HomeMy WebLinkAboutSDP201700062 Review Comments Final Site Plan and Comps. 2017-12-27Phone 434-296-5832 County of Albemarle Department of Community Development 401 McIntire Road, Charlottesville, VA, 22902 Memorandum To: Justin Shimp(justin(o)-shimp-engineering.com) From: Paty Saternye, Senior Planner Division: Planning Date: December 27, 2017 Subject: SDP 201700062 Riverside Village Block 1 — Final Site Plan Fax 434-972-4126 The County of Albemarle Planning Division will recommend approval of the plan referenced above once the following comments have been satisfactorily addressed (The following comments are those that have been identified at this time. Additional comments or conditions may be added or eliminated based on further review.): [Each comment is preceded by the applicable reference, which is to the Subdivision/Zoning Ordinances unless otherwise specified.] Initial Site Plan Comments (from conditional approval letter dated 12/28/16): 1. A site plan meeting all the requirements of section 32.6 of Chapter 18 of the Code. FINAL: Comment not fully addressed. See comments below. A site plan meeting all the requirements of ZMA 2016-19, its Application Plan and its Code of Development (C.O.D). Also, because Block 1 is the last portion of Riverside Village to be developed ensure that any remaining requirements and/or amenities specified for the other blocks within the development, as specified in ZMA2015-3, its application, C.O.D. and/or its proffers must be provided with this site plan. FINAL: Comment not addressed. It does not appear that any changes have been made in order to address this comment. Either revise the site plan to address this comment or provide information to the plan reviewer where on the site plan this information was already provided. As the last block to be developed in an Neighborhood Model District in order to evaluate this site plan all of the requirements and/or amenities specified in ZMA2015-3, its application, C.O.D. and/or its proffers tallies must be shown to have already been provided with previous site plans or shown to be provided with this site plan. Until this information is provided the site plan cannot be evaluated for conformance with the ZMA. Therefore, charts must be provide, and expanded from what was provided with the ZMA approval, to show what has been already built and/or platted for the other blocks and what is being proposed with this block. Revise the final site plan to provide the required information. Address the following: • Add columns to the "Minimum Green Space, Civic Areas, and Amenities by Block" chart for what has already been Built/Platted/Provided and for those Proposed with this site plan. • Ensure that all "Minimum Green Space, Civic Areas, and Amenities by Block" specified with the ZMA have been, or with this site plan will be, provided. • Revise the "Proposed Block Summary" chart to be the "Developed Square Footage Proposed" chart as shown in the C.O.D. on Sheet No. 5 of 7 including all of the information shown there, and for ALL blocks of the development. Also, expand it as specified below. • Add columns to the "Developed Square Footage Proposed" chart for what has already been Built/Platted/Provided as well as what is being Proposed with this site plan including number of dwelling units, dwelling units per acre, and square feet of commercial. • Ensure that all totals built/platted/provided or proposed in the "Developed Square Footage Proposed" chart fall within the minimum and maximum values specified for there individual blocks and for the NMD in general. Page 1 of 11 Add a "Land Use Summary" chart to the site plan. Include all of the information specified in the Application plan on Sheet No. 4 of 7 and add columns for those that are already built/platted with the previous blocks and what is proposed with this site plan for both acreage and percentage of the total site. Ensure that totals are provided at the bottom of the chart, and added to the right side of the chart. Revise the site plan to include an "Affordable Units by Type and Block" chart that includes a provided column and show that the minimum of 15% affordable dwelling units has been met (C.O.D. section Vill. Revise the site plan to include a "Landscape Treatment' chart that specifies each required treatment and includes a column that specifies in which site plan or subdivision plat the treatment was provided (C.O.D. section IX.) or if it has not vet been provided. [ZMA2016-19 Proffer #11 Provide as many affordable units within Block 1 as are necessary to meet the remaining affordable housing requirement for all of Riverside Village. It appears that only 10 affordable residential units have been provided in previously approved plans. The proffer specifies 15% affordable units. If there will be a total of 93 residential units in all of Riverside Village then a total of 14 affordable units are required and therefore 4 more affordable units must be provided in Block 1. FINAL: Comment not addressed. It does not appear that any information on the affordable units that are proposed has been added to the site plan. Revise the site plan to provide this required information. See zoning comment for more details. 4. IZMA2016-19 Proffer #2] The status of the cash proffer specified in #2 will be reviewed as construction continues. FINAL: Comment not fully addressed. The status of the cash proffer specified in #2 will be reviewed as construction continues. 5. [ZMA2016-19 Proffers] Provide the correct, final and signed version of the proffers. There was a modification made to the final version of the proffers that must be included. See the attached PDF. FINAL: Comment not fully addressed. The final, signed, and approved version of the proffers must be scanned and inserted into the plan set. Although the content of the proffers currently provided in the plan may be correct the signed and approved version is what needs to be in the site plan. 6. [ZMA2016-19] Because this is the final site plan that is required for the development ensure that all requirements and amenities specified in the C.O.D. are provided within Riverside Village. In the Final Site Plan provide the following: • The "Minimum Green Space, Civic Area, and Amenities by Block" chart for the C.O.D. must be updated to be a "Required and Provided" chart showing that all required items for all of Riverside Village have been provided or will be with the approval of the site plan (C.O.D. section VII.). • The "Proposed Block Summary" must be expanded to show all blocks, show totals for the development, and show that the development as a whole has stayed within the Minimums and Maximums for the Residential / Commercial uses (C.O.D. sections I.D. and V.). • Provide an "Affordable Units by Type and Block" chart that includes a provided column and show that the minimum of 15% affordable dwelling units has been met (C.O.D. section VI.). • Provide a "Landscape Treatment' chart that specifies each required treatment and includes a column that specifies in which site plan or subdivision plan the treatment was provided (C.O.D. section IX.). FINAL: Comment not addressed. See comments #2 & #3 above. 7. [32.7.2.3(a)] Provide in the site plan an additional segment of sidewalk parallel to Route 20 between the east entrance to the site and the east boundary line of the parcel along Route 20 (Stony Point Road). FINAL: Comment not addressed. No additional sidewalk has been added to the site plan. This pedestrian connection is required. If there are topographical challenges provide supporting documentation about the sites restraints, as well as possible solutions, and discuss them with the plan reviewer prior to the next submission. At the bare minimum a crosswalk and handicapped ramp must be provided so that a future connection will be feasible. In addition, whatever portion of the sidewalk the reviewers considers appropriate and realistic, prior to development to the east of the parcel, must also be provided. Page 2 of 11 8. [32.5.1(c) & 32.5.2(a)] Address the following: • Revise the dimensions for the existing boundaries to include bearings for each portion of the boundary and include all required curve data where appropriate. FINAL: Comment not fully addressed. Only one bearing and distance was added to the parcel information and it was for the parent parcel and not Block one. Revise the site plan to include all of the bearing and distance information for Block 1 specifically. All line and curb data is to be provided. Provide the Tax Map number for the subject parcel in the Existing Conditions sheet. FINAL: Comment addressed. • Show the setback lines in the site plan. FINAL: Comment not fully addressed. Address the following: o Use two different linetypes for the Build -to lines and the parking setback lines. o The parking setback from route 20 is incorrect. It appears to be shown at 33' instead of 50'. Revise this line. o No parking setback line is shown from Road A. Add the parking setback line for Road A to the site plan. o The side setback line adjacent to TMP 78-58A (Elks parcel) appears to be incorrect. It scales at about 6' instead of 5'. Revise this setback line. o Add a label and leader for the side setback line adjacent to TMP 78-58A. Since the building and parking setbacks are identical along this propertv line include the Parking setback information in this same label. o No rear setback line appears to be provide on the site plan. Add the line and a label and leader to specify its location. o Revise the site plan to provide both types of setback lines (parking & building) along the boundary with TMP 78G-2G-28. • Provide all of the required "Abutting Parcel Information" including the names of owners, zoning district, tax map and parcel numbers and present uses. FINAL: Comment not fully addressed. Only TMP 78-58A's parcel information has been provided. Address the following: o Revise the plan to include the abutting parcel information internal to the NMD. o Revise the plan to include the abutting parcel information for TMP 78-8A. • The "Sheet Index" on the cover sheet includes a sheet that is not part of the initial site plan. A "lighting plan & details" sheet was not included. Also, the "site and utility details" sheet should be labeled as C7 and not C8 in the "Sheet Index". FINAL: Comment not fully addressed. Address the following: o Change the sheet title for C3 to be "Existing Conditions and Demo Plan" so that it matches the information shown on the cover sheet. o Although C3 is specified to be "Existing Conditions and Demo Plan" the demolition information is not included or not obvious. Also, the landscaping in the private landscaping easement on Road A appears to not be shown in the landscape plan and vet is not noted as being removed on this sheet. • Revise the boundary information to include the required datum reference for the elevation. '7INAL: Comment addressed. 9. [32.5.2(b)] Address the following: Provide the gross residential density for Block 1. FINAL: Comment addressed. Revise the square footage of commercial uses so that they are consistent within the "Proposed Use" and "Parking" portions of the site data. There appears to be a typo in the "Parking" calculations. FINAL: Comment addressed. Page 3 of 11 Revise the maximum amount of impervious on the site to include the patios or specify the patios as materials that are pervious. FINAL: Comment not fully addressed. Where the patios are included in the calculation is not specified. The "new pavement" seems to have been reduced by about 5,000 and the "new sidewalk" increased but about 3,000. Overall the total impervious area appears to have decreased despite the response to the comment being that "The amount of impervious area has been revised to include the patios". Revise the calculations to show specifically which area of the calcs include the patios and either revise the totals or provide the plan reviewer with information to explain why the impervious was reduced when large areas were added. Revise the "new pavement" square footage on the coversheet to match the "paved parking and vehicular circulation area" or clarify why these numbers should not be the same. The existing paved area connecting the two existing roads/alleys should be included since it is part of Block 1. This should be included in the calculations. FINAL: Comment not fully addressed. The "new pavement" on the coversheet and "paved parking and vehicular circulation area" on the landscape plan still to not match. Revise the plan in order to correctly represent this information in both locations. 10. [32.5.2(b), 32.5.2(e), 32.5.2(p), 32.6.20) & 32.7.9.4(c)] Provide a full landscape plan that provides all required landscaping, calculations and meets the buffer & landscaping requirements for 32.7.9 and the ZMA Code of Development. Address the following: • The existing paved area connecting the two existing roads/alleys should be included in the "parking and vehicle circulation area" since it is part of Block 1. Included it in the calculation or clarify why is should not be included. FINAL: Comment not fully addressed. The "new pavement" on the coversheet and "paved parking and vehicular circulation area" on the landscape plan do not match. Revise the plan in order to correctly represent this information. • Revise the provided landscape canopy so that it is the same or greater than the required tree canopy. FINAL: Comment not fully addressed. Address the following: o The total area of the site on the coversheet and the landscaping sheet do not match. Revise accordingly and update calculation. o The street trees along Route 20 were planted, approved, and included in the calculations for SDP2014-43. Those plantings cannot be changed without amending that site plan. o Since the street trees were part of a previously approved site plan can cannot be utilized in the canopy calculation also for this site plan. Since this is a mixed -use site, and not purely commercial, utilize the canopy calculation for residential uses. FINAL: Comment addressed. There is a note just above the "Landscaping Required:" calculations that states "Approved Landscape Plan 1" = 30"'. However, this landscape plan in not yet approved and the scale bar in the lower right corner of the page shows a scale of 1" = 20'. Revise this note or clarify why all of part of it is correct. FINAL: Comment addressed. Revise the landscape plan so that, as III. D. states, the plazas are a balanced mixture of hardscaping and landscaping and as stated in ll. they have planting beds, benches and paving to create harmonious areas for people to congregate. FWAL: Comment addressed. There are benches specified in the C.O.D. for the patios in Block 1 that are not shown in this site plan. Provide the required benches. o III. D specifies a minimum of two benches per plaza. o VII. specifies at least four benches in one of the plazas. FINAL: Comment not fully addressed. The two central plazas do not have any labels specifying where benches may be located, although there is some linework that may represent built in benches. Add labels and leaders and ensure that the two central plazas also meet the bench requirement. Page 4 of 11 • Revise the landscape plan to include the flowering ornamentals specified for the plazas in section IX of the C.O.D. They should be evenly spaced around the plaza. FINAL: Comment not fully addressed. There appear to be only "ornamental deciduous trees" in the two central plazas. Revise the landscaping in the plazas so that all four of the plaza's meet this requirement. • Revise the landscape plan to include the 24" tall (at planting) shrubs specified for the plazas in section IX of the C.O.D. They are to be interspersed between the trees and used to screen the parking. FINAL: Comment not fully addressed. Add a label and leader for the three "FM" shrubs on the far east front of the building. As stated in II. the plaza furthest to the east will be a focal point aligned with Road "C" providing a visual and pedestrian connection between Stony Point Road and the Rivanna River. Therefore the pedestrian connection should be extended through the plaza and connect directly to the sidewalk along route 20. MNAL: Comment addressed. • Provide a clear, and safe, delineation for the pedestrian connection that crosses the parking lot and connects the plaza to the rest of Riverside Village. FINAL: Comment addressed. • Revise the landscape plan to include the perimeter shade trees, ornamental trees and screening shrubs specified for the parking areas in section IX of the C.O.D. Ensure that there are at least the number specified in the C.O.D. FINAL: Comment not addressed. Address the following o Provide the required perimeter large shade trees. There are no perimeter large shade trees on the north side of the parking lot and only one to the east. o Provide the required ornamental trees in the islands and around the pedestrian crossings within the parking lot. • Revise the landscape plan to include the evergreens, ornamental trees and shrubs specified in section IX of the C.O.D. along the foundations of the buildings. FINAL: Comment not fully addressed. Provide additional shrubs and the required evergreen and ornamental trees along the exposed foundation and around window and door opening (see "Other" portion of C.O.D. section). • Revise the landscape plan to include the Ornamental trees, shrubs and ornamental grasses specified in section IX of the C.O.D. at the "Entrance — Block 1". FINAL: Comment not addressed. Address the following: o These plantings were shown in a previously approved site plan. In order to remove them, or replace them with anything different, the site plan in which they were shown and approved must be amended. Until that site plan is amended this site plan that shows them being removed cannot be approved. o Landscaping cannot be utilized two meet the canopy calculation in two different site plans. o Show all existing landscaping on the site in the existing conditions sheet. o No landscaping is being provided to meet this C.O.D. requirement. This requirement must be met before the site plan can be approved. o If landscaping is proposed in a different area than shown on the previously approved site plan than the existing landscape easement for those plantings must be revised to include the modified planting area. Page 5 of 11 • There are existing plantings near the entrance from Route 20 that are being impacted by a proposed plaza. Specify how these previously approved plantings will still be provided, how they will be preserved, and if necessary where they will be relocated to while still meeting the requirements they were meant to meet. FINAL: Comment not fully addressed. These plantings are required in C.O.D. IX for the "Entrance — Main Road". Address the following: o These plantings were shown in a previously approved site plan. In order to remove them, or replace them with anything different, the site plan in which they were shown and approved must be amended. Until that site plan is amended this site plan that shows them being removed cannot be approved. o Landscaping cannot be utilized to meet the canopy calculation in two different site plans. o Show all existing landscaping on the site in the existing conditions sheet. o No landscaping is being provided to meet this C.O.D. requirement. This requirement must be met before the site plan can be approved. • There are existing plantings at the corner of Route 20 and Trialside Drive that are not shown on the site plan. Show these plantings and include them in the schedule for the existing landscaping. Also, show how these plantings will be preserved. FINAL: Comment not fully addressed. These plantings were shown in a previously approved site plan. In order to remove them, or replace them with anything different, the site plan in which they were shown and approved must be amended. Until that site plan is amended this site plan that shows them being removed cannot be approved. • There appear to be notes about "existing" landscaping that does not yet exist. Revise the notes so that they correctly specify in which previously approved site plan the plantings were included and in what time frame they will be provided. FINAL: Comment not fully addressed. The plantings on the east side of the lot, adjacent to TMP 78-58A, have a note that specifies that they were required with SUP2015-00038. They were actually required with SDP2014-43. Address the following: o Revise the note to state "SDP2014-00043" instead of "SUB2015-00038". o These plantings were shown in a previously approved site plan. In order to remove them, or replace them with anything different, the site plan in which they were shown and approved must be amended. Until that site plan is amended this site plan that shows them being removed cannot be approved. o Landscaping cannot be utilized to meet the canopy calculation in two different site plans. o Show all existing landscaping on the site in the existing conditions sheet. o No landscaping is being provided to meet this C.O.D. requirement. This requirement must be met before the site plan can be approved. • If the plantings in the clouded area on the east side of Block 1 are meant to meet the "Northern Buffer" requirements specified in section VII of the C.O.D. for Block 1 then include information on those plantings. If they were specified in a previously approved site plan then they could be included in a separate "existing" landscape schedule in this site plan in order to differentiate it from plantings that will be provided with this site plan while still supplying the information required for review. FINAL: Comment addressed. • Provide parking lot screening trees and shrubs between the existing residential units and open spaces in Block 2 and the Block 1 parking lot. FINAL: Comment not fully addressed. There is a gap in landscaping between the biofilter and the parking lot. A residential lot is just on the other side of the biofilter from the parking lot. • Provide parking lot screening shrubs to the west side of the parking lot. FINAL: Comment not fully addressed. Additional screening from the road is required in this area. • Provide landscape screening for the dumpster locations. FINAL: Comment not fully addressed. Address the screening of the eastern dumpster. • tinow all required landscaping in the Lanciscape Plan and Landscape bcheaiu€e(s). FINAL: Comment addressed. Page 6 of 11 • Include all landscaping in the landscape schedule(s) and provide all required information on the landscaping in that table. FINAL: Comment not fully addressed. Provide "Planting Type" for all proposed trees and shrubs and ensure that the plat is categorized properly. • Revise the required and provided landscaping calculations to accurately represent all requirements of the zoning ordinance, the ZMA and the C.O.D. FINAL: Comment not fully addressed. Address the following: o Provided the calculations for both the required and the provided Large Shade Street trees (C.O.D. IX Street frontage). o Provide a count of the required and provided required ornamental along Route 20 (C.O.D. IX Street frontage). At this time no ornamental trees are shown alonq the street. The C.O.D., the EC guidelines, and previously approved site plan all specify ornamental trees interspersed along the road. Provide the required trees. o Provide a calculation for the provided landscape area. Please note that the landscape area is the area of landscaping beds and not the canopy of the trees in the beds (32.7.9.6). o Provide a count of the canopy provided that does not include any canopy previous utilized to meet the canopy requirement on previously approved site plans. See other landscape comments about the need to amend previously approved site plans. o Do not include proposed trees in the canopy count if they area outside of the project area. The proiect area appears to be the parcel for Block 1 and does not appear to include the two pocket parks that where part of Block 2. If these pocket parks are supposed to be part of the project, and utilized to plant required landscaping, include them in the project area and the "Total Area" utilized in the canopy calculation. o Ensure that all C.O.D and zoning ordinance landscaping requirements are met. • Ensure that the different species of existing and proposed plant and plant types are differentiated by symbol and/or label. FINAL: Comment addressed. • Ensure all species of trees and Shrubs conform to the "Native Plants for Virginia Landscaping" list (C.O.D. Section IX. Restriction (1)). FINAL: Comment not fully addressed. It appears that half of the tree and shrub, as well as grass and groundcover, species specified are native. Ensure all species of trees and Shrubs conform to the "Native Plants for Virginia Landscaping" list as specified in C.O.D. Section IX. Restriction (1). Ensure that the required street trees are provided along Trailside Drive. FINAL: Comment addressed. • On the landscape plan identify the existing trees that have previously been planted to meet the requirements of previously approved site and subdivision plans for Riverside Village. Provide a landscape table for existing trees so that they can be reviewed for meeting requirements of the Code, ZMA and/or C.O.D. FINAL: Comment not fully addressed. Landscaping from previously approved site plans may not be removed or replaced with different plantings without amending the previously approved site plan. • Provide a conservation checklist, conservation details, and tree protection fencing to ensure that the existing trees that area to remain area preserved. FINAL: Comment addressed as long as existinq landscaping is still to be replaced. Consider the comments above. Provide the required information if any existing landscaping is to remain. 11. [32.5.2(i) & (n)] Address the following: • Dimension the width, and centerline radii, and corner radii of the proposed eastern entrance and ensure that the entrance road meets or exceeds minimum road requirements. FINAL: Comment addressed. More information has been provided. • Provide all road and alley names, and their letter designation from the Application Plan, on the site plan. FINAL: Comment not addressed. None of the roads or alleys internal to Riverside Village have names provided on the site plan. Revise the site plan to show them as specified. Page 7 of 11 • Provide all access easements. FINAL: Comment not fully addressed. Address the following: o Submit for review all easement plats. o Submit draft deeds of easement for all proposed easements. o Easement plats and deeds must be approved by the County, signed, and recorded prior to approval of the site plan. o Provide an access easements along the main parking access, closest to the proposed building. o Revise the "New v/w access easement to be dedicated" label to more clearly state what the access easement is for and provide reviewer information on what the "v/w" means. • Provide trash containers and dimension the dumpster pad. FINAL: Comment not fully addressed. Address the following: o Clarify is both dumpster pads will be built according to the Dumpster Pad Enclosure Detail on sheet C10. The enclosure for the one to the east does not have a reference to the detail and is of a different design. o Ensure that the Dumpster pads both will be "enclosed" and meet the size requirements. Provide associated details and labels. o Revise the dumpster pad detail to not have the reduced viewport image of another detail within it. • Show the location of any outdoor lighting. FINAL: Comment not fully addressed (32.6.2(k) & 4.17). Address the following: o There is one spot, along the property line with Route 20, where the foot candles are above'/z. This may be an error in the lighting plan since no light fixture is directly adjacent to those numbers. Revise the sight plan to ensure that at any property line adiacent to a road the footcandles are 'h or less. o The items circled in the Philips Gardco detail do not match the catalog number specified in the Schedule. 135LA-6470 is specified in the schedule and 215LA-641A is circled in the detail. Ensure that the schedule and detail match. o The items circled in the WAC Lighting "Caliber" sheet does not match those shown in the schedule. The schedule shows "BZ" and the sheet shows "AL". Ensure that the schedule and detail match. o Revise the note under the schedule to specify that the other lighting fixtures can be found on sheet C12. o Does note number 4 mean that light fixture "D" is not included in the photometric diagram? Clarify why this cannot be done, or if it was just not able to be accomplished before first submittal. o Clarify the location of lights B9, B22, B23, B24, & B25. Revise the hatch for the walkways. There appears to be portions not hatched. FINAL: Comment addressed. • Provide required Loading area(s). FINAL: Comment not addressed. (4.12.13 & 4.12.18) No loading spaces appear to be provided and no loading space calculation is shown. Provide the required loading space(s) and an associated calculation. • If there is to be any new sign for the proposed use(s), on the final site plan depict and label the sign location. (Depicting the sign on the final site plan is not approval of the sign location or type). FINAL: Comment not addressed. No information is provided for two structures at the entrance of Road A onto Route 20. Label the existing monument sign and specify what the angled structure next to the existing sign represents. Is it existing or proposed and what is it. Provide information on the site plan about both of these structures that have no labels. • Show all proposed signage on the site plan. FINAL: Comment not fully addressed. See engineering comments. • Revise the parking calculation. There appears to be a math error. FINAL: Comment addressed. Page 8 of 11 12. [32.5.20)] Revise the plan such that the existing pipes are visible. It appears some of the storm pipes and sanitary sewer pipes are hidden behind the hatching for the parking lot and cannot be seen. Also, the drainage system should include the direction of flow on all pipes and watercourses with arrows. FINAL: Comment not fully addressed. Provide direction of flow on the existing conditions sheet as well. This includes pipes and ditches. 13. r32.5.2(k, Provide the proposed drainage facilities and channels. Include the direction of flow on all pipes channels and watercourses with arrows. ► INAL: Comment addressed. 14. [32.5.2(1) & 32.6.1(e)(5)] Provide the location of any existing or proposed utilities and utility easements including telephone, cable, electric and gas. Indicate the deed book and page reference for all exiting utility easements located on the property. FINAL: Comment not fully addressed. Address the following: • An underground electric (UGE) line appears approximately parallel to Route 20 and near the road on the existing conditions sheet. It is not shown in the Utility Plan. • No easement information is provided for this electric line. No other electric easement appears to be proposed. Provide information on any existing or proposed electrical lines. • Confirm that not telephone, gas or cable utility lines are existing or proposed on the site. 15. [32.5.2(n)] Provide the required handicapped parking signage. FINAL: Comment not fully addressed. Provide the required handicapped signage detail in the site plan. 16. 132.5.2(p) & 32.7.9.4(b)] Preserve all existing trees that are to remain. Include the following: • Areas and other features shown on landscape plan. The landscape plan shall show the trees to be preserved, the limits of clearing, the location and type of protective fencing, grade changes requiring tree wells or walls, and trenching or tunneling proposed beyond the limits of clearing. • Conservation checklist. The applicant shall sign a conservation checklist approved by the agent to ensure that the specified trees will be protected during construction. Except as otherwise expressly approved by the agent in a particular case, the checklist shall conform to the specifications in the Virginia Erosion and Sediment Control Handbook, pages III-393 through I11-413, and as hereafter amended. FINAL: Comment not addressed. Address the following: • All existing landscaping along Route 20 and Road A cannot be removed or replaced with something different without amending SDP2014-43 which is the site plan in which they were established. They are a requirement of that previous site plan and the site would be in violation if they were removed or replaced with different plantings. They could be temporarily removed during construction and replaced, or replaced with the exact same plantings in the same location, if they are damaged but they cannot be permanently removed or replaced without amending SDP2014-43. • Since the existing landscaping is part of SDP2014-43 it cannot be used to meet requirements of this proposed site plan. • The landscaping is now shown on sheets C11 & C12, not C9 & C10 17. [Comment] Address the following: Provide reference benchmarks for the survey. FINAL: Comment addressed. • - Indicate the available sight distance for the new entrance onto Route 20. FINAL: Comment not addressed. There does not appear to be linework or labels on the site plan for the proposed entrance onto Route 20. Either revise the site plan to include the required information or specify to plan reviewer where on the drawing it was already located. Page 9 of 11 • Label the maximum height of all retaining walls. FINAL: Comment not fully addressed. Although the retaining walls now appear to be labeled there is at least on location where the height of the retaining wall is above 6', which is not allowed in the Entrance Corridor. Rework any walls above 6' in height, and their associated grading, to ensure that not retaining wall is above Wand that if necessary additional walls are terrace, spaced, and planted as required. Indicate the deed book and page references for all existing utility easements located on the property. F€NAL: Comment addressed. •F Provide a copy of all off -site easements, or letters of intent to grant them from off -site property owners. FINAL: Comment not vet addressed. Provide a copy of all off -site easements, or letters of intent to grant them from off -site property owners. 18. [Cor ment,y Revise the "Parking Area Pavement Section" to fix the portion of the section that has shifted. FINAL: Comment addressed. 19. [Comment] The site plan has been submitted to Virginia Department of Conservation and Recreation (DCR) for review of its impact on the Dam Break Inundation Zone (DBIZ). Any comments received by the reviewer will be forwarded to the applicant once they are received. UPDATE: Comment above still valid. Also, show the state Dam Break Inundation Zone (DBIZ) line on the site plan. FINAL: Comment not addressed. Comment above still valid. Show the state Dam Break Inundation Zone (DBIZ) line on the site plan. 20. [Comment] See the attached comments from the majority of the other SRC reviewers. Fire/Rescue and RWSA comments will be forwarded to you once they have been received. UPDATE: See the attached comments from all of the other SRC reviewers. FINAL: See the attached comments from the majority of the other reviewers. Others will be forwarded to you when they are received. 21. [UPDATE: NEW COMMENT: ZMA2016-19 C.O.D. VIII. A.1 Form, Massing and Proportion of Structure. Ensure that building facades facing a street do not exceed more than 80' in length without a change in vertical plane. See C.O.D. Vill. A. for more details on the requirement. FINAL: Comment not fully addressed. Provide scaled elevations and building floor plans with the next submission of the final site plan. Ensure that they show that the building meets this C.O.D. requirement. Additional comments for Final Site Plan: 22. [Commentl Revise the protect number on the coversheet to be SDP201700062. 23. [Comment: 32.5.1(c) & 32.6.1(e)(1)1 Revise the note on the coversheet of the site plan for setbacks to specify the correct page of the ZMA documents in which the setback information is specified. 24. [Comment: 32.5.2(b)l Specify the specific height and number of stories for each of the buildings. 25. [Comment: 32.5.2(b), 32.5.2(e), 32.5.2(p) & 32.7.91 Hatching of parking planting areas should either be changed to something more obviously representing landscape planting areas or a label and a leader should specify "Landscaping Bed Typ." For those areas. 26. [Comment: 32.5.2(n)l There are labels for tops of walls (TW) that do not have a corresponding bottom of wall (BW) value and there are some that have leaders that are not pointing at walls. Ensure all required wall information is provided and that all labels and leaders are pointing at the appropriate walls. Page 10 of 11 27. Mommentl The date in the title block is incorrect. This plan was submitted on10/30/17, with an official submittal date of 11/06/17, and the title block date is from June. Ensure that a correct revision date is provided, in the revision box, before resubmission. 28. fCommentl Revise to remove the curb that is shown to be blocking the access way between the residential units in Block 2 and the biofilter, or clarify with plan reviewer why it should stay. 29. fCommentl Revise the width of the parking lot access ways to have sufficient width in all areas for two way traffic. There is at least on location where the drive aisle appears to be reduced down to only 20' wide. This is not sufficient for parking aisle where the spaces are 9' wide. 30. fCommentl Revise the corners of the west most parking planting island to have sufficient radii. 31. fCommentl Revise the hatch in the "Flush Curb to CG3 Nose". There are two different hatches. If the 2"d hatch is to remain clarify with a label what it represents. 32. fCommentl See the attached comments from other reviewers. Approval of each reviewer is required before site plan approval. Staff has provided references to provisions of Chapter 18 of the Code of the County of Albemarle. The Code is kept up to date by the County Attorney's office. The Code may found on the County Attorney's website which may be found under "Departments" at Albemarle.org. In accord with the provisions of Section 32.4.3.5 of Chapter 18 of the Code if the developer fails to submit a revised final site plan to address all of the requirements within six (6) months after the date of this letter the application shall be deemed to have been voluntarily withdrawn by the developer. Please contac7*nfo y ern in the Planning Division by using psaternye(Qalbemarle.orq or 434-296-5832 ext. 3250 for furthio . Page 11 of 11 Review Comments for SDP201700062 IFinal Site Development Plan Project Name: Riverside Village Block 1 Date Completed: Friday, December 15, 2017 DepartmentlDivisionfAgency: Review Sys: Reviewer: Rebecca Ragsdale CDD Zoning No Objection El Page: County of Albemarle Printed On: '1212'U20'17 Review Comments for SDP201700062 lFinal Site Development Plan Project Name: Riverside Village Block 1 Date Completed: Monday, December 04, 2017 DepartmentlDivisionfAgency: Review sus: [Bobby Jocz � CDD En ineerin Requested Changes Reviewer: b]+ 9 9 Comments on plans dated? 1_ Update plan revision date, still includes revision date of IP_ _ Update submittal ID to that related to the current F P ( DP20170006 )- 3_ WPO plan must be approved prior to FP approval- 4- Computations must be provided for stormsewer design- 5- Include owner/parcel information for adjacent parcel 78-8A_ 6_ Traffic control signs/stop bars needed for intersections of proposed parking lot travel ways and existing private alleyslintersection with Trailside Drive- 7- Safety railing must be provided for retaining walls taller than 4'_ Engineered designs, with PE seal and signature, must be provided for retaining walls greater than 4'_ Building permit may also be required- 8- Ensure hatching/symbols are consistent throughout plans for similar features (i_e_ exposed aggregate concrete has 3 different hatch types associated with it)_ 9_ Detectable surface should be provided at crosswalks prior to crossing the travelway_ 10_ Isle widths adjoining 9118 parking must be 24'_ Isle width adjacent to location of biofilter tapers to 20'_ Please correct 11_ Provide approvable radius for cubing where the west alleyway adjoins proposed northern parking lot travelway (to the southeast of the biofilter)_ The sharp angle is not approvable as shown_ 12_ All curb and gutter must conform to County Code Ch 18 section 4.1 _16_ Gutter shall be provided where necessary to control stormwater runoff_ 13_ [Sheet C3] Identify areas with critical/managed/preserved slopes_ 14_ [Sheet C5]Double check TVV/BW elevation callouts, some appear to be switched_ 15_ [Sheet C5] 16_ [Sheet C5] Identify hatching located leading up to structure All on parcel 78-8A_ This hatching type is not called orit or identified in key_ 17_ [Sheet C5] Evaluate potential drainage issue adjacent to the easternmost handicap parking space_ It appears due to grading water will pond at the corner where the CG-12 and curb and gutter meet_ 18_ [Sheet C5] Identify hatching used on parking lot islands_ Is this just being used to differentiate between island and parking lot? 19_ [Sheet C5] identify location of any proposed ditches/conveyance channels, call out to related det3ll.+calcr1latl017s_ 0_ [Sheet C6] Drainage easements must be provided for stormsewer conveying water off of VDOT ROW_ Easement plats and Deeds must be recorded_ 1 _ [Sheet C7] Stormsewer profiles identify two structures as A6A_ Title identified profile as showing sections from Al -All when onlyA4-All are shown_ Please correct_ 22_ [Sheet C8] Provide engineering detail for drop inlet associated with structure A11_ 23_ [Sheet C9] Rename sheet to better describe contents_ No roadway profiles are shown_ Incorrect scale bar included for figure 31C9_ Provide horizontal scale for Figures 1&2_ 4_ [Sheet Cll] low maintenance groundcover must be provided on slopes greater than 3.1. Indicate location and type_ Page: County of Albemarle Printed On: '1212-V20'17 COMMONWEALTH of VIRGINIA DEPARTMENT OF TRANSPORTATION 1601 Orange Road Culpeper, Virginia 22701 Charles A. Kilpatrick, P.E. Commissioner November 28, 2017 County of Albemarle Department of Community Development 401 McIntire Road Charlottesville, VA 22902 Attn: Paty Saternye Re: Riverside Village -Block I- Final Site Plan SDP-2017-00062 Review #1 Dear Ms. Saternye: The Department of Transportation, Charlottesville Residency Transportation and Land Use Section, has reviewed the above referenced plan as submitted by Shimp Engineering, dated .Tune 16, 2017, revised October 12, 2017 and offers the following comment: Land Use 1. Please add the WP-2 detail standard to the plan set. 2. PIease show an entrance/left turn lane plan that dimensions the tapers and shifts necessary for the additional lane. 3. Please maximize storage for the new left turn lane; this should include the elimination of the taper. 4. Please mill and overlay re -stripping areas. S. Please show more detail to plan set toward the east of Stoney point road. Please provide a copy of the revised plan along with a comment response letter. If further information is desired, please contact Willis C. Bedsaul at 434-422-9866. A VDOT Land Use Permit will be required prior to any work within the right-of-way. The owner/developer must contact the VDOT Charlottesville Residency Land Use Section at (434) 422-9399 for information pertaining to this process Sincerely, ����att✓ ti)i(ore, Adam J. M P.E. Area Land Use Engineer Charlottesville Residency VirginiaDOT.org WE KEEP VIRGINIA MOVING Review Comments for SDP201700062 lFinal Site Development Plan Project Name: Riverside Village Block 1 Date Completed: Monday, November 27, 2017 Department1DivisionfAgency: Review : Reviewer: I Heather McMahon U DDDARB Requested Changes El At its meeting on 1110117, the ARB approved a Certificate of Appro pri at e n e s s forARB-017-11: Riverside Village, Block 1, Final Site Development Plan pending staff administrative approval of the conditions listed in the staff report, as follows: 1- Vary the tree and shrubs species throughout the entirety of the site- _ Illustrate the number of benches in each of the plazas_ Ensure that each plaza holds a minimum of two benches and that one plaza holds at least four benches- 3- Provide a roof plan and elevations that show roof -mounted mechanical equipment locations and sizes_ Show how visibility of all equipment will be eliminated- 4- Correct the standard mechanical equipment note on the architectural drawings- 5- Ensure that the kelvins emitted by all light fixtures are consistent throughout the site- 6- Choose either black or bronze for the Model B bollard lighting and specify choice on the lighting plan- 7- Consider adding ornamentals between the large shade trees (London Plane trees) proposed for the EC frontage- 8- Retaining walls six feet and higher must be terraced and planted_ Specify retaining wall material- 9- Clarify the wall-like element on Sheet C4, which is near the curved monument sign/wall in the southeast corner of the block, near the throat of Trailside Drive_ 10_ Show adequate tree protection for any existing trees to remain on the site during construction 11_ Add all drawing and revision dates as well as correct sheet numbers to the site plan set and to the architectural drawings_ Correct Sheet C11 title 'Existing Landscape Plan," to 'Landscape & Lighting Plan Details Page: County of Albemarle Printed On: '1212'U20'17 Review Comments for SDP201700062 lFinal Site Development Plan Project Name: Riverside Village Block 1 Date Completed: Monday, November 13, 2017 Department1DivisionfAgency: Review Sys: Reviewer: Shawn Maddox FJ Fire Rescue H Requested Changes 1 _ No fire department connections shown on the plans_ It appears each building will be sprinklered so FDD must be shown and located within 100' of afire hydrant_ The one hydrant provided in the open space is not easily accessible and WOLIld require lengthy hose lays just to get around all of the parking spaces- _ Add a note that a knox box will be required and location to be coordinated with the fire marshal s office- 3- Afire flow test will be required prior to final acceptance_ Based on building square footage and an estimation of constrriction type the fire flow requirement is 1,500 gpm_ 4_ Hydrant spacing - based on the estimated fire flow fire hydrants should be located on an approximate 500' spacing, with no more than 250' feet of distance on any road to a hydrant_ A hydrant should be provided closer to the travel way serving the building which will assist with the FDD to hydrant distance requirement_ Page: County of Albemarle Printed On: '1212'U20'17 APPLICATION# TMP: County of Albemarle Department of Community Development 401 McIntire Road, North Wing Charlottesville, Virginia 22902 PLAN REVIEW COMMENTS - E911 SDP201700062 078G00001000A0 DATE: 11/9/2017 FROM: Elise Kiewra ekiewra@albemarle.org Geographic Data Services (GDS) www.albemarle.org/ads (434) 296-5832 ext. 3030 This site will require a one (1) new private road name for the parking/throughway area that connects Rt20 and Trailside Dr. Per Sec. 7-200-B of the County's Road Naming and Property Numbering Ordinance (Page 2 of PDF). "It is intended by this article that all roads within the county which serve or are designed to serve three (3) or more dwelling units or business structures shall be named." Please review the procedures in the Road Naming and Property Numbering Manual to decide upon a road name. We recommend providing three (3) candidate names for each road to our office for review, in case your first choices are not acceptable. A PDF version of the Ordinance and Manual can be found here: httns://www.albemarle.ora/unload/imaaes/Forms Center/Departments/Geoaraphic Data Service s/Forms/Road Namina and Prooertv Numberina Ordinance and Manual.odf Please consult the County's Road Name Index to check your road names prior to submittal. The Index can be found here: http://www.albemarle.org/albemarle/upload/images/webapps/roads/ Parcel and mapping information can be found here: http://gisweb.albemarle.org/ If you should have any questions, please do not hesitate to contact our office. Review Comments for SDP201700062 IFinal Site Development Plan Project Name: Riverside Village Block 1 Date Completed: DepartmentIDivisionfAgency: Review Sys: Reviewer: Alexander Morrison ADSA Pending Page: County of Albemarle Printed On: '1212'U20'17 Review Comments for SDP201700062 IFinal Site Development Plan Project Name: Riverside Village Block 1 Date Completed: Thursday, November 16, 2017 DepartmentlDivisionfAgency: Review Sys: Reviewer: Michael Dellinger CDD Inspections No Obje-Ction Page: County of Albemarle Printed On: '1212'U20'17