HomeMy WebLinkAboutSDP201300064 Review Comments Letter of Revision 1 2017-10-27COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road, North Wing
Charlottesville, Virginia 22902-4596
Phone (434) 296-5832 Fax (434) 972-4126
August 16, 2017
REVISED: October 27, 2017
Geoff Kilmer
700 Rio Road West
Charlottesville, VA 22901
VIA EMAIL TO: eg oft2photoworks rg_oup.com
RE: LOR#1 for SDP-2013-00064 — Church of Our Savior — First Revision Comments (Revised 10/27/2017)
Tax Map/Parcel #06100-00-00-14400
Mr. Kilmer,
This letter contains review comments for your submitted Letter of Revision for the above referenced site plan.
Please provide revised drawings that demonstrate compliance with the reviewer comments.
This is the first (1st) Letter of Revision for this site. Three (3) Letters of Revision are allowed, after which all
required changes must submitted in the form of a site plan amendment.
Sincerely,
Llu ��w
Cameron Langille
Senior Planner
County of Albemarle
Department of Community Development
blan ig lle@albemarle.org
Phone: (434)296-5832 Ext 3432
Albemarle County Planning Services (Planner) — Cameron Langille, blan ig llena,albemarle.org — Requested changes:
1. [General Comment] The lighting plan approved with final site plan showed a total of thirty-eight (38) luminaires
being installed on site. Please verify that the letter of revision is intended to fully replace the previously approved
lighting plan, and that only five (5) luminaires will be installed. Rev. 1: Comment addressed.
2. [4.17.4 (a)(1)] Page 2 of the letter of revision does not contain a cut sheet for either type of proposed light. Please
provide the manufacturer cut -sheet that identifies and shows all luminaire specifications, features, and photometry
data for both proposed fixture types. Rev. 1: Please amend the "Total Lamp Lumens" column on Sheet 2 to
state the lumens for the luminaire. Per ARB comments (attached) all proposed luminaires must have a LLF
factor of 1.0.
a. Please state the proposed height of each luminaire on Page 2. Rev.1: In the Luminaire Schedule on
Sheet 2, please add a column stating the pole heights. Applicant response to first review stated that
all luminaries will be 20' in height.
[4.17] The symbology used for each light is identical and staff cannot distinguish between the two on Page 1. Please
use a different symbology and identify each ficture as "Fixture A" and "Fixture B" in the luminaire schedule on
page 2. Rev. 1: Comment addressed. This comment was made because the Luminaire Schedule on Sheet 2
states that four (4) luminaires are proposed for the first model, and one (1) luminaire is proposed for the
second model. It appears they are the same model type with different wattage outputs based on the "Label"
column in the Luminaire Schedule. The revised layout plan dated 7-11-2017 now shows only 5 luminaires of
the same model.
4. [4.17.4 (a)] Each outdoor luminaire exceeding 3,000 lumens is required to be feature a full -cutoff shield. Rev. 1:
The cutsheets submitted with the revised drawings are unclear as to whether full -cutoff shields will be
installed with each luminaire. Please highlight or identify the specific sections on the cutsheets that
demonstrate that full -cutoff shields will be installed with the luminaires.
a. Please amend the note on Page 2 to state "Each outdoor luminaire equipped with a lamp that emits 3,000
or more initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to reflect light away
from adjoining residential districts and adjacent roads. The spillover of lighting from luminaires onto public
roads and property in residential or rural areas zoning districts shall not exceed one-half footcandle." Rev.
1: The above statement is required on the plans, please remove the note under the Luminaire
Schedule which states "Shields available upon request" and replace with the above language,
b. Please provide the lumens for the first luminaire model identified in the luminaire schedule on Page 2. It
currently says ' N/A." Rev. 1: Please refer to comment #2 above.
5. [4.17.4 (a)(2)] In the luminaire schedule on Page 2, please identify the lamp type (i.e. LED, high pressure sodium,
etc.). Rev. 1: The revised drawings did not include this column as requested. Please include in the Luminaire
Schedule on Sheet 2.
6. [4.17.4 (b)(1)] The spillover of lighting from luminaires onto public roads and property in residential or rural areas
zoning districts shall not exceed one-half (%2) foot candle. Page 1 shows the northernmost luminaire being installed
inside of the R2 zoning district on the property, but the footcandle measurements provided do not go all the way to
the zoning district boundary. Please provide confirmation that the footcandle measurements at and within the R2
district boundary do not exceed one-half footcandle. The luminaire may need to be relocated to a different location
in order to comply with this requirement. Rev. 1: Per applicant response to first review comments, the zoning
standard applies to the footcandle measurement at the zoning district boundaries. Even though the site is all one
property, the maximum footcandle measurement allowed at the R2 zoning district boundary is 0.5 footcandles. As
was stated in the applicant response, staff concurs with the applicant's proposal to move the light into the C 1 zoning
district portion of the property. Please show footcandle measurements along the zoning district boundary line on
Sheet 1 to verify compliance with the standard. REVISED 10-27-2017: Comment has been addressed on the
revised drawings dated 7/17/2017. The footcandle measurement for lighting spillover shall be measured
"shall be measured horizontally and vertically at the property line or edge ofright-of-way or easement, whichever
is closer to the light source" in accordance with Section 18-4.17.4 (b)(1). The luminaire shown in the R2
portion of the property may remain in the proposed location.
Architectural Review Board (ARB) Planner Comments — Margaret Maliszewski, mmaliszewski@albemarle.org —
Requested Changes:
1. To meet ordinance requirements, the LLF must equal 1.0. Please revise accordingly.
2. Add the standard lighting note to the plan: Each outdoor lummaire equipped with a lamp that emits 3,000 or more
initial lumens shall be a full cutoff luminaire and shall be arranged or shielded to reflect light away from adjoining
residential districts and away from adjacent roads. The spillover of lighting from luminaires onto public roads and
property in residential or rural areas zoning districts shall not exceed one-half footcandle.