HomeMy WebLinkAboutWPO200600064 Review Comments 2006-1-16 SY pF:1 fgF,'
sis )t-
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road,Room 227
Charlottesville,Virginia 22902-4596
Phone(434)296-5832 Fax(434)972-4126
Project: Poplar Glen 2 (SDP200600092, WP0200600064)
Plan preparer: Terra Concepts [fax 295-2103]
Owner or rep.: Weather Hill Development LLC [fax 296-2560]
Plan received date: 09 Jan 2006
Date of comments: 16 Jan 2006
Reviewer: Jonathan Sharp
A. Final site plan, Road Plan,Drainage Plans(SDP200600223)
The fmal site plan and road plans have been approved. The road bond is set at$281,660.
B. Stormwater Management Plan(WP0200600057)
The stormwater management plans have been approved. The stormwater bond is set at$560,000.
C. Erosion Control Plan(WP0200600057)
The E&S plan has been approved. The E&S bond is set at $41,000.
If you have any questions,you can reach me, Jonathan Sharp, at(434)296-5832 ext. 3025, or my email:
jsharp@albemarle.org.
0VLPL- irerivatr2z"
A�,
COUNTY OF ALBEMARLE
Department of Community Development
401 McIntire Road,Room 227
Charlottesville,Virginia 22902-4596
Phone(434)296-5832 Fax(434)972-4126
Project: Poplar Glen 2 (SDP200600092, WP0200600064)
Plan preparer: Terra Concepts [fax 295-2103]
Owner or rep.: Weather Hill Development LLC [fax 296-2560]
Plan received date: 11 Aug 2006
17 Oct 2006(Revl)
28 Nov 2006(Rev2)
Date of comments: 5 Sep 2006
3 Nov 2006(Rev1)
8 Dec 2006(Rev2)
Reviewer: Jonathan Sharp
The plans for Poplar Glen 2,received on Nov 28,2006,have been reviewed. All of the previous
engineering comments have been addressed. However,we have begun looking more closely into the
design of the Contech Storm Filter systems for all of the plans coming into the County, and realized there
are some issues with the layout and sizing of the water quality system. The comments we have are below in
the Stormwater Management Plan.
Also,you are correct in stating that this project does not need to go the Planning Commission.
A.Final site plan,Road Plan,Drainage Plans(SDP200600223)
All comments have been addressed. We will come up with a bond amount for the road plan once the
stormwater situation is addressed.
B. Stormwater Management Plan(WP0200600057)
The calculations and methodologies for sizing the StormFilter Structures(and all other underground
water quality structures)have come into question as the differ between plans.
In addition,Engineering had several comments about the Water Quality System for Poplar Glen 2:
1. Engineering recommends that the water quality structures are offline from the larger drainage
areas and online only with the site area which needs to be treated for water quality. Currently,
all 24+acres of drainage area flow through(or past)the water quality system. This could cause
runoff to remain untreated and bypass the system during even a minor storm event. Having
runoff from U-Heights bypass the water quality system would help alleviate this, as would
having the offsite runoff above the development bypass the water quality system.
2. The number of cartridges required does not appear meet the number of required cartridges in
regards to Con Tech's sizing methodologies.
3. The Storm Filter box configuration does not seem to match other designs we have seen before.
(Although designs on Contech's website do not seem to match other designs we have seen
either; everything seems to be different.)The design seemed to be a concern to Joe Battiata,a
ConTech representative,who recommended a design similar to a Storm Filter System used for a
Walgreen's plan.
`"''� 'ngineering Review Comments
Page 2 of 2
24'0 FRAME
AND COVL'R
30'0 FRAME AND (SEE NOTE 4)
This design is used for cweR(T"')
(SEE NOTE 4) GRADE RING
the Walgreen's site. m