HomeMy WebLinkAboutWPO201700011 Review Comments WPO VSMP 2017-11-08�5 oeass 40 Dominion y` Engineering November 8th, 2017 Mr. Bobby Jocz Department of Community Development 401 McIntire Road Charlottesville, VA 22902 172 South Pantops Drive Charlottesville, VA 22911 RE: WPO201700011 Meade Builders Office Building - VSMP Permit Plan Dear Mr. Jocz, 434.979.8121 (p) 434.979.1681 (f) DominionEng.com Please find attached two (2) copies of the revised Plans. The plans have been revised to address your comments received on 10/12/2017 in accordance with the following: C. Stormwater Management Plan (SWMP) VSMP Regulation 9VAC25-870-108 requires the VSMP authority to approve or disapprove a SWMP. This plan is disapproved, and the reasons are provided in the comments below. The stormwater management plan content requirements can be found in County Code section 17- 403. Width of SWM easement inadequate. Easement must beat least 30' in width *15' wide structure @ 9' depth max + 1' access on each side of the outer pipes, with 1:1 slopes from top pipe to final grade level (6')). Response: We have moved the pipe that is closest to the retainin all to the other side of the storm structure to provide a 30' easement exclusiveof tIt etaining wall. Across section of the storm sewer system has been added to SW10. 7101lu 2. Plase amend the label for the stormwater facility easement to sttate"New variable width SWM Facility Easment". Response: The label for the stormwater facility easement has been amended as requested. 01,6,1 lw5 40 6 &*Jtey l-/ pled R 12A'-- 3. 0.55 lbs of Offsite Phosphorous Credit will need to be purchased prior to final VSMP approval. Response: 0.55 lbs of Offsite Phosphorous Credit will be purchased once all technical comments have been addressed and prior to final VSMP approval from a Nutrient Credit Bank in or adjacent to the Hydrologic Unit Code as the development in the same watershed. 1 of 2 �s ,e% e %S c ° Dominion Engineering 172 South Pantops Drive Charlottesville, VA 22911 434.979.8121 (p) 434.979.1681 (f) DominionEng.com 5. VSMP approval must occur prior to major site plan amendment approval - Acknowledged. n� Response: Comment Noted. of We thank you for taking the time to review these plans and trust the above adequately addresses your comments. However, please let me know if you have any questions or require additional information. Very truly Michel Myers, PE, CFM Cc: Charlie Armstrong 6 of 6 COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road, Room 227 Charlottesville, Virginia 22902-4596 Phone (434) 296-5832 Fax (434) 972-4126 VSMP Permit plan review Project title: Meade Builders Office Building Project file number: WP0201700011 Plan preparer: Dustin Greene, Dominion Engineering [dgreene@dominionemg. com] Owner or rep.: Charlie Armstrong, Ballif Investments, LLC [CharlesA@southern-development. com] Plan received date: Rev 1 — 6 Feb. 2017 Rev 2 — 20 August 2017 Rev 3 — 8 September 2017 Date of comments: Rev 1 — 21 Feb. 2017 Rev 2 —12 September 2017 Rev 3 — 28 September 2017 Reviewers: Rev 1 — Bobby Jocz Rev 2 — Bobby Jocz Rev 3 — Bobby Jocz County Code section 17-410 and Virginia Code §62.1-44.15:34 requires the VSMP authority to act on any VSMP permit by issuing a project approval or denial. This project is Approved contingent on purchase of 0.55 lbs of Nutrient Credits and recordation of deed of dedication/easement. The rationale is given in the comments below. The application may be resubmitted for approval if all of the items below are satisfactorily addressed. The VSMP application content requirements can be found in County Code section 17-401. A. Stormwater Pollution Prevention Plan (SWPPP) The SWPPP content requirements can be found in County Code section 17-405. A SWPPP must contain (1) a PPP, (2) an ESCP, (3) a SWMP, and (4) any TMDL measures necessary. 1. [General] Confirm accurate existing topography is provided. All topography should be at least visually field verified by the designer within the last year. Rev 2 — Addressed. 2. [General] Display extent of 100yr floodplain and WPO buffer {County Code 17-403(8)1. Rev 2 — Addressed. 3. [General] Plans show construction/grading occurring on the adjacent parcel. Please include these parcels and owner's signature on future submittals, or obtain temporary construction easement. Rev 2 — Addressed. 4. [SWPPP] Provide copy of DEQ coverage letter when obtained {County Code 17-405}. Rev 2 — Acknowledged. 5. [SWPPP] Correct Table of Contents to reflect section headings in document. The SWPPP seems to be missing section 5 "Stormwater Management Plan", replacing it as the "Pollution Prevention Plan". Rev 2 — Addressed. 6. [SWPPP]The approved SWM plan will need to be included within the SWPPP when plans are Engineering Review Comments Page 2 of 4 ready to be approved {County Code 17-4051. Rev 2 — Acknowledged. 7. [SWPPP]The approved Erosion and Sediment Control Plan will need to be included within the SWPPP when plans are ready to be approved {County Code 17-405}. Rev 2 - Acknowledged. 8. [SWI ] Update plan sheets and SWPPP with current WPO submittal number [WP0201700011 ] Rev 2 — Addressed. 9. [SW5] Separate the SWM plan and E&S Phase II details on sheet SW5. The SWM plan should have its own sheet. Rev 2 — Addressed. 10. [SW6] Remove the "Frame Shed" diagram located over the parking lot on the southeastern portion of the site. According to plans this will already be demolished. Rev 2 — Addressed. 11. [SW8] Level spreader detail should be included as SWM detail, not on E&S detail sheet. Rev 2 — Addressed. 12. [All] Please more clearly label proposed and existing contour elevations. Rev 2 — addressed. B. Pollution Prevention Plan (PPP) The PPP content requirements can be found in County Code section 17-404. 1. [SWPPP] Provide a Pollution Prevention Plan exhibit outlining expected locations of construction staging, parking areas, expected pollutant sources and pollution prevention practices. Rev 2 — Addressed on plan sheet SW3 which is included in SWPPP. C. Stormwater Management Plan (SWMP) VSMP Regulation 9VAC25-870-108 requires the VSMP authority to approve or disapprove a SWMP. This plan is Approved contingent on purchase of 0.55 lbs of Nutrient Credits and recordation of deed of dedication/easement, and the reasons are provided in the comments below. The stormwater management plan content requirements can be found in County Code section 17-403. 1. [General] A stormwater management maintenance agreement, along with deed and plat for stormwater management easements encompassing both the proposed conserved forest and open space and the underground stormwater management facility, must be recorded prior to final VSMP approval. Contact Ana Kilmer, Management Analyst II, at (434) 296-5832 ex. 3246 for more information regarding the Stormwater Management Agreement. Rev 2 — Acknowledged. Easements/agreement under review. Rev 3 — SWM agreement recorded, Deed and PLAT under review 2. [General] Provide Pre -development dra...-, , _as. Rev 2 — Addressed. 3. [SW7] Please verify the correct drainage areas are represented in the VRRM spreadsheet. According to E&S narrative and presented drainage areas only 0.29 Ac will be protected as conserved forest and open space; however, this area is indicated as being 0.32 acres on the VRRM spreadsheet. Rev 2 — Addressed. 4. [SW7] Junction box and outlet structure details (diagrams 1&2) do not match what is presented on the structure profile and subsequent calculations. Please correct. Rev 2 — Addressed. 5. [SW7] Include long term maintenance notes for conserved forest and open space, level spreader, and underground stormwater management facility on plan sheet. Rev 2 — Addressed. Engineering Review Comments Page 3 of 4 6. [All] The SWPPP and plan sheets indicate that water quality requirements will be met through conservation of conserved open space; however, the E&S narrative and hydrologic/hydraulic calculation packet state that water quality requirements will be met through the purchase of offsite nutrient management credits. Please clarify how 0.471b/yr of phosphorous removal will be accounted for on site. Rev 2 — Clarified. Water quality with be addressed through the purchase of offsite water quality credits. 7. [Level Spreader] The level spreader appears to discharge water outside the parcel into areas not able to be included as conserved open space due to the lands not being owned by the parcel holder. The level spreader must discharge into areas that can be conserved as open space. Please correct or provide justification. Rev 2 — Withdrawn, forest and open space no longer used to meet water quality requirements. 8. [Level Spreader] The water authority must approve construction of stormwater features over water and sanitary sewer easements. Rev 2 — VSMP approval occurs prior to site plan approval. Please provide documentation of correspondence so that VSMP plan can be approved. Rev 3 - Acknowledged Additional Rev 2 Comments: With of SWM easement inadequate. Easement must be at least 30' in width (15' wide structure @ 9' depth max + V access on each side of the outer pipes, with 1:1 slopes from top of pipe to final grade level (6')). Rev 3 — Addressed. 2. Please amend the label for the stormwater facility easement to state "New variable width SWM Facility Easement" Rev 3 - Addressed 3. 0.55 lbs of Offsite Phosphorous Credit will need to be purchased prior to final VSMP approval. Rev 3 — Acknowledged. Water quality credits to be purchased once all technical comments are addressed. D. Erosion and Sediment Control Plan (ESCP) Virginia Code §62.1-44.15:55 requires the VESCP authority to approve or disapprove an ESCP. This plan is approved, and the reasons are provided in the comments below. The erosion control plan content requirements can be found in County Code section 17-402. 1. [Sequence of constructioiij indicate when demolition and initial grading activities will be occurring. Rev 2 — Addressed 2. [Section B 11 of E&S narrative] Maintenance schedule task #7 states removal of controls is contingent on approval of "city" E&S inspector. Please change this to "County E&S Inspector". Rev 2 — Addressed 3. [SW4 & SW5] Silt fence should be added along the southeast edge of the site. Rev 2 — Addressed 4. [SW8] Provide tree protection detail as specified in E&S plan. Rev 2 — Addressed Engineering Review Comments Page 4 of 4 Additional Rev 2 Comments: 1. Include all curbing/parking lot areas to be demolished for connection to adjacent parcel in demo plan. Rev 3 — Addressed. 2. Provide drop inlet protection detail such as Block and gravel Sediment Filter or other method. Currently curb inlet protection detail is included, when no curb inlets are to exist on site. Rev 3 - Addressed. 3. Ensure Phase II perimeter controls do not conflict installation of SWM facility. Rev 3 — Addressed. For final submittal please provide 4 copies of the plans with 2 copies of the SWPPP and 1 copy of the final calculations booklet with a completed application form. Ensure calculations booklet and SWPPP are signed and sealed by P.E. Process; After approval, plans will need to be bonded. The County's Management Analyst will prepare bond agreement forms, which will need to be completed by the owner and submitted along with cash, certificates or sureties for the amounts specified. The agreements will need to be approved and signed by the County Attorney and County Engineer. This may take 2-4 weeks to obtain all the correct signatures and forms. After bonding and agreements are complete, county staff will need to enter project information in a DEQ database for state application processing. DEQ will review the application information based on local VSMP authority approval. At this time, the DEQ portion of the application fees will need to be paid directly to the state. For fastest processing, this is done electronically with the emails provided on the application. DEQ should notify applicants with instructions on how to pay fees. When DEQ approves the application, they will issue a permit coverage letter. This should be copied to the county. After DEQ coverage is issued, via the coverage letter, the County can hold a pre -construction conference. Applicants will need to complete the request for a pre -construction conference form, and pay the remainder of the application fee. The form identifies the contractor and responsible land disturber, and the fee remaining to be paid. This will be checked by county staff, and upon approval, a pre -construction conference will be scheduled with the County inspector. At the pre -construction conference, should everything proceed satisfactorily, a joint VSMP and grading permit will be issued by the County so that work may begin. Bobby Jocz, EIT Civil Engineer I County of Albemarle Department of Community Development 401 McIntire Rd. Charlottesville, VA 22902 (434) 296-5832 ext: 3283 www.Albemarle.org �5 Dominion Engineering September 18, 2017 Mr. Bobby Jocz Department of Community Development 401 McIntire Road Charlottesville, VA 22902 172 South Pantops Drive Charlottesville, VA 22911 RE: WPO201700011 Meade Builders Office Building — VSMP Permit Plan Dear Mr. Jocz, 434.979.8121 (p) 434.979.1681 (f) DominionEng.com Please find attached two (2) copies of the revised Plans. The plans have been revised to address your comments received on 02/21/2017 in accordance with the following: A. Stormwater Pollution Prevention Plan (SWPPP) [General] Confirm accurate existing topography is provided. All topography should be at least visually field verified by the designer within the last year. Response: The topography was field verified by Dominion Engineering and Design, LLC on March 9th, 2017. The note on Sheet SW2 has been updated accordingly. 2. [General] Display extent of 1 00yr floodplain and WPO buffer (County Code 17-403(8)). Response: The 100yr floodplain and the WPO buffer lines have been added to the plan sheets 3. [General] Plans show construction/grading occurring on the adjacent parcel. Please include these parcels and owner's signature on future submittals, or obtain temporary construction easement. Response: As noted on the plan, TMP 78-15C2 and TMP 78-15C3 are both owned by Ballif Investments, LLC. We have added a temporary construction easement to be executed by the owners. 4. [SWPPP] Provide copy of DEQ coverage letter when obtained (County Code 17-4051. Response: Acknowledged 5. [SWPPP] Correct Table of Contents to reflect section headings in document. The SWPPP seems to be missing section 5 "Stormwater Management Plan", replacing it as the "Pollution Prevention Plan". Response: The section headings have been corrected. I of 5 �s ce o ��..,rs Dominion �? Engineering 0 s s 172 South Pantops Drive Charlottesville, VA 22911 434.979.8121 (p) 434.979.1681 (f) DominionEng.com 6. [SWPPP] The approved SWM plan will need to be included within the SWPPP when plans are ready to be approved (County Code 17-405). Response: Acknowledged. 7. [SWPPP] The approved Erosion and Sediment Control Plan will need to be included within the SWPPP when plans are ready to be approved (County Code 17-405}. Response: Acknowledged. 8. [SW1] Update plan sheets and SWPPP with current WPO submittal number [WP0201700011 ]. Response: The VSMP cover sheet and the SWPPP have been updated. 9. [SW5] Separate the SWM plan and E&S Phase II details on sheet SW5. The SWM plan should have its own sheet. Response: A detailed SWM detail showing grading and spot elevations have been added to sheet SW5. We have created separate sheets for the SWM details and E&S details. 10. [SW6] Remove the "Frame Shed" diagram located over the parking lot on the southeastern portion of the site. According to plans this will already be demolished. Response: The frame shed diagram has been removed from sheet SW6. 11. [SW8] Level spreader detail should be included as SWM detail, not on E&S detail sheet. Response: The level spreader detail has been moved to Sheet SW9. 12. [All] Please more clearly label proposed and existing contour elevations. Response: Existing and proposed contour elevations have been labeled more clearly. B. Pollution Prevention Plan (PPP) The PPP content requirements can be found in County Code section 17-404. [SWPPP] Provide a Pollution Prevention Plan exhibit outlining expected locations of construction staging, parking areas, expected pollutant sources and pollution prevention practices. 2 of 5 �5 CMZ ���5 Dominion Engineering 172 South Pantops Drive Charlottesville, VA 22911 434.979.8121 (p) 434.979.1681 (f) DominionEng.com Response: The Pollution Prevention Plan has been updated to include the PPP exhibit showing the required elements. C. Stormwater Management Plan (SWMP) VSMP Regulation 9VAC25-870-108 requires the VSMP authority to approve or disapprove a SWMP. This plan is disapproved, and the reasons are provided in the comments below. The stormwater management plan content requirements can be found in County Code section 17- 403. [General] A stormwater management maintenance agreement, along with deed and plat for stormwater management easements encompassing both the proposed conserved forest and open space and the underground stormwater management facility, must be recorded prior to final VSMP approval. Contact Ana Kilmer, Management Analyst II, at (434) 296-5832 ex. 3246 for more information regarding the Stormwater Management Agreement. Response: A stormwater management maintenance agreement will be provided under separate cover. Easements will be recorded prior to VSMP approval. [General] Provide Pre -development drainage areas. Response: Pre -Development areas have been added to sheet SW6 and SW7. [SW7] Please verify the correct drainage areas are represented in the VRRM spreadsheet. According to E&S narrative and presented drainage areas only 0.29 Ac will be protected as conserved forest and open space; however, this area is indicated as being 0.32 acres on the VRRM spreadsheet. Response: The areas have been updated to show 0.29 Acres. 4. [SW7] Junction box and outlet structure details (diagrams 1 &2) do not match what is presented on the structure profile and subsequent calculations. Please correct. Response: The outlet structure details have been updated and matched on all pertinent sheets. [SW7] Include long term maintenance notes for conserved forest and open space, level spreader, and underground stormwater management facility on plan sheet. Response: The maintenance notes have been added to cover sheet SWI. Please note that the applicant is not using conserved open space to meet water quality because the slope in this area is above the maximum allowable in the DEQ specifications. 3 of 5 �s ce ops Dominion Engineering 172 South Pantops Drive Charlottesville, VA 22911 434.979.8121 (p) 434.979.1681 (f) DominionEng.com [All] The SWPPP and plan sheets indicate that water quality requirements will be met through conservation of conserved open space; however, the E&S narrative and hydrologic/hydraulic calculation packet state that water quality requirements will be met through the purchase of offsite nutrient management credits. Please clarify how 0.47 Ib/yr of phosphorous removal will be accounted for on site. Response: The applicant has chosen to purchase offsite credits to satisfy the water quality portion of the VRRM. The SWPPP plan sheets have been updated to reflect this. Please also refer to response to comment #5. 7. [Level Spreader] The level spreader appears to discharge water outside the parcel into areas not able to be included as conserved open space due to the lands not being owned by the parcel holder. The level spreader must discharge into areas that can be conserved as open space. Please correct or provide justification. Response: We are not claiming any Water Quality credits for outflow the level spreader. The level spreader does not have to discharge on to conserved open space, as it is being used to mimic pre -development conditions at the current site outfall. 8. [Level Spreader] The water authority must approve construction of stormwater features over water and sanitary sewer easements. Response: The ACSA has approved the level spreader in discussions. ACSA approval will be provided prior to Site Plan approval. D. Erosion and Sediment Control Plan (ESCP) Virginia Code §62.1-44.15:55 require the VESCP authority to approve or disapprove an ESCP. This plan is disapproved, and the reasons are provided in the comments below. The erosion control plan content requirements can be found in County Code section 17-402. 1. [Sequence of construction] Indicate when demolition and initial grading activities will be occurring. * Response: The sequence has been updated. Demolition activities are expected to begin 10/1/17. 2. [Section 1311 of E&S narrative] Maintenance schedule task #7 states removal of controls is contingent on approval of "city" E&S inspector. Please change this to "County E&S Inspector". t / Ott"/ � Response: The sequence has been updated. [SW4 & SW51 Silt fence should be added along the southeast edge of the site 4 of 5 A PJ cs e ois Dominion Engineering 172 South Pantops Drive Charlottesville, VA 22911 434.979.8121 (p) 434.979.1681 (f) DominionEng.com Response: A silt fence has been added to the Southeast edge of the property. ► I 4. [SW8] Provide tree protection detail as specified in E&S plan. Response: A tree protection detail has been added to sheet SW8. oYv We thank you for taking the time to review these plans and trust the above adequately addresses your comments. However, please let me know if you have any questions or require additional information. Very Michllyers, PE, CFM Charlie Armstrong 5 of 5 �5 Oz's Dominion y Engineering 172 South Pantops Drive Charlottesville, VA 22911 434.979.8121 (p) 434.979.1681 (f) DominionEng.com D. Erosion and Sediment Control Plan (ESCP) Virginia Code §62.1-44.15:55 require the VESCP authority to approve or disapprove an ESCP. This plan is disapproved, and the reasons are provided in the comments below. The erosion control plan content requirements can be found in County Code section 17-402. Include all curbing/parking lot areas to be demolished for connection to adjacent parcel in demo plan. Response: All curbing/parking lot areas to be demolished have been added to the demo plan. 2. Provide drop inlet protection detail such as Block and gravel Sediment Filter or other method. Currently curb inlet protection detail is included, when no curb inlets are to exist on site. Response: Drop inlet protection detail has been added to sheet SW8. 3. Ensure Phase II perimeter controls do not conflict installation of SWM facility. Response: Phase II perimeter controls have been adjusted to not conflict with the installation of SWM Facility. We thank you for taking the time to review these plans and trust the above adequately addresses your comments. However, please let me know if you have any questions or require additional information. Cc' Charlie Armstrong 2 of 2 COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road, Room 227 Charlottesville, Virginia 22902-4596 Phone (434) 296-5832 Fax (434) 972-4126 VSMP Permit plan review Project title: Meade Builders Office Building Project file number: WP0201700011 Plan preparer: Dustin Greene, Dominion Engineering [dgreene@dominionemg.com] Owner or rep.: Charlie Armstrong, Ballif Investments, LLC [CharlesA@southern-development.com] Plan received date: Rev 1 — 6 Feb. 2017 Rev 2 — 20 August 2017 Date of comments: Rev 1 — 21 Feb. 201 Rev 2 —12 September 2017 Reviewers: Rev 1 — Bobby Jocz Rev 2 — Bobby Jocz County Code section 17-410 and Virginia Code §62.1-44.15:34 requires the VSMP authority to act on any VSMP permit by issuing a project approval or denial. This project is denied. The rationale is given in the comments below. The application may be resubmitted for approval if all of the items below are satisfactorily addressed. The VSMP application content requirements can be found in County Code section 17-401. A. Stormwater Pollution Prevention Plan (SWPPP) The SWPPP content requirements can be found in County Code section 17-405. A SWPPP must contain (1) a PPP, (2) an ESCP, (3) a SWMP, and (4) any TMDL measures necessary. [General] Confirm accurate existing topography is provided. All topography should be at least visually field verified by the designer within the last year. Rev 2 — Addressed. 2. [General] Display extent of 100yr floodplain and WPO buffer {County Code 17-403(8)1. Rev 2 — Addressed. 3. [General] Plans show construction/grading occurring on the adjacent parcel. Please include these parcels and owner's signature on future submittals, or obtain temporary construction easement. Rev 2 — Addressed. 4. [SWPPP] Provide copy of DEQ coverage letter when obtained {County Code 17-405}. Rev 2 — Acknowledged. 5. [SWPPP] Correct Table of Contents to reflect section headings in document. The SWPPP seems to be missing section 5 "Stormwater Management Plan", replacing it as the "Pollution Prevention PI"', Rev 2 — Addressed. 6. [5 wrrrl i ne approved SWM plan will need to be included within the SWPPP when plans are ready to be approved {County Code 17-405}. Rev 2 — Acknowledged. Engineering Review Comments Page 2 of 4 7. [SWPPP]The approved Erosion and Sediment Control Plan will need to be included within the SWPPP when plans are ready to be approved {County Code 17-4051. Rev 2 - Acknowledged. 8. [SW 1] Update plan sheets and SWPPP with current WPO submittal number [WPO20170001 I] Rev 2 — Addressed. 9. [SW5] Separate the SWM plan and E&S Phase II details on sheet SW5. The SWM plan should have its own sheet. Rev 2 — Addressed. 10. [SW6] Remove the "Frame Shed" diagram located over the parking lot on the southeastern portion of the site. According to plans this will already be demolished. Rev 2 — Addressed. It. [SW8] Level spreader detail should be included as SWM detail, not on E&S detail sheet. Rev 2 — Addressed. 12. [All] Please more clearly label proposed and existing contour elevations. Rev 2 — addressed. B. Pollution Prevention Plan (PPP) The PPP content requirements can be found in County Code section 17-404. 1. [SWPPP] Provide a Pollution Prevention Plan exhibit outlining expected locations of construction staging, parking areas, expected pollutant sources and pollution prevention practices. Rev 2 — Addressed on plan sheet SW3 which is included in SWPPP. C. Stormwater Management Plan (SWMP) VSMP Regulation 9VAC25-870-108 requires the VSMP authority to approve or disapprove a SWMP. This plan is disapproved, and the reasons are provided in the comments below. The stormwater management plan content requirements can be found in County Code section 17-403. 1. [General] A stormwater management maintenance agreement, along with deed and plat for stormwater management easements encompassing both the proposed conserved forest and open space and the underground stormwater management facility, must be recorded prior to final VSMP approval. Contact Ana Kilmer, Management Analyst II, at (434) 296-5832 ex. 3246 for more information regarding the Stormwater Management Agreement. Rev 2 — Acknowledged. Easements/agreement under review. 2. [General] Provide Pre -development drainage areas. Rev 2 — Addressed. 3. [SW7] Please verify the correct drainage areas are represented in the VRRM spreadsheet. According to E&S narrative and presented drainage areas only 0.29 Ac will be protected as conserved forest and open space; however, this area is indicated as being 0.32 acres on the VRRM spreadsheet. Rev 2 — Addressed. 4. [SW7] Junction box and outlet structure details (diagrams 1&2) do not match what is presented on the structure profile and subsequent calculations. Please correct. Rev 2 — Addressed. 5. [SW7] Include long term maintenance notes for conserved forest and open space, level spreader, and underground stormwater management facility on plan sheet. Rev 2 — Addressed. 6. [All] The SWPPP and plan sheets indicate that water quality requirements will be met through conservation of conserved open space; however, the E&S narrative and hydrologic/hydraulic calculation packet state that water quality requirements will be met through the purchase of offsite Engineering Review Comments Page 3 of 4 nutrient management credits. Please clarify how 0.47lb/yr of phosphorous removal will be accounted for on site. Rev 2 — Clarified. Water quality with be addressed through the purchase of offsite water quality credits. [Level Spreader] The level spreader appears to discharge water outside the parcel into areas not able to be included as conserved open space due to the lands not being owned by the parcel holder. The level spreader must discharge into areas that can be conserved as open space. Please correct or provide justification. Rev 2 — Withdrawn, forest and open space no longer used to meet water quality requirements. [Level Spreader] The water authority must approve construction of stormwater features over water and sanitary sewer easements. Rev 2 — VSMP approval occurs prior to site plan approval. Please provide documentation of correspondence so that VSMP plan can be approved. Additional Rev 2 Comments: 1. With of SWM easement inadequate. Easement must be at least 30' in width (15' wide structure @ 9' depth max + V access on each side of the outer pipes, with 1:1 slopes from top of pipe to final grade level (6')). 2. Please amend the label for the stormwater facility easement to state "New variable width SWM Facility Easement" 3. 0.55 lbs of Offsite Phosphorous Credit will need to be purchased prior to final VSMP approval. D. Erosion and Sediment Control Plan (ESCP) Virginia Code §62.1-44.15:55 requires the VESCP authority to approve or disapprove an ESCP. This plan is disapproved, and the reasons are provided in the comments below. The erosion control plan content requirements can be found in County Code section 17-402. 1. [Sequence of construction] Indicate when demolition and initial grading activities will be occurring. Rev 2 — Addressed 2. [Section B 11 of E&S narrative] Maintenance schedule task #7 states removal of controls is contingent on approval of "city" E&S inspector. Please change this to "County E&S Inspector". Rev 2 — Addressed 3. [SW4 & SW5] Silt fence should be added along the southeast edge of the site. Rev 2 — Addressed 4. [SW8] Provide tree protection detail as specified in E&S plan. Rev 2 — Addressed Additional Rev 2 Comments: 1. Include all curbing/parking lot areas to be demolished for connection to adjacent parcel in demo plan. 2. Provide drop inlet protection detail such as Block and gravel Sediment Filter or other method. Currently curb inlet protection detail is included, when no curb inlets are to exist on site. 3. Ensure Phase II perimeter controls do not conflict installation of SWM facility. Engineering Review Comments Page 4 of 4 The VSMP permit application and all plans may be resubmitted for approval when all comments have been satisfactorily addressed. For re -submittals please provide 2 copies of the complete permit package with a completed application form. Engineering plan review staff are available from 2-4 PM on Thursdays, should you require a meeting to discuss this review. Process; After approval, plans will need to be bonded. The bonding process is begun by submitting a bond estimate request form and fee to the Department of Community Development. One of the plan reviewers will prepare estimates and check parcel and easement information based on the approved plans. The County's Management Analyst will prepare bond agreement forms, which will need to be completed by the owner and submitted along with cash, certificates or sureties for the amounts specified. The agreements will need to be approved and signed by the County Attorney and County Engineer. This may take 2-4 weeks to obtain all the correct signatures and forms. After bonding and agreements are complete, county staff will need to enter project information in a DEQ database for state application processing. DEQ will review the application information based on local VSMP authority approval. At this time, the DEQ portion of the application fees will need to be paid directly to the state. For fastest processing, this is done electronically with the emails provided on the application. DEQ should notify applicants with instructions on how to pay fees. When DEQ approves the application, they will issue a permit coverage letter. This should be copied to the county. After DEQ coverage is issued, via the coverage letter, the County can hold a pre -construction conference. Applicants will need to complete the request for a pre -construction conference form, and pay the remainder of the application fee. The form identifies the contractor and responsible land disturber, and the fee remaining to be paid. This will be checked by county staff, and upon approval, a pre -construction conference will be scheduled with the County inspector. At the pre -construction conference, should everything proceed satisfactorily, a joint VSMP and grading permit will be issued by the County so that work may begin. County forms can be found on the county website forms center under engineering; httD://www.albemarle.oriz/deDtforms.asD?deDartment--cdenizwDo Bobby Jocz, EIT Civil Engineer I County of Albemarle Department of Community Development 401 McIntire Rd. Charlottesville, VA 22902 (434) 296-5832 ext: 3283 www.Albemarle.org COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road, Room 227 Charlottesville, Virginia 22902-4596 Phone (434) 296-5832 Fax (434) 972-4126 VSMP Permit plan review Project title: Dominion Office Park Project file number: WP0201700011 Plan preparer: Dustin Greene [dgreene@dominionemg.com] Owner or rep.: Ballif Investments, LLC. Plan received date: 6 Feb. 2017 Date of comments: 21 Feb. 2017 Reviewers: Bobby Jocz [Rev -1] County Code section 17-410 and Virginia Code §62.1-44.15:34 requires the VSMP authority to act on any VSMP permit by issuing a project approval or denial. This project is denied. The rationale is given in the comments below. The application may be resubmitted for approval if all of the items below are satisfactorily addressed. The VSMP application content requirements can be found in County Code section 17-401. A. Stormwater Pollution Prevention Plan (SWPPP) The SWPPP content requirements can be found in County Code section 17-405. A SWPPP must contain (1) a PPP, (2) an ESCP, (3) a SWMP, and (4) any TMDL measures necessary. 1. [General] Confirm accurate existing topography is provided. All topography should be at least visually field verified by the designer within the last year. 2. [General] Display extent of 100yr floodplain and WPO buffer {County Code 17-403(8)1. 3. [General] Plans show construction/grading occurring on the adjacent parcel. Please include these parcels and owner's signature on future submittals, or obtain temporary construction easement. 4. [SWPPP] Provide copy of DEQ coverage letter when obtained {County Code 17-405 1. 5. [SWPPP] Correct Table of Contents to reflect section headings in document. The SWPPP seems to be missing section 5 "Stormwater Management Plan", replacing it as the "Pollution Prevention Plan". 6. [SWPPP]The approved SWM plan will need to be included within the SWPPP when plans are ready to be approved {County Code 17-405}. 7. [SWPPP]The approved Erosion and Sediment Control Plan will need to be included within the SWPPP when plans are ready to be approved {County Code 17-405}. 8. [SWI] Update plan sheets and SWPPP with current WPO submittal number [WP020170001I 9. [SW5] Separate the SWM plan and E&S Phase II details on sheet SW5. The SWM plan should have its own sheet. 10. [SW6] Remove the "Frame Shed" diagram located over the parking lot on the southeastern portion of the site. According to plans this will already be demolished. 11. [SW8] Level spreader detail should be included as SWM detail, not on E&S detail sheet. 12. [All] Please more clearly label proposed and existing contour elevations. Engineering Review Comments Page 2 of 3 B. Pollution Prevention Plan (PPP) The PPP content requirements can be found in County Code section 17-404. 1. [SWPPP] Provide a Pollution Prevention Plan exhibit outlining expected locations of construction staging, parking areas, expected pollutant sources and pollution prevention practices. C. Stormwater Management Plan (SWMP) VSMP Regulation 9VAC25-870-108 requires the VSMP authority to approve or disapprove a SWMP. This plan is disapproved, and the reasons are provided in the comments below. The stormwater management plan content requirements can be found in County Code section 17-403. 1. [General] A stormwater management maintenance agreement, along with deed and plat for stormwater management easements encompassing both the proposed conserved forest and open space and the underground stormwater management facility, must be recorded prior to final VSMP approval. Contact Ana Kilmer, Management Analyst II, at (434) 296-5832 ex. 3246 for more information regarding the Stormwater Management Agreement. 2. [General] Provide Pre -development drainage areas. 3. [SW7] Please verify the correct drainage areas are represented in the VRRM spreadsheet. According to E&S narrative and presented drainage areas only 0.29 Ac will be protected as conserved forest and open space; however, this area is indicated as being 0.32 acres on the VRRM spreadsheet. 4. [SW7] Junction box and outlet structure details (diagrams 1&2) do not match what is presented on the structure profile and subsequent calculations. Please correct. 5. [SW7] Include long term maintenance notes for conserved forest and open space, level spreader, and underground stormwater management facility on plan sheet. 6. [All] The SWPPP and plan sheets indicate that water quality requirements will be met through conservation of conserved open space; however, the E&S narrative and hydrologic/hydraulic calculation packet state that water quality requirements will be met through the purchase of offsite nutrient management credits. Please clarify how 0.47lb/yr of phosphorous removal will be accounted for on site. 7. [Level Spreader] The level spreader appears to discharge water outside the parcel into areas not able to be included as conserved open space due to the lands not being owned by the parcel holder. The level spreader must discharge into areas that can be conserved as open space. Please correct or provide justification. 8. [Level Spreader] The water authority must approve construction of stormwater features over water and sanitary sewer easements. D. Erosion and Sediment Control Plan (ESCP) Virginia Code §62.1-44.15:55 requires the VESCP authority to approve or disapprove an ESCP. This plan is disapproved, and the reasons are provided in the comments below. The erosion control plan content requirements can be found in County Code section 17-402. 1. [Sequence of construction] Indicate when demolition and initial grading activities will be occurring. 2. [Section B 11 of E&S narrative] Maintenance schedule task #7 states removal of controls is contingent on approval of "city" E&S inspector. Please change this to "County E&S Inspector". 3. [SW4 & SW5] Silt fence should be added along the southeast edge of the site. 4. [SW8] Provide tree protection detail as specified in E&S plan. Engineering Review Comments Page 3 of 3 The VSMP permit application and all plans may be resubmitted for approval when all comments have been satisfactorily addressed. For re -submittals please provide 2 copies of the complete permit package with a completed application form. Engineering plan review staff are available from 2-4 PM on Thursdays, should you require a meeting to discuss this review. Process; After approval, plans will need to be bonded. The bonding process is begun by submitting a bond estimate request form and fee to the Department of Community Development. One of the plan reviewers will prepare estimates and check parcel and easement information based on the approved plans. The County's Management Analyst will prepare bond agreement forms, which will need to be completed by the owner and submitted along with cash, certificates or sureties for the amounts specified. The agreements will need to be approved and signed by the County Attorney and County Engineer. This may take 2-4 weeks to obtain all the correct signatures and forms. After bonding and agreements are complete, county staff will need to enter project information in a DEQ database for state application processing. DEQ will review the application information based on local VSMP authority approval. At this time, the DEQ portion of the application fees will need to be paid directly to the state. For fastest processing, this is done electronically with the emails provided on the application. DEQ should notify applicants with instructions on how to pay fees. When DEQ approves the application, they will issue a permit coverage letter. This should be copied to the county. After DEQ coverage is issued, via the coverage letter, the County can hold a pre -construction conference. Applicants will need to complete the request for a pre -construction conference form, and pay the remainder of the application fee. The form identifies the contractor and responsible land disturber, and the fee remaining to be paid. This will be checked by county staff, and upon approval, a pre -construction conference will be scheduled with the County inspector. At the pre -construction conference, should everything proceed satisfactorily, a joint VSMP and grading permit will be issued by the County so that work may begin. County forms can be found on the county website forms center under engineering; httD://www.albemarle.oriz/deDtforms.asD?deDartment--cdenizwDo Bobby Jocz, EIT Civil Engineer I County of Albemarle Department of Community Development 401 McIntire Rd. Charlottesville, VA 22902 (434) 296-5832 ext: 3283 www.Albemarle.org feiP,7* Ircrett COUNTY OF ALBEMARLE Department of Community Development 401 McIntire Road,Room 227 Charlottesville,Virginia 22902-4596 Phone(434)296-5832 Fax(434)972-4126 VSMP Permit plan review Project title: Dominion Office Park Project file number: WP0201700011 Plan preparer: Dustin Greene [dgreene@dominionemg.com] Owner or rep.: Ballif Investments,LLC. Plan received date: 6 Feb 2017 Date of comments: 17 Feb 2017 Reviewers: Bobby Jocz [Rev-1] County Code section 17-410 and Virginia Code §62.1-44.15:34 requires the VSMP,authority to act on any VSMP permit by issuing a project approval or denial. This project is denied. The rationale is given in the comments below. The application may be resubmitted for approval if all of the items below are satisfactorily addressed. The VSMP application content requirements can be found in County Code section 17-401. A. Stormwater Pollution Prevention Plan(SWPPP) The SWPPP content requirements can be found in County Code section 17-405. A SWPPP must contain(1)a PPP,(2)an ESCP, (3)a SWMP, and(4)any TMDL measures necessary. 1. [General] Confirm accurate existing topography is provided. All topography should be at least visually field verified by the designer within the last year. / 2. [General] Display extent of 100yr floodplain and WPO buffer {County Code 17-403(8)}. ,/ 3. [General] Plans show construction/grading occurring on the adjacent parcel. Please include these parcels and owner's signature on future submittals,or obtain temporary construction easement. 4. [SWPPP] Provide copy of DEQ coverage letter when obtained {County Code 17-405}. ✓ 5. [SWPPP] Correct Table of Contents to reflect section headings in document. The SWPPP seems to be missin section 5 "Stormwater Management Plan",replacing it as the"Pollution Prevention Plan". 6. [SWPPP]The approved SWM plan will need to b -included within the SWPPP when plans are ready to be approved {County Code 17-405}.�/ 7. [SWPPP]The approved Erosion and Sediment Control Plan will need tol‘yitiuded within the SWPPP when plans are ready to be approved {County Code 17-405}. 8. [SW1] Update plan sheets and SWPPP with current WPO submittal number[WPO201700011] 9. [SW5] Separate the SW)I plan and E&S Phase II details on sheet SW5. The SWM plan should have its own sheet. 10. [SW6]Remove the"Frame Shed"diagram located over the parking lot on the southeastern portion of the site. According to plans this will already be demolished. 11. [SW8] Level spreader detail should be included as SWM detail,not on E&S detail sheet. 12. [All] Please more clearly label proposed and existing contour elevations. .- Lew) 61404v dors Moi- cAti 'io op" refffid 41,04""-- oyer/ .5,r't7/ ' 1.4440-440- 014110(1.1) 11a 411,444- +O <o� / Engineering Review Comments Page 2 of 3 B. Pollution Prevention Plan(PPP) The PPP content requirements can be found in County Code section 17-404. 1. [SWPPP] Provide a Pollution Prevention Plan exhibit outlining expected locations of construction staging,parking areas,expected pollutant sources and pollution prevention practices. C. Stormwater Management Plan(SWMP) VSMP Regulation 9VAC25-870-108 requires the VSMP authority to approve or disapprove a SWMP. This plan is disapproved,and the reasons are provided in the comments below. The stormwater management plan content requirements can be found in County Code section 17-403. 1. [General] A stormwater management maintenance agreement, along with deed and plat for stormwater management easements encompassing both the proposed conserved forest and open space and the underground stormwater management facility,must be recorded prior to final VSMP approval. Contact Ana Kilmer,Management Analyst II,at(434)296-5832 ex. 3246 for more informationl. ?ADN' Aebmtm', 2. [General] Provale Pre-development drainage areas. 3. [SW7] Please verify the correct drainage areas are represented in the VRRM spreadsheet. According to E&S narrative and presented drainage areas only 0.29 Ac will be protected as conserved forest and open space;however,this area is indicated as being 0.32 acres on the VRRM spreadsheet.✓ 4. [SW7] Junction box and outlet structure details(diagrams 1&2)do not match what is presented on the structure profile and subsequent calculations. Please correct. 5. [SW7] Include long term maintenance notes for conserved forest and open space, level spreader, and underground stormwater management facility on plan sheet. 6. [All] The SWPPP and plan sheets indicate that water quality requirements will be met through conservation of conserved open space;however,the E&S narrative and hydrologic/hydraulic calculation packet state that water quality requirements will be met through the purchase of offsite nutrient management credits. Please clarify how 0.471b/yr of phosphorous removal will be accounted for on site. D. Erosion and Sediment Control Plan(ESCP) Virginia Code §62.1-44.15:55 requires the VESCP authority to approve or disapprove an ESCP. This plan is disapproved,and the reasons are provided in the comments below. The erosion control plan content requirements can be found in County Code section 17-402. 1. [Sequence of construction] Indicate when demolition and initial grading activities will be occurring. Overall,would like to see a little more detail. 2. [Section B11 of E&S narrative]Maintenance schedule task#7 states removal of controls is contingent on approval of"city"E&S inspector. Please change this to"County E&S Inspector". 3. [SW4& SW5] Silt fence should be added along the southeast edge of the site. 4. [SW8]Provide tree protection detail as specified in E&S plan. The VSMP permit application and all plans may be resubmitted for approval when all comments have been satisfactorily addressed. For re-submittals please provide 2 copies of the complete permit package with a completed application form. Engineering plan review staff are available from 2-4 PM on Thursdays, should you require a meeting to discuss this review. .c sA- 7c 'Z ‘`I <-.7- SI, t 1 1 %C:1 41\ 1 ki--- A f t t 1 z- _ . k,,, ,- , _ - U.► N -"Z H O C) O s _...1 .-ett, 1 t : • w tJ ) d Cil -4--;\ 'A tat N zs N ti I ' 1 ti\ X ),(e ,...,vo 5} .34. iS Si t tl" ," 1 oo 4 0 c►t • I -I- NI-i) Q _ -. °` a i 1 -Ni 1 ..... i t*) \ trt ci4 N- 0.' ‘ .J n ciN be., U 1 c :'0l3