December 21, 2017
Seth Maughan
Solunesco, LLC
1818 Library Street, Suite 500
Reston, VA 20190
RE: ARB-2017-96: Rivanna Solar
Dear Seth,
The Albemarle County Architectural Review Board, at its meeting on Monday, December 18, 2017,
completed an advisory review of the above -noted request to establish a solar -energy electrical generation
facility. The Board, by a vote of 4:0, forwarded the following recommendation to the Planning Commission
and Board of Supervisors:
Solar panels are considered equipment. The Entrance Corridor design guidelines state that equipment should
be located to eliminate visibility from the EC; if, after appropriate siting, these features will have a negative
visual impact, then screening should be provided to eliminate visibility. These guidelines primarily were meant
to address mechanical equipment associated with buildings; they were not intended to address a solar -energy
electrical generation facility of this scale. The ARB has not had the opportunity to establish guidelines specific
to such a facility to date. Consequently, the ARB offers the following advice.
As currently proposed, even with the considerable landscape screening proposed along the portion of the
development adjacent to the EC, and with the 35' buffer of retained young pines in other locations, portions of
the solar installation will be visible from the EC. These views are not expected to be open, sustained views,
which is a positive factor. At the completion of construction, and for a period oftime, it is anticipated that there
will be a degree of visibility of the installation through the young screening buffers adjacent to the EC. Other
views will be at distances of at least 500' through parcels currently developed with residences, outbuildings,
and/or wooded areas. Other views will be fully screened by off -site wooded areas, most of which is not
controlled by the applicant. Because views of the facility will be available, the proposal does not meet the EC
guidelines related to eliminating visibility of equipment. To eliminate all visibility, a significant amount of
additional landscaping (and/or major changes to grading and/or size of the solar field) would need to be
employed. It is likely that these alternatives are impractical. The revisions to the concept plan listed in Al,
below, and the conditions on the Special Use Permit in B 1, below, are recommended, with the understanding
that there will be some visibility of the development from the Entrance Corridor. If maximizing screening to
better match the equipment screening guidelines is the goal, the changes in A2 and the conditions in B2 would
be appropriate. However, they may be impractical for a project of this scale and would still not meet the goal of
complete screening.
Al. Required changes to the plan (to further reduce visibility)
1. Revise the landscape plan to eliminate conflicts among trees, utilities, easements, and rights -of -way.
Screening shall have height differentiation and should incorporate understory plants to mitigate
visibility. Shorter plants shall be planted as close to the EC as possible without conflicting with utility
and other easements, followed by mid -sized and large trees. Some interspersed deciduous plants are
acceptable, but the majority shall be evergreen. Show the planting height for at least 30 ofthe large EC
buffer trees to be 7' minimum.
2. Revise the Conceptual Layout (sheet 1 of 2) to show the development area in the northeastern arm
pulled back to align with the property line shared by parcels 47J and 47M. Show that existing
vegetation north and east of this line shall be preserved.
3. At the west end of the EC buffer, add trees at the corner to increase screening and mitigate visibility.
4. Revise the easement documents to reference the appropriate parcels, to clearly show the tree
preservation area, and to indicate that neither the owner nor the tenant will remove trees from the
designated preservation area.
5. Clarify on the plan the location of wetlands and associated wooded area described in 5.3.3.
6. Revise the decommissioning plan to eliminate the option to retain the chain link fence.
Bl. Recommendation on the Special Use Permit
The ARB recommends the following conditions:
1. The Entrance Corridor landscape buffer plan is subject to ARB review/approval. At least 30 of the
large trees in the EC buffer shall be 7' high minimum at planting.
2. All inverter/transformer stations shall be located at least 700' from the EC edge of pavement.
3. All chain link fencing shall be removed from the development at decommissioning.
4. Revise the easement documents to reference the appropriate parcels, to clearly show the tree
preservation area, and to indicate that neither the owner nor the tenant will remove trees from the
designated preservation area.
5. The northeastern limit of the development area shall align with the property line shared by parcels 47J
and 47M. Existing vegetation north and east of this line shall be preserved.
A2. Required changes to the plan (to attempt to eliminate visibility)
1. Revise the landscape plan to eliminate conflicts among trees, utilities, easements, and rights -of -way.
Screening shall have height differentiation and should incorporate understory plants to mitigate
visibility. Shorter plants shall be planted as close to the EC as possible without conflicting with utility
and other easements, followed by mid -sized and large, trees. Some interspersed deciduous plants are
acceptable, but the majority shall be evergreen. Show the planting height for at least 30 ofthe large EC
buffer trees to be 7' minimum.
2. Revise the Conceptual Layout (sheet 1 of 2) to show the development area in the northeastern arm
pulled back to align with the property line shared by parcels 47J and 47M. Show that existing
vegetation north and east of this line shall be preserved.
3. At the west end of the EC buffer, add trees at the corner to increase screening and mitigate visibility.
4. Revise the easement documents to reference the appropriate parcels, to clearly show the tree
preservation area, and to indicate that neither the owner nor the tenant will remove trees from the
designated preservation area.
5. Clarify on the plan the location of wetlands and associated wooded area described in 5.3.3.
6. Revise the decommissioning plan to eliminate the option to retain the chain link fence.
7. Revise the concept plan to show that on -site landscape buffers will be extended along property lines
adjacent to parcels 47A, 47E, 47J, 47L and 47M.
B2. Recommendation on the Special Use Permit
The ARB recommends the following conditions:
1. The Entrance Corridor landscape buffer plan is subject to ARB review/approval. At least 30 of the
large trees in the EC buffer shall be 7' high minimum at planting.
2. All inverter/transformer stations shall be located at least 700' from the EC edge of pavement.
3. All chain link fencing shall be removed from the development at decommissioning.
4. Revise the easement documents to reference the appropriate parcels, to clearly show the tree
preservation area, and to indicate that neither the owner nor the tenant will remove trees from the
designated preservation area.
5. The northeastern limit of the development area shall align with the property line shared by parcels 47J
and 47M. Existing vegetation north and east of this line shall be preserved.
6. Extend on -site landscape buffers along property lines adjacent to parcels 47A, 47E, 47J, 47L and
47M.
If you have any questions concerning any of the above, please feel free to contact me.