent roads. The spillover of
lighting from luminaires onto public roads and property in residential or rural areas zoning districts
shall not exceed one half footcandle."
4. Correct the plan regarding existing trees on site. Show that existing trees meet or exceed frontage
requirements or add trees to meet required quantities and sizes,with species and spacing compatible
with the character of the rural area.
5. Accurately show existing trees and shrubs on the site plan. Clearly identify all trees and shrubs to be
removed.
6. Add a tree and/or shrubs at the east end of the parking row located just north of the building.
7. Add a plant schedule to the site plan.
8. Add the standard plant health note to the plan. "All site plantings of trees and shrubs shall be allowed
to reach,and be maintained at,mature height;the topping of trees is prohibited. Shrubs and trees shall
be pruned minimally and only to support the overall health of the plant."
9. Clarify the terrace and sidewalk connections on the site plan.
10. Revise the site plan to show the existing tree located near the front sidewalk. Show that it will be
protected with fencing during construction.
Albemarle County Department of Fire Rescue—Robbie Gilmer,rgilmer(&albemarle.org
1. No comments were provided,but their approval will be required prior to final approval(JTN).
Virginia Department of Transportation
1. No comments were provided,but their approval will be required prior to final approval(JTN).
Virginia Department of Health
1. No comments were provided,but their approval will be required prior to final approval (JTN).
Ai;
COMMONWEALTH of VIRGINIA
DEPARTMENT OF TRANSPORTATION
160i Orange Firma
Culoeper%/Imo I 227D1
Charles A. Kilpatrick,P.E.
Commissioner
May 19, 2016
Mr. J.T. Newberry
County of Albemarle
Department of Community Development
401 McIntire Road
Charlottesville,VA 22902
Re: SDP-2016-00021 Chapman Grove Baptist Church—Major Site Plan Amendment
SP-2016-00007 Chapman Grove Baptist Church—Special Use Permit
Dear Mr. Newberry:
We have reviewed the Chapman Grove Baptist Church Major Site Plan Amendment and Special
Use Permit applications,dated March 1, 2016, as submitted by Stoneking Von Storch Architects,
and have the following comment;
• The Virginia Access Management Regulations(24VAC30-73-110) states that
commercial entrances may be reviewed and reconstruction,relocations, consolidation,
upgrading, or a combination of these may be required if any of the following occur; 1)
the property is being considered for rezoning or other local legislative action that
involves a change in use, 2) if the property is subject to a site plan or subdivision plat
reviw,3) there is a change (increase) in commercial use,or 4)circulation between
adjoining properties becomes available.
• It appears that there may not be adequate sight distance at this entrance. Please show
sight distance lines (Road Design Manual, Appendix F)and provided sight line
easements if necessary.
If additional information is needed concerning this project, please do not hesitate to contact me at
(434)422-9373.
Sincere
/
Joel DeNunzio, P.E.
Resident Engineer
Culpeper District
11�:iL31
IV 04'
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road,North Wing
Charlottesville,Virginia 22902-4596
Phone(434)296-5832 Fax(434)972-4126
Memorandum
To: Ms,Gale Brown
From: Scott Clark, Senior Planner; e *n,;) 2:70A, J lrea,k,
Date: 7/28/14
Subject: Chapman Grove Pre-application Meeting, 7/12/2014
The following are County staff comments regarding the above noted pre-application meeting. This
meeting satisfies the requirement for a pre-application meeting prior to submittal of your special use
permit application The purpose of for the meeting is summarized below:
The purposes for a pre-application meeting are to:(i)provide the applicant and the county a
common understanding of the proposed project;(ii)inform the applicant about the proposed
project's consistency with the comprehensive plan, other relevant policies, and county
regulations;(iii)broadly identify the planning, zoning and other issues raised by the application
that need to be addressed by the applicant;(iv)inform the applicant about the applicable
procedure;and(v)allow the director to identify the information the applicant must submit with the
application, including the supplemental information delineated in subsection(c). Receiving the
relevant supplemental information will allow the application to be comprehensively and efficiently
reviewed_
The following are staff comments:
(ii)Consistency with the Comprehensive Plan:
• As discussed in the meeting, Comprehensive Plan issues will mainly involve the appropriateness
of the'new scale of use in the Rural Areas.
(iii)broadly identify the planning, zoning and other issues raised by the application that need to be
addressed by the applicant
• VDOT will need to verify that the entrance is acceptable, or comment on necessary
improvements.This will happen during the review.
• Parking needs must be addressed.As discussed at the meeting,the church will need to provide a
parking study with the application.
• Zoning will need to review the existing setback issue and determine if it creates any problem for
the proposed use, and if the proposed driveway can legally fit within the remaining space.
(iv)applicable procedures
• Community Meeting—the applicant is required by ordinance to undertake a community meeting
process as part of the review of the rezoning request. This meeting should be held, if possible,
within 30 days from the date the application is submitted,and can be held prior to the submittal of
1
the application. Adjacent property owners and neighborhoods(and the Coordinating
Reviewer/planner)should receive advance notification of this meeting (date/time/location). Staff
can provide a mailing list for this meeting.
• ARB review,Ag-Forestal District reviews
• Need for special exceptions
(v) Identify the information the applicant must submit with the application,including the supplemental
information
• Parking study,as noted above.
• An conceptual plan should be submitted with the special use permit application.
• Floorplans and elevations for the existing and proposed structures.
• See attached pre-application checklist for other required information. This checklist will need to
be filled in, signed and submitted with the ZMA application.
If you have any further questions, please contact me.
Sincerely,
Scott Clark
Senior Planners, Rural Areas
2
Johnathan Newberry
From: Johnathan Newberry
Sent: Tuesday, April 05, 2016 6:11 PM
To: 'svonstorch@s-vs.com'
Cc: 'gddent@yahoo.com'; John Anderson; Margaret Maliszewski; Elaine Echols
Subject: Special Use Permit and Major Site Plan Amendment Applications
Attachments: Review Timeline - SP201600007.pdf; Planning Application Review for SDP201600021
Chapman Grove Baptist Church - Major.
Hi Stephen,
My name is J.T. Newberry and I am coordinating the review of the special use permit and major site plan amendment
applications for Chapman Grove Baptist Church. I'm sending this email to you because your name is listed as the contact
person and I would like to share some important upcoming dates.
Special Use Permit — SP201600007
Please see the attached review timeline. Comments will be provided on 5/6/2016. The public hearing date with the
Planning Commission is scheduled to happen no earlier than the 6/7/16 meeting.
Major Site Plan Amendment — SDP201600022
Comments will be provided on 5/16/2016. The Site Review Committee (SRC) meeting will be held on 5/19/16 at 10am in
Room 246 of the County Office Building. There's a chance that I may contact you for additional copies of the site plan
and phasing plan, but I'm trying to work it where the reviewers can use just the one set of plans you've already
submitted to review both SP201600007 and SDP201600021. I'll let you know if additional copies are needed.
Finally, although all of the available site plan comments will be provided on 5/16/16, I've attached the comment from
the Engineering Division because I anticipate it will take some time to address it. In part, it states that a Tier 3
Groundwater Assessment is required. John Anderson, P.E. (ext. 3069) provided an example report of this type of
assessment from another church that was recently reviewed, which can be viewed here:
http://www.albemarle.org/weblink/`O/doc/240113/Pagel.aspx He also provided contact information for the author of
the report.
Please let me know if you have any questions.
Thanks,
J.T. Newberry
Planner
County of Albemarle, Planning Division
434-296-5832, ext. 3270
Johnathan Newberry
From: John Anderson
Sent: Tuesday, April 05, 2016 3:27 AM
To: Johnathan Newberry
Subject: Planning Application Review for SDP201600021 Chapman Grove Baptist Church - Major.
The Review for the following application has been completed:
Application Number=SDP201600021
Reviewer=John Anderson
Review Status = No Objection
Completed Date = 04/05/2016
Thanks for your patience.
CV comments have not been shared with Applicant.
CV comments:
"Area of disturbance estimated<5,000 ft2. Activity is not subject to the VESCP or VSMP [17-300.A.; 17-302.A,
respectively], and is not required to prepare an Erosion and Sediment Control or SWM plan. A Tier 3 groundwater
assessment is required-ref. 17-1003 [sample Tier 3 GW Assessment Attached]."
-x3069
[Tier 3 Author: Mike Craun,PE/Waynesboro,VA/540-255-1700]